Combustion air inlet
The combustion air inlet, with separate ducts, is assembled as
follows:
– remove the air outlet cap (5); choose your preferred outlet
– cut the bottom of the cap (5) using a suitable tool (a)
– turn over the cap (5) as shown (b) and refit it on the air outlet,
inserting the new seal (6) provided in the kit
– fix everything in place with the screws removed previously.
The overturned cap (5) is now the attachment for the first com-
ponent on the air inlet duct
5
b
a
6
5
5
5
Fig. 26
Smoke outlet and combustion air inlet fittings
E
B
C
D
A
Fig. 27
Description
UNIQA.REVOLUTION
A (mm)
248
B (mm)
140
C (mm)
175
D (mm)
180
E (mm)
220
6.12 Electrical connections
The boiler is equipped with a ready wired power cable which is
to be connected to a 230V~50 Hz network.
If this cable needs to be replaced, an original spare must be re-
quested from
Sime
.
Therefore only the connections of the original components as
shown in the table are needed. These are to be ordered sepa-
rately from the boiler.
DESCRIPTION
CODE
External sensor kit (ß=3435, NTC 10KOhm at 25°C)
8094101
Power cable (dedicated)
6329400
Remote control HOME (open therm)
8092280
Remote control HOME PLUS (open therm)
8092281
m
CAUTION
The maintenance interventions described must ONLY
be carried out the professionally qualified personnel.
a
WARNING
Before carrying out any interventions described:
– set the main system switch to "OFF"
– close the gas valve
– make sure that no hot parts inside the appliance are
touched.
OFF
Fig. 28
To facilitate introduction of the connection wires of the optional
components into the boiler:
– remove the screws (1), pull the front panel (2) forwards and
release it from the top by lifting it
1
2
Fig. 29