33
threshold
short
undercurrent, overcurrent, no current, high
current, and the number of channels with low
current is greater than or equal to this value,
the trip unit performs the tripping action.
Otherwise it will not work.
0x0B0E
2830
Channel arc intensity super
high alarm threshold
Short
The default is 70.Need to set according to
the site conditions or customer requirements,
you can call the company's technical staff
W/R
0x0B0F
2831
O + O- output level during
alarm
Bool
0: low level; 1: 24V, release mode: default is
0; relay mode: default is 1
W/R
0x0B10
2832
O + O- output time during
alarm
Unsigned
short
Unit S (seconds),
Release mode: default is 1;
Relay mode: default is 180
W/R
0x0B11
2833
Automatic current calibration
setting
Bool
Write 1 to enable automatic current
calibration, write 0 to disable, default is 0
W/R
0x0B12
2834
Manual current calibration
setting
Bool
Write 1 to start current calibration, write 0 to
turn off, default is 0
Note: Make sure the channel has no current
when starting calibration.
W/R
0x0B13
2835
Channel 1~16 current
channel switch setting
Unsigned
short
bit0
:
Represents the switch setting for
channel 1
bit15
:
Represents the switch setting for
channel 16
0 means disabled, 1 means enabled
Default 0xFFFF
W/R
0x0B14
2836
Channel 17~24 current
channel switch setting
Unsigned
short
bit0
:
Represents the switch setting for
channel 7
bit7
:
Represents the switch setting for
channel 24
0 means disabled, 1 means enabled
Default 0xFFFF
W/R
0x0B15
2837
External power management
time setting
Unsigned
short
Unit M (min), default 120 minutes. When the
photovoltaic power supply stops, the host
can be powered by external 24 power
sources, and the power supply time can be
set.
W/R
0x0B16
2838
Current UI display, direction,
reverse order control
Unsigned
short
Bit0
~
bit1: Y-axis scale setting of UI
interface
0 means the UI interface displays the current
up to 10A
1 means the UI interface displays the current
up to 20A
2 means the UI interface displays a
maximum current of 30A
bit2: current channel forward / reverse
sequence setting
(Positive sequence: 1 ~ 24 channels
arranged near the host Hall;
Reverse order: Calculate from 24 to 1
channel near the host Hall)
0 means positive order; 1 means reverse
order
bit3: Channel current direction setting
0 means the direction is positive, 1 means
the current is reversed.
0x0000 by default;
W/R
0x0B17
2839
Arc output mode setting
Unsigned
short
0: release mode; 1: relay mode
Default value: 0
W/R
0x0B20
2848
Alarm function management
1
Unsigned
short
Bit0 Bus arc,
bit1 Channel arc,
bit2 Low pressure,
bit3 Over pressure,
bit4 High temperature 1,
bit5 High temperature 2,
bit6 Channel current value is reversed,
W/R