06: ECO voltage range setting
07: Bypass enable/disable
Interface
Setting
Use this menu to set the acceptable high voltage point and
low voltage point for ECO & AECO mode by pressing
Down key or Up key.
HS:
High loss voltage in ECO & AECO modes.
For 200/208/220/230/240 VAC models, the setting range in
parameter 3 is from +7V to +24V of the nominal voltage.
(Default: +12V)
For 100/110/115/120/127 VAC models, the setting range in
parameter 3 is from +3V to +12V of the nominal voltage.
(Default: +6V)
LS:
Low loss voltage in ECO & AECO modes.
For 200/208/220/230/240 VAC models, the setting range in
parameter 3 is from -7V to -24V of the nominal voltage.
(Default: -12V)
For 100/110/115/120/127 VAC models, the setting voltage
in parameter 3 is from -3V to -12V of the nominal voltage.
(Default: -6V)
08: Bypass voltage range setting
Interface
Setting
Parameter 3
:
Use it to activate or cancel the Bypass mode.
ENA
: Bypass enabled
DIS
: Bypass disabled
Interface
Setting
Parameter 2 & 3
:
Press the
UP
or
Down
key to choose the
acceptable high and low voltage values for Bypass operation
HS
: High voltage adjustment in bypass mode
For 200/208/220/230/240 VAC:
230-264
: High voltage setting ranges from 230VAC to 264VAC
as set in parameter 3. (Default: 264VAC)
LS
: Low voltage adjustment in bypass mode
For 200/208/220/230/240 VAC:
170-220
: Low voltage setting ranges from 170VAC to 220VAC
as set in parameter 3. (Default: 170VAC)