Forza FDC-1502R Manual Download Page 4

2.3.1 Initial setup 

• For safety considerations, the UPS is shipped out from the factory with battery wires disconnected. 
• Before installing the UPS, the user must first reconnect the wires. To do so, follow the steps illustrated below.  

2-4.   UPS connections
   
2-4.1 UPS input connection

• Plug the UPS into a two-pole, three-wire, grounded receptacle only.
• Avoid using extension cords or adapter plugs.

• Connect a single line modem/phone/fax cable into the network surge-protection “IN” jack on the rear panel of the UPS.
• Connect a network cable from the OUT jack on the rear of the UPS to a port on a PC or network device such as a router.

2-4.2 UPS output connection

2.4.3 Disabling and enabling the EPO function

For socket-type outputs, there are two kinds of outputs: programmable outlets and general outlets. Connect non-critical devices 
to the programmable outlets and critical devices to the general outlets. During power failure, you may extend the backup time to 
critical devices by setting shorter backup times for non-critical devices.

To allow for unattended UPS shutdown/start-up and status monitoring, connect one end of the communication cable to the 
USB/RS-232 port, and the other end to the communication port of your PC. With the monitoring software installed, you can schedule 
UPS shutdown/start-up and monitor its status through a PC.

The UPS is equipped with an intelligent slot perfect for either SNMP or AS400 card. When installing either SNMP or AS400 card in the 
UPS, it will provide advanced communication and monitoring options.

Note:

 The USB port and RS-232 port cannot be used at the same time.

CAUTION:

 For 1.5K model, to reduce the risk of fire, connect only to a circuit provided with 20 amperes maximum

branch circuit overcurrent protection in accordance with the National Electric Code, ANSI/NFPA 70.

CAUTION:

 For 3K model, to reduce the risk of fire, connect only to a circuit provided with 30 amperes maximum

branch circuit overcurrent protection in accordance with the National Electric Code, ANSI/NFPA 70.

Rack-mount installation

The unit comes with mounting brackets for the standard 19-inch (46.5cm) rack.

CAUTION:

 Do NOT use the mounting brackets to lift the unit. The mounting brackets are only for securing the unit to the rack.

This UPS can be either placed on a desktop, mounted in a rack or installed in an upright position. Define the proper display orienta-
tion based on the configuration chosen to install this UPS.

Step 1

Remove the front panel.

Step 1

Tower installation

Allows the user to install the UPS in the upright position.

Step 2

Step 2

Connect the AC input and then
reconnect battery wires.

Step 3

Replace the front panel.

Step 1

Unfold and align the tower 
support base.

Step 2

Place the UPS vertically on
the base.

Step 3

Verify that the UPS is stable and 
firmly attached to the base.

Connect the network surge protection

Network/Fax/Phone port

The UPS has two network cable RJ45 connectors for network lines.

Keep pins 1 and 2 closed for UPS normal operation. To activate the EPO feature, remove the wire between pin 1 and 2.

Communication ports

USB port

RS-232 port

Intelligent slot

IN

OUT

Closed for UPS normal
operation

 

Summary of Contents for FDC-1502R

Page 1: ...2 Y e a r w a r r a n t y...

Page 2: ...k Do not install the UPS system near water or in moist environments Do not install the UPS system where it would be exposed to direct sunlight or near a heater or heating vent Do not block ventilation...

Page 3: ...y can result in electrical shock The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance When replacing the battery make sure to use the same type a...

Page 4: ...S it will provide advanced communication and monitoring options Note The USB port and RS 232 port cannot be used at the same time CAUTION For 1 5K model to reduce the risk of re connect only to a circ...

Page 5: ...n the same LAN no matter how far they might be from the UPS 2 6 Battery replacement Service personnel only NOTICE This UPS is equipped with internal batteries and only quali ed service personnel shall...

Page 6: ...r display Load information UPS status Battery information Display Function Backup time information Overload indicator Indicates the load or the UPS output is short circuited Indicates that the program...

Page 7: ...Two parameters need to be configured in order to set up the UPS Refer to following diagram Parameter 1 it is used for the different configuration options Please refer to the table below Parameter 2 it...

Page 8: ...3 is from 7V to 24V of the nominal voltage Default 12V For 100 110 115 120 127 VAC models the setting voltage in parameter 3 is from 3V to 12V of the nominal voltage Default 6V 08 Bypass voltage range...

Page 9: ...tting Parameter 3 Sets the backup time limits for the programmable outlets 0 999 Use this setting to define the programmable outlets backup time in minutes from 0 999 in order to connect non critical...

Page 10: ...t voltage is within the voltage regulation range 3 V max the UPS will bypass voltage to loads for energy saving PFC and INVERTER are disabled in this mode When input frequency is between 40Hz and 70Hz...

Page 11: ...s connected to the UPS outlet The AC input cable is not properly connected Line and neutral conductors of UPS input are reversed The external or internal battery connection is incorrect Battery voltag...

Page 12: ...S system contains no user serviceable parts If the battery service life 3 5 years at 25 C ambient temperature has been exceeded the batteries must be replaced In this case please contact your dealer o...

Reviews: