Local Microwave Protective Detector 

“Forteza-50” 

“Forteza-100” 
“Forteza-200” 

 

Description Manual & Service Instruction 

4372-43071246-065 ТО 

 
 

 

 

 

 

 

 

 

 

 

 

                       

 

 

 

 

 

                       

 

 

 

 

 

                       

 
 

 

 

 

 

 

 

 

 

                       

 

 

 

 

 

 

                       

 

 

 

 

 

                       

 
 
 
 
 
 

 
 
 
 
 
 
 
 

 

 
 
 
 
 

2012

Summary of Contents for Forteza-100

Page 1: ...ZA 50 100 200 Please visit our internet sites www forteza com www forteza eu Page 1 Local Microwave Protective Detector Forteza 50 Forteza 100 Forteza 200 Description Manual Service Instruction 4372 43071246 065 ТО 2012 ...

Page 2: ...tor Construction 6 6 1 Rx Construction 6 6 2 Tx Construction 7 6 3 MK mounting kit 7 7 Safety Measures 12 8 Mounting Procedure 12 8 1 Requirements for the preparation of the sector and the arrangement of Rx and Tx 12 8 2 Sensor Mounting 12 8 3 Sensor Connection 15 9 Preparation of the Detector for the Operation Adjustment 20 9 1 Detector Preparation for its Operation 20 9 2 Adjustment of Tx and Rx...

Page 3: ...r continuous round the clock outdoor operation at an ambient temperature 40ºC 65 С and relative humidity up to 98 at the temperature 35 С 3 SPECIFICATIONS 3 1 The recommended length of a sector for modifications Forteza 200 10 200 m Forteza 100 10 100 m Forteza 50 5 50 m 3 2 The configuration and the dimensions of the detection zone are given in fig 3 1 and table 3 1 The detection zone is a volume...

Page 4: ...the voltage drops below 9 V Failure of Rx or Tx A fault signal is generated constantly latching till the same is rectified and indicated by break in the contacts of an individual point optoelectronic relay indicated by yellow and pink colored wires marked NC NC 3 6 The dimensions of an individual point optoelectronic relay are the maximum switching current is 0 1A the maximum voltage is 50 V the m...

Page 5: ...configuration in fig 3 1 there are given in table 3 1 its crosscuts dimensions for three performances of the detector dependency on the length of a sector with the height 0 85 m of Rx Tx mounting 5 1 2 An intruder crossing a detection zone causes the change of the signal magnitude on Rx input The signal passes through the amplifier and is compared with the value thresholds according to the algorit...

Page 6: ...ontact breaking Alarm signal open condition Tamper state of Rx the contacts of the tamper circuit are opened 5 3 3 The receiver control device realizes the receipt and the indication of alarms The detector operates with the receiver control devices providing the check of the relay contacts 5 3 4 During the operation the remote control checks the detector efficiency The constant voltage 5 30 V for ...

Page 7: ...ntrols adjustment and indication elements are absent three wire cables are used instead of cable 8 6 3 MK mounting kit 6 3 1 Mounting kit includes two brackets and four buckles for the mounting on the support of Rx and Tx 1 support 1 item 8 cable 1 item 2 bracket 1 item 9 ring 1 item 3 figured washer 2 items 10 nut M6 1 item 4 base 1 item 11 washer 6 2 items 5 enclosure 1 item 12 bolt M6 16 1item ...

Page 8: ...etector constantly upgrades their quality and reliability That s why in some lots of detectors one can find design modifications unspecified in the documents delivered with the detectors Nevertheless the main specifications are valid 1 indicator PROTECTION 2 threes holding MIN MAX 3 socket TEST 4 AGC button 5 tamper circuit 6 marking of cable cords ...

Page 9: ...00 mm If the upper part of the fence is not protected with barbed wire it is recommended to use the bracket of 350 mm 2 The height of Rx and Tx units for the protection of the fence upper part is equal to the fence height 100mm 3 The dimensions and materials of the fence are not specified It is necessary to provide the fence rigidity 4 The detection zone dimensions B and H are given for the correc...

Page 10: ...JSC FORTEZA FORTEZA 50 100 200 Please visit our internet sites www forteza com www forteza eu Page 10 1 fence 4 washer 6 1шт 2 bracket 1шт 5 nut М6 1шт 3 figured washer 1шт 6 ring 1шт Fig 6 4 ...

Page 11: ...er 2items 9 nut М6 2items 4 bracket fastener 1item 10 washer 6 4items 5 Rx unit 1item 11 bolt М6х14 1item 6 screw М6х50 4items Note Dear user Manufacturer of the sensor constantly upgrades its quality and reliability That s why in some lots of sensors there can be design modifications unspecified in the documents delivered with the sensors Nevertheless the main specifications are valid ...

Page 12: ...up to 0 5 m d maximum sector inclination 200 e single motionless objects e g posts tree trunks without lower branches can be situated in the detection zone at the distance of 0 5 m minimum from the detection zone axis f moving leaves bushes trees and etc should not be situated in the detection zone and at the distance of 1 2 m from the detection zone g sector width of the should meet the requireme...

Page 13: ...tion the sensor operation depends on the exact place of its mounting The example of the supports mounting is given in fig 8 3 8 2 4 Lay the main cables according to the project of the security system Mount the Rx and Tx brackets on the supports see item 6 1 2 The height of the brackets if there is no snow is chosen according to fig 6 1 The brackets are mounted on the supports with two buckles see ...

Page 14: ...ected with the corrugated pipe 7 with the JB or PSU one should remove one of the threaded cable connections PG9 and place the bushing 14 with the corrugated pipe 7 into the hole It is recommended to use one PSU U 24 0 7 for power supply of two contiguous sensors It should be remembered that there are five free terminal blocks in PSU U 24 0 7 1 5 That is why it is not necessary to install a junctio...

Page 15: ...g 8 3 Note 1 For A size the ground should be laid after installation works 2 Dimensions are given in millimeters 8 3 Sensor connection 8 3 1 Connect the necessary power signal and remote control circuits Rx and Tx units are connected with its own cables The colour or marking of the cable conductors indicate their purpose The information about cable conductors marking colour and purpose is given in...

Page 16: ...trol device with a separate loop In this case the separate signal indicates the opening of the Rx cover The second variant is to connect the blocking contacts in series with the actuating relay contacts In this case an alarm will be registered by one channel of the receiving control device at the relay actuation or at the opening of the Rx cover 8 3 4 The scheme of the sensor connection using the ...

Page 17: ...JSC FORTEZA FORTEZA 50 100 200 Please visit our internet sites www forteza com www forteza eu Page 17 Terminator terminator of the control receiving device Fig 8 4 ...

Page 18: ...JSC FORTEZA FORTEZA 50 100 200 Please visit our internet sites www forteza com www forteza eu Page 18 Terminator terminator of the control receiving device Fig 8 5 ...

Page 19: ...JSC FORTEZA FORTEZA 50 100 200 Please visit our internet sites www forteza com www forteza eu Page 19 Fig 8 6 ...

Page 20: ...ccurate alignment The TEST voltage of 1 0 corresponds to the signal level margin of 15 dB If the TEST voltage is more than 4 5 V it is necessary to disalign Rx and Tx upwards at a small angle so the voltage does not exceed 4 5 V Don t disalign Rx and Tx down or aside The sensor is operable at the TEST voltage from 0 1 up to 4 8 V The boundary values of 1 0 V and 4 5 V are recommended to create the...

Page 21: ... special safety trainings 10 2 2 During the sensor exploitation it is necessary to conduct check and preventive works 10 2 3 Every month carry out visual examination of the sensor units and the protected sector It is necessary to check the absence of dust dirt snow and ice from the side of Tx signal transmission and Rx signal reception clean the units if necessary the absence of foreign objects in...

Page 22: ...e 3 The sensor alignment is disturbed Align Tx and Rx antennas 4 Tx is out of order Replace Tx 5 Rx is out of order Replace Rx 2 False alarms 1 Moving branches in the detection zone Inspect the protected sector and remove interference factors 2 High grass in the detection zone 3 Snow blanket is above the norm and reduces the input signal 4 Animals movement in the detection zone 5 The Rx thresholds...

Page 23: ... relative humidity 85 maximum During storage the influence of hostile environment should be prevented 13 TRANSPORTATION 13 1 Packaged sensors can be transported by any transport if by air transport in pressurized modules if they are transported in covered cars holds or covered bodies at the distance up to 10 000 km The boxes should be carefully stowed in order to prevent their shifting or fall in ...

Page 24: ...72 041 43071246 2009 and it is considered as operable Date of issue _________201 Quality department 3 MANUFACTURER S WARRANTIES 3 1 The manufacturer guarantees the conformity of the sensor specifications to the requirements of the Document Part Number 4372 041 43071246 2009 if a user meets the service conditions and operating rules specified by the User Manual 4372 43071246 041 3 2 Warranty period...