background image

20

21

3.2.11. 

“OPEN THERM”

 remote control installation (option)

The heating unit can be connected to an 

Open Therm

 remote 

control (delivered as optional equipment). Position the remote 
control on an inside wall of the premises, far from heat sources or 
draughts. Detach the rear part of the plastic casing (grey) from the 
front one (white), by means of a screwdriver, and fix the rear part to 
the wall using the holes A (pic.8).

pic. 8

WARNING
The  remote control is not to be connected to the 230V power 
main.
The  remote control wires are not to be routed together with the 
power main cables.

In order to connect the remote control, employ two-wire cables 
with the following characteristics:
-  max length: 

 

40 m;

-  max. impedance: 

2 x 4 Ω/m 

-  in order to avoid interferences it is possible to implement interla-
ced wires or with a sheath.

An electronic board, code 0SCHEREM00 is provided with the 
remote control kit, and it to be used to connect the remote control 
to the boiler.
Refer to the instruction delivered with the electronic board, code 
0SCHEREM00, for its installation.

The connection of the remote control to the heating units to be 
implemented by connecting position 1 and 2 of the remote control 
to the OT-BUS 06 terminal board of the 0SCHEREM00 board (see 
electric layout charts). The OT-BUS 06 terminal board is protected 
against false polarity, that is the connections can be switched.

Now close the remote control.

WARNING
When connecting the remote control, selector 11 is to be set 
to the COMFORT � position, and the programmable timer, 
when available, has to have  both channels, 1 and 2, program-
med as permanently ON (see 1.2.3 paragraph).

3.2.12. External probe installation 

The heating unit can be connected to an external probe for ou-

tdoor temperature measurement (standard for BV and RV models, 

as option for B and R models), and “sliding temperature” function 

operation (see 1.2.2.3 paragraph)

Refer to the heating unit layout charts when choosing the type 

of external probe.

The external probe wires are NOT to be routed together with 

the power main cables.

Position the external probe on an outside wall facing North – North 

/ East.

Do not install the probe in the windows areas, near ventilation 

openings or heat sources.

In order to assure correct heating unit operation, employ only 

manufacturer supplied probes.

3.3. Filling up the heating system

When all system connections are performed, the CH circuit can be 

filled.

The procedure is to be carefully performed, following the steps 

below indicated:

- open all radiator air purging valves and the automatic relief valves 

on the heating unit;

- remove the front panel (for model R), or its lower part (for models 

B), of the heating unit by pulling it toward the outside;

- turn the loading tap counter-clockwise in order to allow water 

into the system;

- close the radiator air purging valves as soon as water comes out; 

- check the gauge to show a pressure of 1-1,3 bars; 

- close the loading tap and open all radiator air purging valves 

again; 

- switch on the heating unit and allow the system to reach working 

temperature, then switch it off and repeat the air bleeding proce-

dure;

- allow the system to cool down and check the water pressure to 

be 1-1,3 bars. 

3.4. Starting up the heating unit

3.4.1. Preliminary checks

Prior to starting up the heating unit perform the following checks: 

-  the flue gas discharge pipe and the air intake pipe are installed  

  correctly: while the heating unit is working, no leakage of 

  combustion products from any of the seals is to be detected;

-  the power supply voltage is 230 V - 50 Hz;

-  the system is correctly filled with water (water pressure gauge  

  reading 1-1,3 bar); 

-  any cut-off valves in the CH and DHW systems are open;

-  the fuel supply tap is open; 

-  the master switch is ON;

-  the safety valve is not blocked; 

-  no water leaks are detected;

 

3.4.2. Switching on and off

 

For instructions on how to switch the heating unit on and off, refer 

to the “Instructions for the user”.

 

3.4.3. Burner adjustment

 

After starting up the heating unit it is necessary to adjust the bur-

ner (see paragraph 4.4), checking that:

-  fuel oil pressure;

-  CO

2

 concentration;

-  Bacharach index;

-   flue gas temperature;

are in compliance with the values indicated in the technical data 

chart (see4.4 paragraph).

Summary of Contents for CAPRI B

Page 1: ...CAPRI B R IST 03 C 217 01 INSTALLATION USE AND MAINTENANCE GB...

Page 2: ...Dear Customer thank you for choosing our boilers Please read these installation use and maintenance instructions with care...

Page 3: ...es All the packaging materials can be recycled and should be sent to specific waste management sites Keep the packaging out of the reach of children as it constitutes a serious hazard In the event of...

Page 4: ...imensions page 14 2 3 Heating unit layout page 15 2 4 Technical data of the heating units page 16 2 5 Technical data of the burner page 16 3 Instructions for the installer page 17 3 1 Installation reg...

Page 5: ...d is flashing B and BV models only the temperature probe 2 cylinder is faulty inter rupted or out of range The heating unit keeps operating in CH mode DHW supply is halted As soon as the faulty probe...

Page 6: ...nd BV models or through the adjustable thermo stat on the cylinder Temperature range is 35 C 65 C in B and BV models in R and RV models it is depending on the type of cylinder optional equipment The p...

Page 7: ...s the boiler is active The unit heats the cylin der up to the temperature set via knob 12b B and BV models or via the adjustable thermostat on the cylinder when a cylinder was installed R and RV model...

Page 8: ...h Comfort position All functions are active CH DHW ANTI FROST PUMP ANTI LOCKING ANTI LEGIONELLA Channel 1 of the programmable timer is considered always ON re gardless of the set program therefore CH...

Page 9: ...r the bottom of the chart NOTE TO THE FITTER The fictitious room temperature set by the user through knob 13b is more precise when the SLIDING TEMPERATURE curves are set correctly Such curves are to b...

Page 10: ...eriods can be set a total of 16 In order to set a start program follow the instructions below press button 1 7 in order to set the desired week day or days 1 press button h and button m to set hour an...

Page 11: ...UTO It is possible to permanently activate one channel and permanently de activate the other Proceed as follows position selector 1 to I press button 6 once to select channel 1 twice for channel 2 the...

Page 12: ...ssure by acting upon the loading tap pic 5 located in side the heating unit In order to restore proper water pressure proceed as follows turn the main switch 16 pic 1 to O the green light turns off re...

Page 13: ...tem and 24 kW thermal output TFD 33 sealed chamber heating unit with split air ue gas system and 33 kW thermal output TFD 43 sealed chamber heating unit with split air ue gas system and 43 kW thermal...

Page 14: ...NI01 VA version 5 LOW TEMP FLOW VA version G1 M 10 FUEL INLET Models R and RV Models B and BV D mm TF 150 TFD 120 1 FLOW G1 M 6 HIGH TEMP FLOW BV version G1 M 2 RETURN G1 M 7 HIGH TEMP RETURN BV versi...

Page 15: ...ater Domestic hot water REMOTE CONTROL or CYLINDER PROBE ZONA 1 HIGH TEMPERATURE TS S1 MODEL B PR CH PUMP PS DHW PUMP TS LIMIT THERMOSTAT TA1 ROOM THERMOSTAT OPTIONAL TA 1 TS HEATING UNIT PROBE EXTERN...

Page 16: ...0 5 0 5 0 5 CH temperature range C 50 82 50 82 50 82 Max CH operating pressure bar 3 3 3 CH expansion vessel capacity l 12 12 12 DHW expansion vessel capacity l 5 5 5 DHW temperature range C 35 57 35...

Page 17: ...securing the base to the wooden pallet in order to remove the wooden pallet from the heating unit it is necessary to raise it proceed carefully insert two ropes or cables under the base front rear wis...

Page 18: ...minal Types and classi cation of air intake and ue gas discharge systems Type B23 Discharge through the wall when allowed by applicable installation standards or through the roof or via chimney system...

Page 19: ...y earth the system The DHW CH and fuel pipes are not suitable for grounding purposes 3 2 9 Hydraulic connections CENTRAL HEATING Before installing the heating unit we recommend you clean the sy stem t...

Page 20: ...ted together with the power main cables Position the external probe on an outside wall facing North North East Do not install the probe in the windows areas near ventilation openings or heat sources I...

Page 21: ...OM THERMOSTATS M6 CONNECTOR FOR TELE METERING M1 M24 AVAILABLE CONNECTIONS TA1 TA2 ZONE 1 ROOM THERMOSTAT AND ZONE 2 ROOM THERMOSTAT BOTH OPTIONAL EQUIPMENT TSM LOW TEMPERATURE ZONE THERMOSTAT SE EXTE...

Page 22: ...D ZONE 2 ROOM THERMOSTAT BOTH OPTIONAL EQUIPMENT TSM LOW TEMPERATURE ZONE THERMOSTAT SE EXTERNAL PROBE CODE 0SAODAES01 CT PHONE PROGRAMMER OPTION FUSE 2AF 250Vac FUSE P4 POTENTIOMETER FOR HIGH TEMPERA...

Page 23: ...V 0CIRCSTA05 MAIN ELECTRONIC BOARD M TERMINAL BOARD FOR CONNECTION TO POWER MAINS EXTERNAL PROBE ROOM THERMOSTATS M6 CONNECTOR FOR TELE METERING M1 M24 AVAILABLE CONNECTIONS TA1 TA2 ZONE 1 ROOM THERMO...

Page 24: ...MODEL BV with REMOTE CONTROL 0CIRCSTA05 MAIN ELECTRONIC BOARD M TERMINAL BOARD FOR CONNECTION TO POWER MAINS EXTERNAL PROBE ROOM THERMOSTATS M6 CONNECTOR FOR TELE METERING M1 M24 AVAILABLE CONNECTIONS...

Page 25: ...BE WITH CYLINDER MODEL R 0CIRCSTA05 MAIN ELECTRONIC BOARD M TERMINAL BOARD FOR CONNECTION TO POWER MAINS EXTERNAL PROBE ROOM THERMOSTATS M6 CONNECTOR FOR TELE METERING M1 M24 AVAILABLE CONNECTIONS TA1...

Page 26: ...E METERING M1 M24 AVAILABLE CONNECTIONS TA1 TA2 ZONE 1 ROOM THERMOSTAT AND ZONE 2 ROOM THERMOSTAT BOTH OPTIONAL EQUIPMENT TSM LOW TEMPERATURE ZONE THERMOSTAT SE EXTERNAL PROBE CODE 0SAODAES01 CT PHONE...

Page 27: ...djustement set a value between 3 and 4 NOTE SET THE BOILER JUMPER TO CM3 TO ON EXTERNAL CYLINDER MODEL RV 0CIRCSTA05 MAIN ELECTRONIC BOARD M TERMINAL BOARD FOR CONNECTION TO POWER MAINS EXTERNAL PROBE...

Page 28: ...RATURE CN4 OFF 2 C THE REMOTE MANAGES ZONES 2 WHEN THE REMOTE CONTROL IS CONNECTED BOTH CHANNELS CH1 AND CH2 OF THE DIGITAL TIMER ARE ALWAYS TO BE ELECTRICALLY CLOSED MODEL RV with REMOTE CONTROL 0CIR...

Page 29: ...datory to install a lter on the fuel oil supply pipe The burner pump is designed to operate in a twin pipe system In order to supply via a single pipe unscrew cap 2 and remove the grub screw 3 Afterwa...

Page 30: ...ire adjustment Combustion air can be adjusted by turning the socket screw A shown in pic 15 The setting is shown on the relevant graduated scale B The oil pressure can be adjusted by turning screw 5 i...

Page 31: ...18 pic 17 4 8 Burner ignition cycle The burner ignition cycle is shown in pic 19 chart In the event of shutdown the red light 7 on the control panel pic 1 comes on and the reset button C on the burner...

Page 32: ...Optical resistence Solenoid valve Motor and condenser Burner earth Safety thermostat Limit thermostat Remote shutdown light 230V 0 5A max Ignition electrodes Optical resistence Solenoid valve Motor an...

Page 33: ...terminal connections The burner performs pre purge correctly and then shuts down The optical resistance is dirty Clean it The optical resistance is faulty Replace it The flame goes out or does not lig...

Page 34: ...rvice technicians T accurately trained personnel 6 1 Maintenance schedule Routine maintenance is to include the following general check and inspection of the heating unit check for leaks of the oil su...

Page 35: ...isconnected Reconnect it Flow probe is faulty Replace it The heating unit has shut down the red shutdown light no 6 is flashing The unit will automatically resu me operation once the problem is solved...

Page 36: ...tel 39 365 878 31 fax 39 365 878 576 email fondital fondital it www fondital it The manufacturer reserves the right to implement modifications to the products as required without affecting the basic f...

Reviews: