- 29 -
FUS
E
JP1
OPEN→JUMP
SHORT→JUMP
AC
DIP-SW
U
JP3
JP2
JP4
7.3 Receiver Function Setting
7.3.1
α
604/607/608 Receiver Function Setting
7.3.1.1 Set by programming tool
Input from programming port CN5 and CN9. The data of CN5 and CN9 have to be identical.
7.3.1.2. Adjust Jumper setting function by decoder board
Adjusting jumper setting to change function selection (refer to Jump Set table as below):
Receiver function setting:
(*Mode 1 only for EN ISO 13849-1 version)
System type Mode Description
JP1
α604/607/608
Mode 1 Use short pin only. Start the system by rotating the power switch to
“ON” position
.
JP2
No function
JP3
All
Mode 1 1. Refer to “JP3 (*1)“ of Jumper Set Table on Page 41 & 42, for
α604AS/BS, 607AS/ATS/BS/BTS and 608AS/BS.
2.
Refer to”JP3(*2),
α608T only”
on Page 42
,
for α608ATS/BTS.
A.
Select any pushbutton or ON/OFF power switch to start the system. The MAIN relay will be activated
when system is started. (After the receiver power is started and emergency stop button is elevated)
B.
The MAIN relay auto shutdown time can be set as 3 minutes or depends on customer’s single request.
(Remark 1)
C.
When transmitter voltage is low, relays for the receiver MAIN and LV (Remark 1) will be auto shutdown
after one minute.
(Fig. 13) Alpha 604, 607, 608 models
Jumper Set table:
in-plant setting (default).
JP1
Open
Not available
Short
Transmitter power switch start (when MAIN is off)
JP2
Open
No function
Short
No function
JP3(*1)
Open
When the transmitter voltage is low, LV relay
activates/deactivates every second.