www.fmiproducts.com
126454-01B
16
INSTALLATION
Continued
Figure 19 - Remote Control Receiver
ON
OFF
REM
OTE
Remote
Control
Receiver
Convertible
Gas Valve
GAS SUPPLY TESTING
NOTICE: This section is in-
tended as a guide for qualified
technicians installing gas to the
appliance.
WARNING: Do not connect
appliance before pressure test
-
ing gas piping. Damage to gas
valve may result and an unsafe
condition may be created.
Appliance and its individual shutoff valve
must be disconnected from gas supply piping
system during any pressure testing of that
system at test pressures in excess of 1/2 psig
(3.5 kPa).
Appliance must be isolated from gas supply
piping system by closing its individual shutoff
valve during any pressure testing of gas sup-
ply piping system at test pressures equal to
or less than 1/2 psig (3.5 kPa).
Gas control valve is secured under firebox.
Two 1/8" ports are provided on gas control
valve for pressure test gauge connections
(see Figure 20).
Figure 20 - Gas Control Valve
ON/OFF
Knob
Pilot Adjustment
Inlet
Pressure Outlet
Pressure
Flame
Adjustment Knob
Pilot Gas Line
Do Not Kink
To Pilot
Burner
To Main
Burner
GAS LINE HOOK-UP
WARNING: Gas line hook-
up should be done by your gas
supplier or a qualified service
person.
WARNING: Before you pro
-
ceed, make sure your gas supply
is OFF.
An equipment shutoff valve has been included
in fireplace's gas supply system. Consider
installing an extra shutoff valve outside appli-
ance’s enclosure (check local codes), where it
can be accessed more conveniently with a key
through a wall as shown in Figure 21.
In conformance with local codes, route a 1/2"
NPT gas line towards appliance coming in
from bottom, left or right side of fireplace (see
Figure 22, page 17).
Install a sediment trap between incoming
gas line and gas control box (see Figure 23,
page 17). The sediment trap should extend
down a minimum of 3" (7.62 cm) beyond
center of pipe.
Figure 21- Typical Exterior Wall Gas
Shutoff Installation
Key
Extension
Shutoff
Valve
The remote control receiver is factory wired
and connected to the convertible gas valve
as shown in Figure 19.
f i r e - p a r t s . c o m