background image

www.fmiproducts.com

115607-01D

12

  CAUTION:  All  gas  piping 

and connections must be tested 

for  leaks  after  the  installation 

is  completed.  After  ensuring 

that the gas valve is on, apply 

soap  and  water  solution  to  all 

connections and joints. Bubbles 

forming  show  a  leak.  Correct 

all leaks at once. DO NOT USE 

AN  OPEN  FLAME  FOR  LEAK 

TESTING AND DO NOT OPER-

ATE ANY APPLIANCE IF A LEAK 

IS DETECTED. LEAK TESTING 

SHOULD BE DONE BY A QUALI-

FIED SERVICE PERSON.

  WARNING:  Do  not  oper-

ate an unvented gas log set in 

this fireplace with the chimney 

removed.

Figure 29 - Gas Line Knockout

Side 

Firebrick 

Finished 

Side

Refractory 

Knockout 

Plug

Outside of 

Fireplace

Gas Line 

Conduit
Insulation

Gas 

Conduit 

Cover

1/2" Dowel

Remove 

Knockout

oPTional gas line 

insTallaTion

  WARNING:  A  qualified 

service  person  must  connect 

fireplace to gas supply. Follow 

all local codes.

NOTICE: 

Before you proceed, make sure your 

gas supply is turned off.

A gas line may be installed for the purpose 

of installing a vented or vent-free decorative 

gas  appliance  available  through  your  local 

distributor.  Use  only  gas  piping  approved 

by local codes. When installing a gas line, a 

shutoff valve designed for installation outside 

the appliance is recommended.

The gas pipe is intended for connection to a 

decorative gas appliance that operates using 

natural or propane/LP gas only. This appliance 

must have an automatic shutoff device and 

must comply with the 

Standard for Decora-

tive Gas Appliances for Installation in Vented 

Fireplace, ANSI Z21.60

. ONLY UNVENTED 

GAS  LOG  SETS  WHICH  HAVE  BEEN 

FOUND TO COMPLY WITH THE STANDARD 

FOR  UNVENTED  ROOM  HEATERS, ANSI 

Z21.11.2, ARE TO BE INSTALLED IN THIS 

FIREPLACE.

Use only a 1/2" black iron pipe and appropri-

ate fittings. 

1.  Remove knockout indentation on refrac-

tory or firebrick wall located approximately 

2" above refractory hearth floor. Knockout 

indentation must be firmly tapped with any 

solid object such as a 1/2" dowel until it is 

released. Remove fragmented portions of 

refractory (see Figure 29).

2.  Remove gas line cover plate located on 

rear  of  fireplace  and  pull  out  insulation 

from gas line conduit sleeve. Save insula-

tion for reuse. 

3.  Run gas line into fireplace through the rear 

at 11 

1

/

4

" from floor and through gas line 

conduit sleeve (if using a raised platform, 

add height). Provide sufficient gas line into 

fireplace  chamber  for  fitting  connection 

(see Figure 30). 

Note:

 

Secure incoming 

gas line to wood framing to provide rigidity 

for threaded end.

4.  Repack insulation around gas line and into 

sleeve opening. Seal any gaps between 

gas line and refractory knockout hole with 

refractory cement or commercial furnace 

cement, Install gas appliance or cap off 

gas line if desired.

Seal 

Opening 

with 

Refractory 

Cement

Outside of 

Fireplace

Gas 

Line 

Conduit

Repack 

Insulation

Incoming 

1/2" Black 

Iron Pipe

Side 

Firebrick 

Finished 

Side

Provide Enough Threaded 

End for Fitting Connection

Figure 30 - Gas Line Installation

Summary of Contents for (V)PN36-A

Page 1: ...ved to ANS Z21 60 Z21 84 standards or for use with a vent free gas log heater approved to ANS Z21 11 2 standard This wood burning fireplace complies with UL127 CAN ULS S610 M87 standard as a FACTORY BUILT APPLIANCE FOR CANADA The authority having jurisdiction such as the municipal building department fire department etc should be contacted before installation to deter mine the need to obtain a per...

Page 2: ...FMI PROD UCTS LLC fireplace system Proper installation is the most important step in ensuring safe and continuous operation of the fireplace Although grounding may not be required by code in your area it must be electrically grounded in accordance with lo cal codes or in the absence of local codes with the National Electrical Code ANSI NFPA 70 This fireplace is intended for installation in ac cord...

Page 3: ...lways leave glass doors fully opened or fully closed when operating fireplace WARNING Children and adults should be alerted to the hazardsofhighsurfacetempera tures and to stay away to avoid burns or clothing ignition Young children should be carefully su pervised when in the same room as fireplace Figure 1 V PN36 A Dimensions Nailing Flanges 21 19 12 10 1 4 40 12 3 7 11 1 4 36 1 2 37 1 2 22 5 8 6...

Page 4: ... may be ideal for a new addition on an existing finished wall Minimum clearance to combustibles Back and sides of fireplace 1 2 min Adjacent wall 12 min Chimney outer pipe surfaces 2 min Bottom of fireplace to floor 0 min WARNING Do not block required air spaces with insu lation or any other material Do notobstructeffectiveopeningof fireplace with any type of facing material Combustible material m...

Page 5: ...ugh flanges located on sides of the fireplace see Figure 8 Fireplace Installation Continued 1 2 MIN OVERLAP 1 2 MIN Figure 7 Ember Protectors Figure 8 Nailing Flanges Nailing Flanges Prepared Framing Nails or Screws 1 2 Minimum to Combustibles Hearth Extension A hearth extension projecting a minimum of 16 in front of and a minimum of 8 beyond each side of the fireplace opening is required to prote...

Page 6: ...ing of the fireplace due to the nature of it s location Outside combustion air is accessed through and exterior wall or a vented crawl space CAUTION Air inlet ducts must not terminate in attic space The maximum height for the air vent can not exceed 3 feet below the flue gas outlet of the termination For further details on installation of outside air kit please refer to instructions included with ...

Page 7: ...imney together exception see Figure 17 page 8 WARNING The opening in the collar around the chimney at the top of the fireplace must not be obstructed Neveruseblowninsula tion to fill the chimney enclosure Figure 13 Outside Air Kit Installation Secure to Collars with Duct Tape or Screws Air Inlet Location Must Allow For Bushes or Snow Vent Hood Required for Wall Installation Air Inlet Termination V...

Page 8: ...FS 10 Firestop spacers are required at each point where the chimney penetrates a floor or ceiling joist space Their purpose is to establish and maintain the required clearance between the chimney and the combustible materials When penetrating a floor or ceiling at an angle use firestop spacer number 30FS 10 see Re placement and Accessory Parts page 15 When the pipe passes through a framed open ing...

Page 9: ...uter pipe of chimney with screws if screws do not penetrate inner flue pipe Figure 22 Maximum Chimney Height Storm Collar Flashing Firestop Spacer RLT 12D RLT 12D STL 12D Minimum Maximum Chimney Height The minimum height of the chimney mea sured from the base of the fireplace to the flue gas outlet end of pipe is 16 feet for a straight run 16 feet minimum for a run with 1 elbow set and 25 feet min...

Page 10: ...erproof Caulk Storm Collar Flashing Flashing Installation Determine flashing to be used with roof open ing chart Slide flashing over pipe until base is flat against roof Replace as many shingles as needed to cover exposed area and flashing base Secure in position by nailing through shingles see Figure 24 DO NOT NAIL THROUGH FLASHING CONE Storm Collar Installation Place storm collar over pipe and s...

Page 11: ...tile or other noncom bustible materials may overlap the front face provided they do not obstruct essential open ings like louvered slots or any other opening When overlapping with a noncombustible facing material use only noncombustible mortar or adhesive Installing fireplace facing Any noncombustible material may be used for facing glass tile brick etc as long as proper clearances are adhered to ...

Page 12: ...automatic shutoff device and must comply with the Standard for Decora tive Gas Appliances for Installation in Vented Fireplace ANSI Z21 60 ONLY UNVENTED GAS LOG SETS WHICH HAVE BEEN FOUND TO COMPLY WITH THE STANDARD FOR UNVENTED ROOM HEATERS ANSI Z21 11 2 ARE TO BE INSTALLED IN THIS FIREPLACE Use only a 1 2 black iron pipe and appropri ate fittings 1 Remove knockout indentation on refrac tory or f...

Page 13: ... chimney cleaner Creosote will ignite if heavily heated WARNING When using a decorative vented gas log the damper must be removed or permanently locked in the fully open position and the glass doors must be in the fully open position Note An appropriate FMI PRODUCTS LLC hood see Replacement and Accessory Parts page 15 must be installed when using an unvented gas log set Operation and Maintenance G...

Page 14: ...calling please have your model and serial numbers of your heater ready You can also visit web site at www fmiproducts com damper Mechanism The damper control lever is located inside the fire chamber see Figure 32 Make sure lever is cool before handling Pull down to close and push up to open Damper must be open when lighting a fire Not doing so will cause smoke spillage into the room When fireplace...

Page 15: ...Double Wall Pipe support assembly 12S 12DM Also available in triple wall Outside Air Kit AK4 Vent Plaster Collar Vent Hood Connector Duct 4 x 3 Storm Collar SC2 1 Firestop Spacer FS 10 for Straight Pipe 30FS 10 for 30 Angled Run Flashing V6F 10DM 0 to 6 12 Pitch V12F 10DM 6 12 to 12 12 Pitch Round Top Termination RLT 12D Econo Top Termination STL 12D Bi Fold Glass Doors DG368ST Brushed Brass DBP36...

Page 16: ...115607 01 Rev D 09 09 2701 S Harbor Blvd Santa Ana CA 92704 1 866 328 4537 www fmiproducts com ...

Reviews: