***Forever Tan does not do any electrical wiring. The electrician must do the pre-
wiring then return for the final hook-up during the equipment installation. This
includes the wiring of any transformers.
***Due to insurance and liability reasons NO employee of Forever Tan is allowed
(either written or verbally) to include any wiring with the purchase of tanning
equipment from Forever Tan.
***Employees of Forever Tan do not mount timers or body fans to walls.
***The factory is allowed by ETL to size the wire coming out of the beds to match
the amp draw not the size of the circuit (Appliance Rule). Wire gauges may be
smaller (or larger for phase conversion purposes) than listed for circuit.
*** All information concerning wire gauge and breaker size are calculated using the
NEC table B-310-1 for 75 degree Celsius wire no more than three conductors in a
raceway or cable in free air. Electrical contractors should verify all information on
wire gauge and breaker sizes. Forever Tan will take no responsibility for any
miscalculations or any misprints.
*** Forever Tan will allow all beds to be cord and plug connected. Forever Tan
requires that the conversion from hard-wire to cord and plug be made externally.
Forever Tan will not provide materials and/or labor for any conversions.
***All information is subject to change at the manufactures and Forever Tan’s
discretion.