Forza FDC-1502R Manual Download Page 7

Interface

Setting

 

For 200/208/220/230/240 VAC, you may choose any of the
following output voltages

200:

 the output voltage is 200VAC

208:

 the output voltage is 208VAC

220:

 the output voltage is 220VAC

230:

 the output voltage is 230VAC (Default)

240:

 the output voltage is 240VAC

For 100/110/150/120/127 VAC you may choose any of the
following output voltages

100:

 the output voltage is 100VAC

110:

 the output voltage is 110VAC

115:

 the output voltage is 115VAC

120:

 the output voltage is 120VAC (Default)

127:

 the output voltage is 127VAC

3-4. Abbreviations on the LCD display

3-5. UPS parameter settings

01: Output voltage settings

Enable

Disable

Escape

High loss

Low loss

ON

OK

Site fault

EPO

Over temperature

Charger failure

Frecuency is unstable in bypass mode

EEPROM error

Fan failure

Battery replacement

Abreviation

Display content

Meaning

HS

LS

ON

OK

sf

EE

FU

ch

ep

fA

 

Parameter 2

 

Parameter 1

 

Two parameters need to be configured in order to set up 

the UPS. Refer to following diagram. 

Parameter 1:

 it is used for the different configuration 

options. Please refer to the table below. 

Parameter 2:

 it represents the setting information or 

values of each program.

02: Frequency Converter enable/disable

Interface

Setting

Activates or cancels the converter mode. 

CF ENA:

 Enable converter mode  

CF DIS: 

Disable converter mode (Default)

 

03: Output frequency settings

Interface

Setting

Use this menu to define the initial frequency on battery mode:

BAT 50:

 The output frequency is set to 50Hz

BAT 60:

 The output frequency is set to 60Hz

If the converter mode is enabled, the following options
will be available:

CF 50: 

The output frequency is set to 50Hz

CF 60:

 The output frequency is set to 60Hz

04: ECO enable/disable

Interface

Setting

Activates or cancels the ECO mode. 

ENA:

 the ECO mode is enabled

DIS:

 the ECO mode is disabled (Default)

05: AECO enable/disable

Interface

Setting

Activates or cancels the advanced ECO mode. 

ENA:

 the advanced ECO mode is enabled

DIS:

 the advanced ECO mode is disabled (Default)

Summary of Contents for FDC-1502R

Page 1: ...2 Y e a r w a r r a n t y...

Page 2: ...k Do not install the UPS system near water or in moist environments Do not install the UPS system where it would be exposed to direct sunlight or near a heater or heating vent Do not block ventilation...

Page 3: ...y can result in electrical shock The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance When replacing the battery make sure to use the same type a...

Page 4: ...S it will provide advanced communication and monitoring options Note The USB port and RS 232 port cannot be used at the same time CAUTION For 1 5K model to reduce the risk of re connect only to a circ...

Page 5: ...n the same LAN no matter how far they might be from the UPS 2 6 Battery replacement Service personnel only NOTICE This UPS is equipped with internal batteries and only quali ed service personnel shall...

Page 6: ...r display Load information UPS status Battery information Display Function Backup time information Overload indicator Indicates the load or the UPS output is short circuited Indicates that the program...

Page 7: ...Two parameters need to be configured in order to set up the UPS Refer to following diagram Parameter 1 it is used for the different configuration options Please refer to the table below Parameter 2 it...

Page 8: ...3 is from 7V to 24V of the nominal voltage Default 12V For 100 110 115 120 127 VAC models the setting voltage in parameter 3 is from 3V to 12V of the nominal voltage Default 6V 08 Bypass voltage range...

Page 9: ...tting Parameter 3 Sets the backup time limits for the programmable outlets 0 999 Use this setting to define the programmable outlets backup time in minutes from 0 999 in order to connect non critical...

Page 10: ...t voltage is within the voltage regulation range 3 V max the UPS will bypass voltage to loads for energy saving PFC and INVERTER are disabled in this mode When input frequency is between 40Hz and 70Hz...

Page 11: ...s connected to the UPS outlet The AC input cable is not properly connected Line and neutral conductors of UPS input are reversed The external or internal battery connection is incorrect Battery voltag...

Page 12: ...S system contains no user serviceable parts If the battery service life 3 5 years at 25 C ambient temperature has been exceeded the batteries must be replaced In this case please contact your dealer o...