Fonderie SIME UNIQA.REVOLUTION User, Installation And Servicing Instructions Download Page 47

47

Type

No. Fault

Solution

ALL

11 Gas valve modulator 

disconnected

- Check the electrical con-

nection

ALL

12

Incorrect configuration 

of the open /sealed 

chamber

- Set the parameter tS 0.4 

(Combustion configuration) 

to 0

ALL

13 Smoke probe inter-

vention

- Check the sensor is 

working

- Replace the smoke probe

ALL

14 Smoke probe fault

- Replace the smoke probe

- Check the electrical con-

nection of the smoke probe

- Contact the Technical 

Assistance Centre

ALL

15 Fan check cable dis-

connected

- Check the connection cable 

between the fan and the 

board

ALL

18 Condensate level fault

- Check for any clogging in 

the pipe which takes the 

condensate to the siphon

- Check that the siphon is 

not clogged

ALL

28 Maximum number of 

consecutive releases

- Contact the Technical 

Assistance Centre

ALL

30 Return sensor (SR) 

fault

- Replace the return probe

- Check parameters

- Contact the Technical 

Assistance Centre

ALL

37 Fault due to low net-

work voltage

- Check the voltage

- Contact your network 

provider

ALL

40 Incorrect network 

frequency detected

- Contact your network 

provider

ALL

41 Flame loss more than 6 

consecutive times

- Check the detection 

electrode

- Check the gas supply (open 

valve)

- Check mains gas pressure

ALL

42 Button fault

- Check that buttons are 

working

ALL

43 Open Therm communi-

cation fault

- Check the electrical 

connection of the remote 

control

ALL

44 No flame valve opening 

time sum anomaly

- Replace the board

ALL

62 Self-calibrating proce-

dure is required

- Carry out the self-cali-

brating procedure (see the 

specific section)

ALL

70 HP high pressure time 

max. interventions

- Decrease setting PAR 46

- Contact the Technical 

Assistance Centre

ALL

72 Incorrect positioning of 

the delivery sensor

- Check that the delivery 

sensor is attached to the 

delivery pipe

ALL

77 EV current max/min 

absolute limits error

- Check gas valve and board

ALL

78 EV current upper limit 

error

- Check gas valve and board

ALL

79 EV current lower limit 

error

- Check gas valve and board

ALL

80 Fault on the valve 

control logic line

- Check/replace the connec-

tion cable to the gas valve

ALL

81 Block due combustion 

during start-up

- Check for blockage in 

chimney or recirculation

- Bleed the air from the gas 

circuit

- Check for any dirt on the 

air evaporator

ALL

82

Block due to numerous 

combustion control 

failures

- Check electrode

- Check outlets

- Check air diaphragm

- Check gas calibration

- Check for any dirt on the 

air evaporator

Type

No. Fault

Solution

ALL

83 Irregular combustion 

(temporary error)

- Check for blockage in 

chimney

- Check for any dirt on the 

air evaporator

ALL

84

Flow rate reduced for 

(presumed) low pres-

sure on mains gas

- Check gas flow rate

ALL

88 Internal error (board 

component protection) - Replace the board

ALL

89 Unstable combustion 

feedback signal error

- Check electrode

- Check outlets

- Check air diaphragm

- Check gas calibration

ALL

90 Combustion set cannot 

be reached error

- Check electrode

- Check outlets

- Check air diaphragm

- Check gas calibration

ALL

92

System has reached 

maximum air cor-

rection error (at the 

minimum flow rate)

- Check electrode

- Check outlets

- Check air diaphragm

- Check gas calibration

ALL

93 Combustion set cannot 

be reached error

- Check electrode

- Check outlets

- Check air diaphragm

- Check gas calibration

ALL

95 Flame signal micro 

interruptions error

- Check electrode

- Check board

- Check electric power 

supply

- Check gas calibration

ALL

96 Block due to clogging 

in smoke outlet

- Check for blockage in 

chimney

ALL

98 SW error, board start-

up

- Contact the Technical 

Assistance Centre

ALL

99 General board error

- Contact the Technical 

Assistance Centre

8.7.1 

Maintenance request

When it is time to perform maintenance on the boiler, the 

c

 

symbol shows on the display.

Contact the technical assistance service to organise the neces-

sary work.

Summary of Contents for UNIQA.REVOLUTION

Page 1: ...Fonderie SIME S p A 6330326 12 2018 R0 Cod USER INSTALLATION AND SERVICING INSTRUCTIONS UNIQA REVOLUTION Low temperature wall mounted boiler EN TRANSLATION OF THE ORIGINAL INSTRUCTIONS...

Page 2: ...least one of the fol lowing operations must be carried out set the main system switch to OFF close the gas and water valves for the water heating system In order to ensure optimal appliance operation...

Page 3: ...supply Do not modify the safety or adjustment devices without authorization and in structions from the manufacturer d IT IS FORBIDDEN Do not block the condensate drain if present Do not pull detach o...

Page 4: ...tant and useful informa tion MANUAL STRUCTURE This manual is organized as follows CHECKLIST a WARNING Before installing and starting up the boiler make sure you have done the following handle the boil...

Page 5: ...ng the heating temperature 7 1 5 Adjusting the domestic hot water temperature 7 1 6 Fault malfunction codes 8 2 SHUTDOWN 8 2 1 Temporary shutdown 8 2 2 Shutting down for long periods 9 3 MAINTENANCE 9...

Page 6: ...tting or value increasing by pressing this button c Programming connector cover plug NOTE pressing any one of these buttons for more than 30 sec onds generates a fault on the display without preventin...

Page 7: ...e 2 and restore the heating system pressure until the display 1 shows a reading of 1 1 2 bar close the filling valve 2 2 1 Fig 3 select the SUMMER l operating mode by pressing and holding the ybutton...

Page 8: ...et the main system switch to OFF contact the Qualified Technical Personnel OFF Fig 5 m CAUTION Should you see an alarm not described here contact a qualified technical professional 2 SHUTDOWN 2 1 Temp...

Page 9: ...d in the INSTALLATION AND MAINTENANCE MANUAL 3 2 External cleaning a WARNING Should it be necessary to access the areas in the bottom part of the appliance make sure that the system components and pip...

Page 10: ...10...

Page 11: ...stics 12 5 2 Check and safety devices 12 5 3 Identification 12 5 3 1 Technical Data Plate 13 5 4 Structure 14 5 5 Technical features 15 5 6 Main water circuit 16 5 7 Sensors 17 5 8 Expansion vessel 17...

Page 12: ...matically every 24 hours if no request for heat has been made domestic hot water comfort function which allows the time necessary for the hot water to become available to be reduced and ensures that t...

Page 13: ...FACTURE SERIAL NUMBER NAME MAX USEFUL OUTPUT MAX OPERATING PRESSURE MAX HEAT INPUT FLOW RATE MAX OPERATING PRESSURE ELECTRICAL SUPPLY MAXIMUM ABSORBED POWER MAX HEAT INPUT COUNTRY OF INTENDEDINSTALLTI...

Page 14: ...ater sensor 9 Control panel 10 Domestic hot water heat exchanger 11 Gas valve 12 Domestic water filter and flow regulator 13 System relief valve 14 Boiler drain 15 System pump 16 Water pressure transd...

Page 15: ...DOMESTIC HOT WATER Domestic hot water energy efficiency class A Domestic hot water energy efficiency 81 Stated domestic hot water profile load XL ELECTRICAL SPECIFICATIONS Power supply voltage V 230...

Page 16: ...ermal bulb 9 Refrigerant gas high pressure pressure switch 10 Gas valve 11 Domestic hot water flow meter 12 Domestic hot water filter 13 System filling 14 Boiler drain 15 System relief valve 16 System...

Page 17: ...M UNIQA REVOLU TION Total capacity l 8 0 Prefilling pressure kPa 100 bar 1 0 Useful capacity l 4 0 Maximum system content l 109 Conditions of Average maximum temperature of the system 85 C Start tempe...

Page 18: ...creasing by pressing this button c Programming connector cover plug NOTE pressing any one of these buttons for more than 30 sec onds generates a fault on the display without preventing boiler operatio...

Page 19: ...SR Return Probe SIA Air inlet probe APS Air pressure switch EXP Expansion card CP Compressor CR Remote control instead of air thermostat To connect the Air Thermostat or alternatively the Remote Contr...

Page 20: ...20...

Page 21: ...meter setting and display 33 7 4 List of parameters 34 7 5 Display of operating data and counters 36 7 6 Gas conversion 37 7 6 1 Preliminary operations 37 7 7 Automatic calibration procedure 38 7 7 1...

Page 22: ...single unit pro tected by cardboard packaging Fig 15 The plastic bag found inside the packaging contains the follow ing Installation use and maintenance manual Paper template for boiler installation...

Page 23: ...and accident protection when re moving the packaging and when handling the appli ance Observe the maximum weight that can be lifted per person 6 4 Installation room The room where the appliance is to...

Page 24: ...is not availa ble replace it with a pump to circulate water in the system and then proceed as described above Once cleaning operations have been carried out and before installing the new appliance it...

Page 25: ...ied with the accessory itself or are to be found on the packaging 6 10 Gas supply UNIQA REVOLUTION boilers leave the factory specifically prear ranged for G20 gas or G31 The G20 models can be converte...

Page 26: ...ll smoke outlet The pipes can start from the boiler but the outlets must be concentric or close together no more than 50 cm to be subject to similar wind conditions C32 C32X Concentric roof outlet Out...

Page 27: ...the presence of the diaphragm modifies the maximum length of the duct as shown below Model Diaphragm Max L m UNIQA REVOLUTION YES 2 5 UNIQA REVOLUTION NO 5 6 11 2 Separate ducts 80mm The smoke outlet...

Page 28: ...d 10 m inlet 10 m outlet for ducts 80 mm NOTE for the boiler to operate correctly it is necessary that a minimum distance of 0 50 m of the duct is respected with a 90 inlet curve Example calculation o...

Page 29: ...a 230V 50 Hz network If this cable needs to be replaced an original spare must be re quested from Sime Therefore only the connections of the original components as shown in the table are needed These...

Page 30: ...ins power is disconnected by setting the main system switch to OFF The manufacturer is not responsible for any damage caused by failure to earth the appliance or failure to ob serve the information pr...

Page 31: ...R M SE TA CR Fig 34 MULTI ZONE system with zone valve air thermostat and ex ternal sensor TA TZ1 VZ1 VZ2 VZ3 TZ2 TZ3 SE R M Fig 35 m CAUTION Set the parameter tS 17 DELAY SYSTEM PUMP AC TIVATION to al...

Page 32: ...of the system 4 3 Fig 39 NOTE to completely remove all air from the system it is recom mended that this operation is repeated a number of times check the pressure on the display and if necessary top u...

Page 33: ...stem is cold is between 1 and 1 2 bar press the button y once for at least 1 second to select SUMMER mode l the value of the delivery sensor detect ed at that moment will appear on the display open on...

Page 34: ...aximum threshold for deactivating compressor CP 40 PAR 08 External sensor value correction 5 5 C 1 0 PAR 09 DOMESTIC HOT WATER HEATING PAR 10 Boiler antifreeze threshold 0 10 C 1 3 PAR 11 External sen...

Page 35: ...ery return 10 40 C 1 20 PAR 42 PAR 43 PAR 44 Minimum time between compressor ignitions m 14 PAR 45 Minimum time between compressor on off 13 PAR 46 Return temp threshold for activating the compressor...

Page 36: ...99 C 1 PAR 06 Actual heating SET temperature Par 13 Par 14 C 1 PAR 07 Power level 0 99 1 PAR 08 Flow meter rate 0 99 l min 0 1 PAR 09 Water pressure transducer reading if resent 0 99 bar 0 1 PAR 10 Re...

Page 37: ...ventions described set the main system switch to OFF close the gas valve make sure that no hot parts inside the appliance are touched OFF Fig 43 7 6 1 Preliminary operations To carry out the conversio...

Page 38: ...he gas valve following a fault the electronic board following a fault electrode fan burner and is necessary so that the new components can be identified and can communicate with those already fitted o...

Page 39: ...5 the modified value will be stored automatically exit the parameter section by pressing and holding down the buttons rand t at the same time approximately 5 seconds until the delivery temperature is...

Page 40: ...ressure Type of gas G20 G31 Pressure mbar 20 37 Installations with SPLIT and CONCENTRIC flue gas outlet pipe systems Model Heat Output Pressure at nozzles mbar G20 G31 UNIQA REVOLU TION Max 13 3 13 8...

Page 41: ...press and hold the t button and scroll through the parame ters until you reach PAR 15 press and hold the button to change the value to 0 force minimum power the modified value will be stored automatic...

Page 42: ...ature is stable To activate the function select parameter PAR 22 see Parameter setting and dis play and set it toa 1 exit parameter settings and press button for approximately 5 seconds until the symb...

Page 43: ...arts inside the appliance are touched OFF Fig 52 8 2 External cleaning 8 2 1 Cleaning the cladding When cleaning the cladding use a cloth dampened with soap and water or alcohol for stubborn marks d I...

Page 44: ...pecial care to clean the back part where there is a steel and copper blade 7 7 Fig 56 8 3 4 Checking the ignition detection electrode Check the state of the ignition detection electrode and replace if...

Page 45: ...te the chimney sweep function described below This function lasts 15 minutes and is activated by proceeding as follows if the panel 2 has not already been removed remove the two screws 1 pull the fron...

Page 46: ...wer in kW 0 25 0 PAR 02 Hydraulic configuration 5 Low NOx ErP 5 PAR 03 Gas Type Configuration 0 G20 1 LPG 0 or 1 PAR 04 Combustion configuration 3 Low NOx ErP APS 3 To enter Parameter setting and disp...

Page 47: ...max min absolute limits error Check gas valve and board ALL 78 EV current upper limit error Check gas valve and board ALL 79 EV current lower limit error Check gas valve and board ALL 80 Fault on the...

Page 48: ...n GJ D H W annual combustible consumption GJ C H seasonal energy efficiency D HW energy efficiency Sound power dB A Specific precautionary measures to be adopted at the time of assembly installation o...

Page 49: ...d low temperature regime b P1 8 kW At 30 of nominal heat output and low temperature regime 1 97 9 Auxiliary electricity consumption Other items At full load elmax 0 060 kW Standby heat loss Pstby 0 11...

Page 50: ...50...

Page 51: ...51...

Page 52: ...45 Legnago Vr Tel 39 0442 631111 Fax 39 0442 631292 www sime it Fonderie SIME S p A reserves the right to make changes at any time without prior notice in order to improve its products without comprom...

Reviews: