forlong DRT-341D User Manual Download Page 5

                                                        

DRS-341 series User Manual

 

                                                                                                                                                                                                                                                 
 
Shanghai Fengyilong Electronic CO.LTD                           

www.china-meters.com

                            Email:[email protected]

 

                                                                                                                                                                                86-21-62270763/ 62270963 

 

 

1.6 Operating   

Consumption indication: 

There is a LED which has two colors (green and red) while flashing in the front panel of DRT-341 series. 
When  consumption  happens,  the  LED  will  flash  and  display  red.  The  more  quickly  LED  flash,  the  more 
consumption there is.   

Reading the meter: 

The DRT- 341D series energy meter is equipped with a 6+2 register. Six integers are marked with black color 
and one decimal is marked with red. The DRT- 341D LCD series energy meter is equipped with 6+2 LCD 
display which is used as recording consumption and can’t be reset to zero. The reading accuracy is 1/100 
kWh. 

Record 

The DRT- 341D series energy meter can separate records the total power, 

phase A, phase B, phase C subentry 

power. (

The total power= phase A power + phase B power + phase C power) 

Pulse output 

The DRT_341D Series DIN rail energy meter is equipped with a pulse output which is fully separated from the 
inside circuit. That generates pulses in proportion to the measured energy for accuracy testing. The pulse 
output  is  a  polarity  dependant,  passive  transistor  output  requiring  an  external  voltage  source  for  correct 
operation.  For  this external  voltage  source,  the  voltage  (Ui)  should  is  5-27V  DC,  and  the  maximum input 
current (Iimax) is 27mA DC. To connect the impulse output, connect 5-27V DC to connector 20 (anode), and 
the signal wire (S) to connector 21 (cathode).   

LCD display (two type operational) 

Summary of Contents for DRT-341D

Page 1: ...eters com Email sale01 china meters com 86 21 62270763 62270963 DRT 341D Three phase four wires DIN rail energy meter LCD display One module 1 1 Foreword 1 2 General Technical Data 1 3 Basic errors 1 4 Dimension 1 5 Wiring diagram 1 6 Operating 1 7 Technical support User manual ...

Page 2: ...ere might be possibilities that our product shows a fault or failure for which we do apologize Under normal conditions your product should give you years of benefit and pleasure In case there is a problem with the energy meter you should contact your dealer immediately All energy meters are sealed with a special seal Once this seal is broken there is no possibility to claim for warranty Therefore ...

Page 3: ...1 2 12 Voltage withstand AC voltage withstand 2KV for 1 minute Impulse voltage withstand 6KV 1 2uS waveform 1 2 13 Current withstand 30Imax for 0 01s 1 2 14 Pulse output rate 400imp kWh 1 2 15 Data stored More than 20 years when power off To comply with the protection requirements the meter must be mounted in a class IP 51 enclosure or better according to IEC 60529 1 3 Basic errors 0 05Ib Cosφ 1 1...

Page 4: ...O LTD www china meters com Email sale01 china meters com 86 21 62270763 62270963 B C A D A Front panel B Cover C Base D Security hasp Material Front panel PC inflammable retarding Cover ABS inflammable retarding Base ABS inflammable retarding 1 5 wiring diagram ...

Page 5: ...g consumption and can t be reset to zero The reading accuracy is 1 100 kWh Record The DRT 341D series energy meter can separate records the total power phase A phase B phase C subentry power The total power phase A power phase B power phase C power Pulse output The DRT_341D Series DIN rail energy meter is equipped with a pulse output which is fully separated from the inside circuit That generates ...

Page 6: ...function Cycle display status the default is 5 seconds The display items as following The display item can be settled Display item Total power A B C Phase A power Phase B power Phase C power Serial number Software version SO Output 0 0025 kWh imp Default 0 0025 kWh imp 0 01kWh imp 0 1kWh imp 1kWh imp 5kWh imp 10kWh imp Optional 1 7 Technical support Please contact TEL 021 60975591 FAX 021 60975593...

Reviews: