background image

4.0 SITE REQUIREMENTS - CONTINUED

GB IE

4

All models : This appliance requires a natural draught flue system which may be one of the following;

225mm x 225mm (9in x 9in) brick or stone.
125mm (5in) minimum diameter lined brick or stone.
125mm (5in) minimum diameter twin wall flue conforming to BS 715.
Pre-cast block flue complying with BS 1289 or BS EN 1858.

Any existing under grate draught device must be sealed off. The opening wall must be non-combustible.

The appliance requires a hearth with non-combustible surface of at least 12mm thick. The top surface must be at least 50mm above the

surrounding floor level, or be surrounded by a raised edge or fender 50mm high.

To enable the products of combustion to be cleared properly up the flue, the outlet at the back of the appliance must have a 50mm min-

imum clearance between it and the back wall of the opening or any other obstruction. The area immediately above the outlet must form

a smooth path into the flue.

Any type of fire surround used with this appliance must be adequately sealed to the wall and floor.

A combustible shelf may be fixed to the wall above the fire, providing that it complies with the dimensions given below.

A non-combustible shelf may be fitted to within 10mm of the top edge of the fireframe. Combustible materials, such as wood, may be

fitted to within 100mm of either side of the fireplace opening, providing the forward projection does not exceed 100mm. Any com-

bustible side walls must be at least 500mm to the side of the radiant heat source. As with all heating appliances, any decorations, soft

furnishings, and wall coverings (i.e. flock, blown vinyl and embossed paper) positioned too close to the appliance may discolour or scorch.

The mounting depth of this appliance is 108mm (120mm - Convector models).

In accordance with BS 5871 part 2, minimum debris collection volumes are required behind the installed appliance. These are shown

below and as dimension ‘X’ in figure 1.

CLAY/CEMENT LINES OR BLOCK FLUE WHICH IS NEW, UNUSED, OR PREVIOUSLY ONLY USED WITH A GAS FIRE.

X Dimension = 20mm

UNLINED  FLUE OR CHIMNEY WHICH HAS BEEN PREVIOUSLY USED FOR A SOLID FUEL OR OIL BURNING APPLIANCE

X Dimension = 60mm

‘A’. Opening height: 540mm min/575mm max. 
‘B’. Opening width: 350mm min/440mm max. 
‘C’. Mounting depth: 108mm 
‘D’. Hearth must extend minimum of 150mm either
side of the  opening.
‘E’. Hearth must extend minimum of 300mm in front
of the opening.
‘F’. Non-combustible hearth must be a minimum of
50mm  in  height,  or  be  surrounded  by  50mm  high
fender.
‘G’.  470mm,  this  area  must  be  flat  and  vertical  to
ensure a good seal.
‘H’.  585mm,  this  area  must  be  flat  and  vertical  to
ensure a good seal.
‘X’. Debris collection space - See section 4.1.

4.1 DEBRIS COLLECTION SPACE

‘A’

‘C’

‘B’

‘E’

‘F’

‘G’

‘H’

‘X’

‘D’

Figure 1

© 2014 Focal Point Fires plc.

Maximum depth of shelf  

Minimum distance from finished 

hearth surface to underside of shelf

100mm (4in)

745mm (29

1/4 

in)

150mm (6in)

845mm (33

1/4 

in)

203mm (8in)

895mm (35

1/4 

in)

Summary of Contents for Aura Multiflue

Page 1: ...326 www focalpointfires co uk e sales focalpointfires co uk INTHE UK ALWAYS USE A GAS SAFE REGISTERED ENGINEERTO INSTALL REPAIR OR SERVICETHIS APPLIANCE MODELS COVERED BY THESE INSTRUCTIONS BLENHEIM M...

Page 2: ...ion and use of this appliance This appliance is free from any asbestos material Refractories and fuel bed are constructed from ceramic fibre Remote control models These appliances features a battery o...

Page 3: ...not evident at any joints Repair and re test as necessary before the appliance is installed The flue must be connected to only one fireplace and the flue must not vent more than one appliance i e not...

Page 4: ...place opening providing the forward projection does not exceed 100mm Any com bustible side walls must be at least 500mm to the side of the radiant heat source As with all heating appliances any decora...

Page 5: ...ation It is important that the sealing requirements of the appliance are met at all times and that the flue box is well sealed to any back or infill panel Note The DEPTH dimension is inclusive of any...

Page 6: ...ontrol position marking sticker on the trim next to the control knob as shown in figure 16 Before installing the fire check the flue using a smoke pellet All of the smoke should travel up the flue and...

Page 7: ...e tensioner nuts to pull the appliance tightly against the fireplace opening Visually inspect the seal and reseat if necessary Do not cut off excess cable Surplus cable must not be cut off as it will...

Page 8: ...for some time hold the knob in this position for longer to allow any air in the pipes to be purged Continue turning anti clockwise through the spark clicks to the nine o clock position ensuring the pi...

Page 9: ...own and the pilot lit with a taper Light the fire on the HIGH setting To commission the appliance the operating pressure must be in accordance with the figures stated in section 2 0 of these instructi...

Page 10: ...this time Advise that the fire is fitted with a spillage safety device O D S If the fire shuts down this system may be in operation If spillage is suspected SWITCH APPLIANCE OFF and call in the instal...

Page 11: ...n the rear of the valve and the two securing screws and lifting away Remove the tubing nut from the valve end of the pilot pipe and blow through to dislodge any debris Clean the pilot assembly with a...

Page 12: ...Blocked pilot clean out Excessive drafts in the room Excessive flue pull Fire is too close to an air vent Dirt or lint in pilot aeration hole or on the lint gauze clean thoroughly If the pilot will no...

Page 13: ...installer to ensure there are no defects or obstructions that may prevent the flow of combustion products This appliance is fitted with a flue blockage safety device which will shut down the fire if...

Page 14: ...ng Push the control knob in fully and turn anti clockwise through both of the SPARK positions keeping fully depressed hold there for a few seconds If the fire has not been used for some time hold the...

Page 15: ...porates an inbuilt safety feature to prevent the main burner being activated or turned up accidentally It is necessary to press button 1 and 2 see figure 5 simultaneously to turn the fire up To turn t...

Page 16: ...sides as shown Place the rear row of four coals making sure that the flat sides are firmly against the brick panel and side cheeks as shown The coals must not be crammed together or inserted into the...

Page 17: ...ith the pebbles supplied when assembled according to the instructions Never add to the fifteen pebbles or change them for a different type Never throw rubbish or other matter onto the fuel bed Due to...

Page 18: ...p cloth and mild household detergent Brass parts of the firefront may be cleaned using a suitable brass cleaner Replace the front centrally against the fire after cleaning Do not use a damp cloth to c...

Page 19: ...control models F730057 Gas valve Manual control models F730085 Gas valve Remote control models F730011 Gas valve Slide control models F730067 Injector Stereo 78 Manual Slide control models F730062 In...

Page 20: ...als pebbles the matrix front strips side cheeks rear panels and tapered rear panels are not covered by the 3 year guarantee For all Electric fires purchased the 3 year guarantee commences from the dat...

Reviews: