background image

www.fmiproducts.com

119315-01D

8

The space in the example is a confined space 

because the actual Btu/Hr used is more than the 
maximum  Btu/Hr  the  space  can  support.  You 
must  provide  additional  fresh  air. Your  options 
are as follows:

A.  Rework worksheet, adding the space of an 

adjoining room. If the extra space provides an 

unconfined space, remove door to adjoining 

room or add ventilation grills between rooms. 
See 

Ventilation Air From Inside Building

.

B.  Vent  room  directly  to  the  outdoors.  See 

Ventilation Air From Outdoors

.

C.  Install a lower Btu/Hr fireplace, if lower Btu/Hr 

size makes room unconfined. 

If the actual Btu/Hr used is less than the maximum 

Btu/Hr  the  space  can  support,

 

the  space  is  an 

unconfined  space.  You  will  need  no  additional 

fresh air ventilation.

 WARNING: If the area in which 

the  heater  may  be  operated  is 

smaller  than  that  defined  as 

an  unconfined  space  or  if  the 

building  is  of  unusually  tight 

construction, provide adequate 

combustion and ventilation air 

by one of the methods described 

in the 

National Fuel Gas Code, 

ANSI Z223.1/NFPA 54 Section 5.3

 

or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside building 

This  fresh  air  would  come  from  an  adjoining 
unconfined  space.  When  ventilating  to  an 

adjoining unconfined space, you must provide 
two permanent openings: one within 12" of the 
ceiling and one within 12" of the floor on the 

wall connecting the two spaces (see options 1 

and 2, Figure 4). You can also remove door into 
adjoining room (see option 3, Figure 4). Follow 

the 

National  Fuel  Gas  Code, ANSI  Z223.1/

NFPA  54,  Section  5.3,  Air  for  Combustion 
and Ventilation

 for required size of ventilation 

grills or ducts.

Ventilation Air From Outdoors

Provide  extra  fresh  air  by  using  ventilation 

aiR FoR CoMBUsTioN 

aND VENTilaTioN

Continued

grills or ducts. You must provide two perma-

nent openings: one within 12" of the ceiling 
and one within 12" of the floor. Connect these 

items directly to the outdoors or spaces open 
to the outdoors. These spaces include attics 
and crawl spaces. Follow the 

National Fuel 

Gas  Code, ANSI  Z223.1/NFPA  54,  Section 
5.3, Air  for  Combustion  and  Ventilation

  for 

required size of ventilation grills or ducts.

IMPORTANT: 

Do  not  provide  openings  for 

inlet or outlet air into attic if attic has a thermo-
stat-controlled power vent. Heated air entering 
the attic will activate the power vent.

Figure 4 - Ventilation Air from Inside 

Building

Or 

Remove 

Door into 
Adjoining 

Room, 

Option 3

Ventilation Grills 

Into Adjoining Room,

Option 2

12"

12"

Ventilation

Grills

into

Adjoining

Room, 

Option 1

Figure 5 - Ventilation Air from Outdoors

Outlet 

Air 

Ventilated 

Attic  

Outlet 

Air 

Inlet 

Air 

Inlet Air 

Ventilated  

Crawl Space 

To  

Crawl 

Space 

To Attic 

Summary of Contents for CGMFN

Page 1: ...h do not use any phone in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a quali fied installer service agency or the gas supplier INSTALLER Leave this manual with the appliance CONSUMER Retain this manual for future reference UNVENT...

Page 2: ...s supplier WARNING This is an unvented gas fired heat er It uses air oxygen from the room in which it is installed Provisions for adequate combustion and ventilation air must be provided Refer to Air for Combustion and Ven tilation section on page 6 of this manual This appliance may be in stalled in an aftermarket permanently located manufactured mobile home where not prohib ited by local codes Th...

Page 3: ...peratures the appliance should be located out oftrafficandawayfromfurniture and draperies SAFETY INFORMATION Continued Do not place clothing or other flammable material on or near the appliance Never place any objects on the heater Fireplace front and screen be come very hot when running heater Keepchildrenandadults away from hot surfaces to avoid burns or clothing ignition Fire place will remain ...

Page 4: ...s a wood burn ing fireplace Use only the logs provided with the fireplace 6 Do not add extra logs or ornaments such as pine cones vermiculite or rock wool Using these added items can cause soot ing Do not add lava rock around base Rock and debris could fall into the control area of fireplace 7 This fireplace is designed to be smokeless If logs ever appear to smoke turn off fire place and call a qu...

Page 5: ... thermostat hand held thermostat remote See Accessories page 34 Assembly WARNING Always have screeninplacebeforeoperating fireplace This prevents exces sive temperatures on fireplace surfaces WARNING Failure to posi tion the parts in accordance with these diagrams or failure to use only parts specifically approved with this fireplace may result in property damage or personal injury Assembling Fire...

Page 6: ...ur home needs to breathe Fresh air must enter your home All fuel burning ap pliances need fresh air for proper combustion and ventilation Exhaust fans fireplaces clothes dryers and fuel burning appliances draw air from the house to operate You must provide adequate fresh air for these appliances This will insure proper venting of vented fuel burning appli ances PROVIDING ADEQUATE VENTILATION The f...

Page 7: ...only if there are doorless passageways or ventilation grills between them AIR FOR COMBUSTION AND VENTILATION Continued DETERMINING FRESH AIR FLOW FOR FIREPLACE LOCATION Determining if You Have a Confined or Unconfined Space Use this work sheet to determine if you have a confined or unconfined space Space Includes the room in which you will install fireplace plus any adjoining rooms with door less ...

Page 8: ...unconfined space you must provide two permanent openings one within 12 of the ceiling and one within 12 of the floor on the wall connecting the two spaces see options 1 and 2 Figure 4 You can also remove door into adjoining room see option 3 Figure 4 Follow the National Fuel Gas Code ANSI Z223 1 NFPA 54 Section 5 3 Air for Combustion and Ventilation for required size of ventilation grills or ducts...

Page 9: ...n and Ventilation page 6 Note Your fireplace is designed to be used in zero clearance installations Wall or framing ma terial can be placed directly against any exterior surfaceontherear sidesortopofyourfireplace except where standoff spacers are integrally at tached If standoff spacers are attached to your fireplace these spacers can be placed directly against wall or framing materials Note When ...

Page 10: ...ficiency install fire place where there is easy access for operation inspection and service in coldest part of room MinimumClearancesForSideCombustible Material Side Wall and Ceiling A Clearances from the side of the fireplace cabinet to any combustible material and wall should follow diagram in Figure 6 Example The face of a mantel bookshelf etc is made of combustible material and protrudes 3 1 2...

Page 11: ...ning for Installing in Wall 297 8 211 8 421 4 171 2 IMPORTANT When finishing your firebox combustible materials such as wall board gypsum board sheet rock drywall plywood etc may be butted up next to the sides and top edge of the firebox Combustible materials should never overlap the firebox front facing WARNING Do not allow any combustibleornoncombustible materials to overlap the firebox front fa...

Page 12: ...rebasetofloorusingwoodscrews Countersink screw heads and putty over 3 Route flexible gas line through access hole in hearth base 4 Center cabinet mantel on hearth base see Figure 11 Make sure mantel is flush against wall and centered left to right on base 5 Use hardware provided with mantel ac cessory to attach mantel assembly to base see mantel instruction sheet 6 Attach flexible gas line to fire...

Page 13: ...oming gas pressure fireplace regulator damage could occur Install external regula tor with the vent pointing down as shown in Figure 13 Pointing the vent down protects it from freezing rain or sleet Propane LP Supply Tank External Regulator Figure 13 External Regulator With Vent Pointing Down Vent Pointing Down CAUTION Use only new black iron or steel pipe Inter nally tinned copper tubing may be u...

Page 14: ...lexible gas line is provided to allow acces sibility from the fireplace see Figure 1 page 5 The flexible gassupplylineconnectiontothe equipment shutoff valve should be accessible Figure 15 Attaching Flexible Gas Line to Equipment Shutoff Valve Flexible Gas Line from Fireplace Gas Regulator Provided With Fireplace To Gas Regulator Manual Controlled Models or Control Valve Remote Ready Models Equipm...

Page 15: ... gas valve located on or near gas meter for natural gas or using compressed air 4 Check all joints of gas supply piping system Apply noncorrosive leak detection fluid to all joints Bubbles forming show a leak 5 Correct all leaks at once 6 Reconnect fireplace and equipment shutoff valve to gas supply Check recon nected fittings for leaks Test Pressures Equal To or Less Than 1 2 PSIG 3 5 kPa 1 Close...

Page 16: ...e OFF position 4 Check all joints from equipment shutoff valve to gas regulator Manual Controlled Models or to gas control valve Remote Ready Models see Figures 17 or 18 page 15 Apply noncorrosive leak de tection fluid to all joints Bubbles forming show a leak 5 Correct all leaks at once 6 Light fireplace see Operating Fireplace page 18 Check all other internal joints for leaks 7 Turn off fireplac...

Page 17: ...d air conditioning ducts 5 Gently remove the cover of the thermostat from the base Grasp the sides of the cover firmly and pull to separate from the base 6 Feed the electrical wires through the rect angular slots on each side of the base see Figure 20 WARNING Do not con nect the thermostat to a power source Electrical shock and or a fire hazard will occur 7 Connect one bare wire end to each termi ...

Page 18: ...he burner see Figure 22 Do not allow log to contact flame If flame contacts log soot will be created 2 Reattach screen by placing the notches in the screen frame over the shoulder screws and pushing down INSTALLATION Continued Log Shoulder Screw Screen Figure 22 Installing Log and Screen Operating Fireplace MANUAL Controlled Models FOR YOUR SAFETY READ BEFORE LIGHTING WARNING If you do not fol low...

Page 19: ... the first time after hooking up to gas supply If so the control knob may need to be pressed in for 30 seconds or more This will allow air to bleed from the gas system If control knob does not pop out when released contact a qualified service person or gas supplier for repairs 6 With control knob pressed in press and release ignitor button see Figure 23 This will light pilot The pilot is attached ...

Page 20: ...se any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department C Use only your hand to push in or turn the gas control knob Never use tools If the knob will not push in or turn by hand don t try to repair it call a quali fied service technician or gas supplier Force or at...

Page 21: ...s out repeat steps 4 through 8 8 Slightly push in and turn control knob counterclockwise to the ON position CAUTION Do not try to ad just heating levels by using the equipment shutoff valve 9 To turn off burner and leave pilot lit Turn control knob clockwise to the PILOT position If using optional hand held remote set remote switch to the OFF position to prevent draining battery TO TURN OFF GAS TO...

Page 22: ...e sure the heater switch is on REMOTE and set the temperature adjustment on wall thermostat to the desired setting The thermostat has been electronically calibrated at the factory and requires no adjustment or leveling Upon installation the thermostat must be allowed to stabilize at room temperature for a minimum of 30 minutes for proper operation See installation instructions on page 17 of this m...

Page 23: ...blue and have no yellow or orange color Figure 30 Correct Pilot Flame Pattern Propane LP Remote Ready Shown Pilot Burner Thermocouple Figure 31 Incorrect Pilot Flame Pattern Propane LP Remote Ready Shown Pilot Burner Thermocouple BURNER FLAME PATTERN Figure 32 shows a correct burner flame pat tern Figure 33 shows an incorrect burner flame pattern The incorrect burner flame pattern shows sporadic i...

Page 24: ... compressed air in a can please follow the directions on the can If you don t follow directions on the can you could dam age the pilot assembly 1 Shut off the unit including the pilot Allow the unit to cool for at least thirty minutes 2 Inspect burner pilot and primary air inlet holes on injector holder for dust and dirt see Figure 34 3 Blow air through the ports slots and holes in the burner 4 Ch...

Page 25: ... Battery not installed bat tery power low or battery not installed correctly REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 3 Replace ignitor cable 4 Replace ignitor 5 Replace pilot assembly 6 Replace pilot assembly 7 Install new alkaline battery in electronic ignitor Verify battery is installed cor rectly OBSERVED PROBLEM Whenignitor...

Page 26: ...ressure is too low 2 Burner orifice is clogged 3 Thermopile leads discon nected or improperly con nected Remote Ready Models Only 4 Burners will not come on in remote position Remote Ready Models Only REMEDY 1 Turn on gas supply or open equipment shutoff valve 2 Turn control knob to PILOT position 3 Press in control knob while in PILOT position 4 Continue holding down con trol knob Repeat igniting...

Page 27: ...olish wax carpet cleaners etc may turn into white powder residue 1 Not enough combustion ventilation air REMEDY 1 Contact local natural or propane LP gas company 2 Clean burner see Cleaning and Maintenance page 24 or replace burner orifice 1 Clean burner see Cleaning and Maintenance page 24 or replace burner orifice 2 Replace damaged burner 3 Replace gas regulator 4 Contact local natural or propan...

Page 28: ... is partially clogged 1 Gas leak See Warning statement at top of page 2 Control valve defective 1 Foreign matter between control valve and burner 2 Gas leak See Warning statement at top of page REMEDY 1 Replace batteries in receiver and remote control 1 This is normal with most fireplaces If noise is ex cessive contact qualified service person 1 Open window to venti late room Stop using odor causi...

Page 29: ...place was malfunctioning type of gas used propane LP or natural gas purchase date Usually we will ask you to return the part to the factory Parts Not Under Warranty Contact authorized dealers of this product If they can t supply original replacement part s call FMI PRODUCTS LLC at 1 866 328 4537 for referral information When calling FMI PRODUCTS LLC have ready model number of your fireplace the re...

Page 30: ...5 01D 30 1 2 34 41 42 41 3 39 4 32 15 16 20 41 41 41 29 26 27 30 14 28 34 23 33 38 21 22 31 43 17 25 36 40 35 40 15 16 24 34 19 18 5 6 7 8 9 34 11 13 10 37 12 Illustrated Parts Breakdown MANUAL controlled models CGMFN AND CGMFP ...

Page 31: ...itor Cable 1 27 107486 01 ODS Pilot Propane LP Gas 1 107485 01 ODS Pilot Natural Gas 1 28 119425 03 Injector NG 1 119425 01 Injector LP 1 29 099387 08 Pilot Tube 1 30 112881 03 Pilot Shield 1 31 097809 03 Male Fitting 1 32 099230 02 Screw HWH Shoulder AB 10 X 63 4 33 098303 02 Screw SHWH AB 6 20 x 31 2 34 M15823 27 Screw PHWH B 10 16 x 50 13 35 M12461 62 Screw Hex SLT WSR 1 4 20 x 38 1 36 102874 0...

Page 32: ...3 33 33 27 30 14 28 29 26 33 38 25 24 36 40 5 22 40 15 16 19 34 20 41 18 23 17 21 6 7 35 9 34 11 13 10 37 12 8 ILLUSTRATED PARTS BREAKDOWN REMOTE READY MODELS VGMRN and VGMRP AA Battery Positive UP AAA Battery Negative UP Install Battery According To This Illustration ...

Page 33: ...lve Bracket 1 20 119416 01 Elbow Male 1 2 MPT x 3 8 Flare 1 21 098264 03 Connector 3 8 MPT x 1 2 Flare 1 22 119318 01 Outlet Tube 1 099415 09 Outlet Tube 1 23 101628 04 Flexible Connector 1 24 118606 01 Ignitor Bracket 1 25 111435 01 Electronic Ignitor 1 26 098271 12 Ignitor Cable 1 27 103778 01 ODS Pilot Propane LP Gas 1 112376 01 ODS Pilot Natural Gas 1 28 119425 01 Injector LP 1 119425 02 Injec...

Page 34: ...sic lines Complete assembly instructions included WALL MOUNT THERMOSTAT SWITCH GWMT1 Not Shown For all Remote Ready Models The desired comfort setting can be selected on the wall thermostat and the fireplace will automatically cycle from pilot to the heat setting selected WALL MOUNT ON OFF SWITCH GWMS2 Not Shown For all Remote Ready Models Allows the fireplace to be turned on and off with a wall s...

Page 35: ..._____________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ________________________________...

Page 36: ...is product and or FMI PRODUCTS LLC who will provide original factory replacement parts Failure to use original factory replacement parts voids this warranty Travel handling transportation diagnostic material labor and incidental costs associated with warranty repairs unless expressly covered by this warranty are not reimbursable under this warranty and are the responsibility of the owner Excluded ...

Reviews: