32
generated energy of Channel
24
short
0x024B
587
The lower 16bit of the
generated energy of Channel
24
Unsigned
short
Unit Wh, default 0
R
Arc information (0x0250-0x0297)
0x0250
~
0x0267
592
~
615
Channel 1~24 arc intensity
real-time value
short
Unit 1, default 0
R
0x0268
~
0x027F
616
~
639
Channel 1~24 arc intensity
history maximum
short
Unit 1, default 0
R
0x0280
~
0x0297
640
~
663
Channel 1
~
24 10 minutes
arc intensity value
short
Unit 1, default 0
R
FR-DCMG-HS4Q Hall special register (0x0400-0x0431
)
0x0400
1024
Current channel 1 current
value
short
Unit 10mA, default 0
0x0401
1025
Current channel 2 current
value
short
Unit 10mA, default 0
.......
......
......
......
....
0x0416
1046
Current channel 23 current
value
short
Unit 10mA, default 0
0x0417
1047
Current channel 24 current
value
short
Unit 1mA, default 0
System information configuration (0x0B00-0x0B24)
0x0B00
2816
Alarm release
Unsigned
Short
The percentage of the alarm threshold is
used as the alarm release threshold.
Unit %, default 2, setting range 0 to 100
W/R
0x0B01
2817
Bus voltage alarm low
threshold
Unsigned
short
Unit V, default 300
W/R
0x0B02
2818
Bus voltage alarm high
threshold
Unsigned
short
Unit V, default 1000
W/R
0x0B03
2819
Temperature sensor 1 alarm
high threshold
short
Unit 0.1 ° C, default 800, setting range is
greater than -400
W/R
0x0B04
2820
Temperature sensor 2 alarm
high threshold
short
Unit 0.1 ° C, default 800, setting range is
greater than -400
W/R
0x0B05
2821
Total current low alarm
threshold
Unsigned
Short
Unit 10mA, default 1600, (take 16 channels
to calculate)
W/R
0x0B06
2822
Total current too high alarm
threshold
Unsigned
Short
Unit 10mA, default 1600, (take 16 channels
to calculate)
W/R
0x0B07
2823
Current channel related alarm
activation threshold
Unsigned
Short
Unit mA, default 2000. The average current
value is greater than this value; the total
current is too high, too low, the channel is
undercurrent, overcurrent, no current, high
current, low current, otherwise these alarms
will be forcibly turned off.
W/R
0x0B08
2824
Undercurrent, overcurrent
alarm threshold
Unsigned
short
Unit mA, default 2000. The average current
is subtracted from this value as the
undercurrent alarm threshold; the average
current is added to this value as the
overcurrent alarm threshold.
W/R
0x0B09
2825
Channel current low alarm
threshold
Unsigned
short
Unit mA, default 1000.
W/R
0x0B0A
2826
Channel current high alarm
threshold
Unsigned
short
Unit mA, default 10000.
W/R
0x0B0B
2827
Reverse total current too high
threshold
short
Unit 10mA, default -600.
W/R
0x0B0C
2828
Channel reverse current too
high threshold
short
Unit mA, default -2000.
W/R
0x0B0D
2839
Current channel related trip
Unsigned
Default 3. When the channel is reversed,
W/R