6. Chimney Installation
Overview
Your chimney may be constructed using either the
Simpson DuraTech chimney system (or similar UL103HT
listed system), or a refractory chimney flue liner. DO NOT
CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING
ANOTHER APPLIANCE.
The Artigiano vent works with 8” internal dimension
chimney pipe. If you have purchased an Artigiano80, and
wish to use 6” chimney pipe, you can use a DuraTech
reducer.
Instructions
Slide the chimney pipe over the Artigiano vent and if
necessary, secure the chimney pieces in place using metal
straps. Using standard masons mortar or furnace caulk,
seal the vent/chimney intersection to ensure that no
smoke or hot air can escape.
6.1. Furnace caulk seals the vent.
6.2. DuraVent chimney sealed to the vent.
6.3. Chimney attached.
Internal Installation
For internal installations, the minimum air space clearance
between interior masonry chimneys and combustible
materials shall be 2”. Any chimney with at least one
interior wall shall be treated as interior. All spaces between
chimneys and floors or ceilings through which chimneys
pass shall be fire stopped with non-combustible material.
The fire stopping of spaces between chimneys and wood
joists, beams or headers shall be galvanized steel not less
thinner than 26 gage in thickness or non combustible
sheet material not more thicker than 1/2 in.
If it is necessary to pass through combustible walls to
connect the oven to a chimney liner, the following
clearances must be maintained.
Method A. 12” (304.8 mm) Clearance to Combustible Wall
Member: Using a minimum thickness 3.5” (89 mm) brick
and a 5/8” (15.9 mm) minimum wall thickness clay liner,
construct a wall pass-through. The clay liner must conform
to ASTM C315 (Standard Specification for Clay Fire
Linings) or its equivalent. Keep a minimum of 12” (304.8
mm) of brick masonry between the clay liner and wall
combustibles. The clay liner shall run from the brick
masonry outer surface to the inner surface of the chimney
flue liner but not past the inner surface. Firmly grout or
cement the clay liner in place to the chimney flue liner.
Artigiano Installation and Operating Manual
© Forno Bravo, LLC 2008/9. All Rights Served.
Ver. 2.2
25