________________________________________________________________________________
49
AST 14 C 259/00
Boiler shut-down; the
pictures flash one after
the other:
No communication with
remote control
Connecting cable
between boiler and
remote control
disconnected
Re-connect it
Remote control faulty
Replace it
Boiler shut-down; the
pictures flash one after
the other:
Boiler type detection
error (CTN or CTFS)
during the self check
which is made once
every 24 hours
See causes related to
error E03
See solutions related to
error E03
Boiler shut-down; the
pictures flash one after
the other:
Gas/fan relay operator
feedback error
The electronic board is
faulty
Replace it
Boiler shut-down; the
pictures flash one after
the other:
Gas valve modulation
coil faulty
Connection between
electronic board and gas
valve modulation coil is
wrong or disconnected
Check electrical
connections
Gas valve modulation coil
faulty
Replace gas valve