Forza FDC-1502R Manual Download Page 8

06: ECO voltage range setting

07: Bypass enable/disable

Interface

Setting

Use this menu to set the acceptable high voltage point and 
low voltage point for ECO & AECO mode by pressing 
Down key or Up key.

HS: 

High loss voltage in ECO & AECO modes.

For 200/208/220/230/240 VAC models, the setting range in 
parameter 3 is from +7V to +24V of the nominal voltage. 
(Default: +12V)
For 100/110/115/120/127 VAC models, the setting range in 
parameter 3 is from +3V to +12V of the nominal voltage. 
(Default: +6V) 

LS: 

Low loss voltage in ECO & AECO modes.

For 200/208/220/230/240 VAC models, the setting range in 
parameter 3 is from -7V to -24V of the nominal voltage. 
(Default: -12V) 
For 100/110/115/120/127 VAC models, the setting voltage 
in parameter 3 is from -3V to -12V of the nominal voltage. 
(Default: -6V)

08: Bypass voltage range setting

Interface

Setting

Parameter 3

:

 

Use it to activate or cancel the Bypass mode.

ENA

: Bypass enabled

DIS

: Bypass disabled

Interface

Setting

Parameter 2 & 3

:

 

Press the 

UP

 or 

Down

 key to choose the 

acceptable high and low voltage values for Bypass operation

HS

: High voltage adjustment in bypass mode

For 200/208/220/230/240 VAC:

230-264

: High voltage setting ranges from 230VAC to 264VAC 

as set in parameter 3. (Default: 264VAC)

LS

: Low voltage adjustment in bypass mode

For 200/208/220/230/240 VAC:

170-220

: Low voltage setting ranges from 170VAC to 220VAC 

as set in parameter 3. (Default: 170VAC)

Summary of Contents for FDC-1502R

Page 1: ...2 Y e a r w a r r a n t y...

Page 2: ...k Do not install the UPS system near water or in moist environments Do not install the UPS system where it would be exposed to direct sunlight or near a heater or heating vent Do not block ventilation...

Page 3: ...y can result in electrical shock The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance When replacing the battery make sure to use the same type a...

Page 4: ...S it will provide advanced communication and monitoring options Note The USB port and RS 232 port cannot be used at the same time CAUTION For 1 5K model to reduce the risk of re connect only to a circ...

Page 5: ...n the same LAN no matter how far they might be from the UPS 2 6 Battery replacement Service personnel only NOTICE This UPS is equipped with internal batteries and only quali ed service personnel shall...

Page 6: ...r display Load information UPS status Battery information Display Function Backup time information Overload indicator Indicates the load or the UPS output is short circuited Indicates that the program...

Page 7: ...Two parameters need to be configured in order to set up the UPS Refer to following diagram Parameter 1 it is used for the different configuration options Please refer to the table below Parameter 2 it...

Page 8: ...3 is from 7V to 24V of the nominal voltage Default 12V For 100 110 115 120 127 VAC models the setting voltage in parameter 3 is from 3V to 12V of the nominal voltage Default 6V 08 Bypass voltage range...

Page 9: ...tting Parameter 3 Sets the backup time limits for the programmable outlets 0 999 Use this setting to define the programmable outlets backup time in minutes from 0 999 in order to connect non critical...

Page 10: ...t voltage is within the voltage regulation range 3 V max the UPS will bypass voltage to loads for energy saving PFC and INVERTER are disabled in this mode When input frequency is between 40Hz and 70Hz...

Page 11: ...s connected to the UPS outlet The AC input cable is not properly connected Line and neutral conductors of UPS input are reversed The external or internal battery connection is incorrect Battery voltag...

Page 12: ...S system contains no user serviceable parts If the battery service life 3 5 years at 25 C ambient temperature has been exceeded the batteries must be replaced In this case please contact your dealer o...

Reviews: