background image

INSTALLATION REQUIREMENTS

The LPG (propane) version of this appliance MUST NOT be installed into a basement, or into an area that is
entirely or partially below ground level.

This appliance MUST NOT be installed into a room containing a bath or shower, or where steam may be
present. The fire has been designed to fit into a builders’ opening or fireplace conforming to BS 1251 (and
meeting certain dimensional requirements), or a suitable flue box complying with the constructional
requirements of BS 715. The flue box must be installed onto a suitable non-combustible insulating surface at least
12mm thick, covering the entire base area of the box.

The flue must have an effective height of at least three meters, as measured from the hearth to the top of the flue.
Any flue damper plates or restrictors should be removed and no other restriction fitted to the flue. Where removal
is not practical, the restriction must be fixed in the fully open position.

A natural draught flue system is required, and if previously used for solid fuel or oil burning, the flue and chimney
must be swept prior to appliance installation. Pre-cast flues must be checked for mortar fangs and correct
installation of joints, flue sections in loft space and terminals. The flue must be checked before installation by
using a smoke pellet or similar to ensure proper draw and that leakage is not evident at any joints. Repair and
re-test as necessary before the appliance is installed.

The flue must be connected to only one fireplace, and the flue must not vent more than one appliance (i.e. not
shared with a gas back boiler). There must be no opening in the flue apart from the one that the appliance is
installed into, and the one venting the gases into the air. A suitable terminal may be fitted, such as class GC1, as
regulations allow.

This appliance has been tested for use in a pre-cast block flue complying with BS 1289. In accordance with BS
1289 part 1, pre-cast flues built with directly plastered faces (front or rear) are not correctly installed as to ensure
proper operation with 

any 

type of gas fire. In some instances of this flue construction, temperature cracking of

the surface plaster may occur through no fault of the appliance. An air gap or some form of insulation material
should be installed to prevent normal flue temperatures from damaging wall surfaces.

This appliance is suitable for use with a “lightweight” surround and back panel of 150C minimum rating.

2

APPLIANCE DATA

Gas Group

G20 Natural Gas CAT I2H

G31 Propane CAT I3P

Inlet Pressure

20 mbar

37 mbar

Max Energy Input (gross)

6.2 kW

6.2 kW

Min Energy Input (gross)

3.5 kW

3.5 kW

Pilot Energy Input (gross)

210 W

210 W

Setting Pressure

17.5 mbar

36.6 mbar

Main Injector Burner

Stereo size 77 / Bray Cat 82-420

Stereo size 130 / Bray Cat 92-190

Gas Inlet Connection

8mm compression

8mm compression

Ignition

Piezo spark

Piezo spark

Spark Gap

3.5 to 4.5mm

3.5 to 4.5mm

Weight

20 Kg

20 Kg

Please see Data Badge affixed to appliance for current data.

This appliance is for use only with the gas type, and at the pressure stated on the appliance

Data Badge, and is for decorative purposes.

2.0

3.0

Summary of Contents for JEMEZ

Page 1: ...instructions must be handed to the user for safekeeping Revision B 11 03 Country s of destination GB IE Focal Point Fires plc Avon Trading Park Christchurch Dorset BH23 2BT 01202 499330 Fax 01202 4993...

Page 2: ...a competent person in accordance with Gas Safety Installation and Use Regulations 1998 It is strongly recommended that a CORGI registered engineer be used for this purpose Read all these instructions...

Page 3: ...stalled in accordance with the rules in force and used only in a sufficiently ventilated space Consult all instructions before installation and use of this appliance This appliance is free from any as...

Page 4: ...must be connected to only one fireplace and the flue must not vent more than one appliance i e not shared with a gas back boiler There must be no opening in the flue apart from the one that the appli...

Page 5: ...to BS 715 Pre cast block flue complying with BS 1289 Any existing under grate draught device must be sealed off The opening wall must be non combustible The appliance requires a hearth with non combu...

Page 6: ...BEEN PREVIOUSLY USED FOR A SOLID FUEL OR OIL BURNING APPLIANCE X Dimension 60mm VENTILATION No purpose provided ventilation is normally required for this appliance The requirements of other appliances...

Page 7: ...allow plugs and screws to secure installation It is important that the sealing requirements of the appliance are met at all times and that the flue box is well sealed to any back or infill panel Note...

Page 8: ...milar Place the coals ceramics and fixings safely to one side Remove the burner from the assembly by removing the two screws in the data control plate Lift away the plate and remove the two screws ret...

Page 9: ...ame or base and relevant points in the opening or on the wall Rawlplugs will be required NOTE Plastic rawlplugs are not suitable for this application Gas supply Following preparation for the fixing me...

Page 10: ...ill prevent proper installation after servicing Coil up the surplus cable and tuck the coils out of the way as suggested in the photograph FITTING THE BURNER TRAY Important Note Check that the thermoc...

Page 11: ...the supports in the matrix over the top of the holes Ensure the coals are not turned sideways such that they actually enter the holes Finally place the rear row of two coals Note The coals must not b...

Page 12: ...he gas supply up to the fire for any leaks in accordance with current Approved Codes of Practice ACOPs OPERATING THE APPLIANCE The pilot is visible through the left hand side of the matrix Rotate the...

Page 13: ...is to be suspected This will be dirt and debris kinked or inadequate size pipes restriction in a fitting or solder flashing across a joint FLUE SPILLAGE MONITORING SYSTEM This fire is fitted with a fl...

Page 14: ...rried out at least one annually Advise that cleaning of the fire may be achieved when the fire is cold using a damp cloth and mild detergent on most surfaces Scratched and other superficial damage to...

Page 15: ...p ceramic components in plastic bags and dispose at proper refuse sites as directed Re fit the coals by referring to the relevant section of these instructions DISMANTLING THE BURNER TRAY Remove the t...

Page 16: ...frame and if necessary replace Refitting of the convector box is as described in the fitting section of these instructions PILOT ASSEMBLY Remove the burner tray as in relevant section and pilot unit a...

Page 17: ...uns for a time and then cuts off Excessive room draught or flue pull rectify Loose or faulty thermocouple rectify ODS system in operation Firebox grommet seal not fitted rectify Lint in pilot aeration...

Page 18: ...ung children the elderly or infirm are concerned Combustible items such as flooring and furniture and soft wall coverings such as blown vinyl or embossed paper may discolour if fitted too close to the...

Page 19: ...irements this will have been carried out by your CORGI registered installer For Republic of Ireland ventilation may be required see IS 813 ICP3 IS 327 and any other rules in force OPERATING INSTRUCTIO...

Page 20: ...ed using a vacuum cleaner or dry cloth Heavy stains may be removed by using a damp cloth and mild household detergent Brass parts of the firefront may be cleaned using a suitable brass cleaner Replace...

Reviews: