background image

www.fmiproducts.com

125192-01B

5

Figure 4 - Nailing Flanges

Screw 

or Nail

Nailing 

Flange

FIREPLACE INSTALLATION

Continued

Figure 5 - Hearth Extension

Seal Gap

Fireplace 

Front

Ember 

Protector

Ember 

Protector

Seal Gap

Hearth 

Extension

FRAMING

1.  Frame opening for fireplace using dimen

-

sions shown in Figures 1 and 2.

2.  If  fireplace  is  to  be  installed  directly  on 

carpeting, tile (other than ceramic) or any 

combustible  material  other  than  wood 

flooring, fireplace must be installed on a 

metal or wood panel extending full width 

and depth of fireplace. (It is acceptable to 

cover two outside ends or columns of top 

louver panel leaving four center columns 

open).

3.  Set fireplace directly in front of this open

-

ing and slide unit back until nailing flanges 

touch side framing.

4.  Check  level  of  fireplace  and  shim  with 

sheet metal if necessary.

5.  Before securing fireplace to prepared fram

-

ing, metal ember protector (provided) must 

be placed between hearth extension (not 

supplied) and under bottom front edge of 

fireplace to protect against glowing embers 

falling through. If fireplace is to be installed 

on a raised platform, a Z-type ember pro

-

tector (not supplied) must be fabricated to 

fit  your  required  platform  height.  Ember 

protector  should  extend  under  fireplace 

a minimum of 1 

1

/

2

". The ember protector 

should be made of metal material.

6.  Using screws or nails, secure fireplace to 

framing through flanges located on sides 

of fireplace (see Figure 4).

HEARTH EXTENSION

A hearth extension projecting a minimum of 

16" in front of and a minimum of 8" beyond 

each side of the fireplace opening is required 

to  protect  combustible  floor  construction  in 

front of the fireplace. Use an equal material 

which  meets  the  following  specifications:  a 

layer  of  noncombustible,  inorganic  material 

having a thermal conductivity of K=0.84 BTU 

IN/FT, HR. F (or less) at 1" thick. For example, 

if the material selected has a K factor of 0.25, 

such  as  glass  fiber,  the  following  formula 

would apply:

 

0.25

 x 1.0" = 0.30" thickness required

 

0.84

Thermal conductivity "K" of materials can be 

obtained from the manufacturer or supplier of 

the noncombustible material. If the hearth ex

-

tension is to be covered, use noncombustible 

material such as tile, slate, brick, concrete, 

metal,  glass,  marble,  stone,  etc.  Provide 

a  means  to  prevent  hearth  extension  from 

shifting and seal gap between fireplace frame 

and hearth extension with a noncombustible 

material (see Figure 5). 

 WARNING: Hearth extension 

is to be installed only as shown 

in Figure 5.

Fireplace Front

Elevated

Summary of Contents for 36EMW-RBC

Page 1: ...andard A vent free log can only be installed in an aftermarket completion of sale not for purpose of resale from the manufacturer permanently located manufactured mobile home where not prohibited by local codes Ap proved hood must be installed when using a vent free gas log heater see Accessories page 18 This firebox meets the construction and safety stan dards of H U D for application in mobile h...

Page 2: ...PFS Corporation WARNING Improper instal lation adjustment alteration service or maintenance can causeinjury propertydamageor loss of life Refer to this manual for assistance or additional in formation Consult a qualified installer or local distributor IMPORTANT Check HUD re quirementsbeforeinstallingthis fireplace The 36EMW Series is specifically designed for use in manufactured mobile homes These...

Page 3: ...ear View of Fireplace Opening for Outside Air Firestop Thimble 91 2 14 14 FIREPLACE INSTALLATION SELECTING LOCATION To determine the safest and most efficient location for the fireplace you must take into consideration the following guidelines 1 The location must allow for proper clear ances see Figures 1 and 2 page 4 2 Consider a location where the heat output will not be affected by drafts air c...

Page 4: ...0 feet This measurement includes fireplace chim ney sections and height of termination assem bly at level of flue gas outlet see Figure 3 For manufactured home application minimum height is 11 for straight flue or flue with one elbow set Maximum height of any system is 20 Figure 3 Standard and Alternate Venting Installation Effective Height of Termination Cap Effective Height of Termination Cap RT...

Page 5: ... must be fabricated to fit your required platform height Ember protector should extend under fireplace a minimum of 1 1 2 The ember protector should be made of metal material 6 Using screws or nails secure fireplace to framing through flanges located on sides of fireplace see Figure 4 HEARTH EXTENSION A hearth extension projecting a minimum of 16 in front of and a minimum of 8 beyond each side of ...

Page 6: ...pleted during the rough framing of fireplace due to nature of its location The supplied flex duct measures approximately 10 compressed and up to approximately 36 extended Outside combustion air is accessed through mobile home floor using air kit model AK6E or a side wall using air kit model AK6 WE see Accessories on page 18 Installer may choose either left or right side mounting to allow for prope...

Page 7: ...ill not be obstructed by bushes snow etc Locate vent near the fireplace to make flex duct installation easier CHIMNEY PIPE The chimney system approved for this fireplace consists of 12 18 24 36 and 48 snap lock double wall pipe segments planned for maximum adaptability to individual site requirements Actual lengths gained after fitting overlaps must be taken into consider ation lineal gain and are...

Page 8: ... by pulling chimney upward after locking Chimney will not come apart if properly locked It is not neces sary to add screws to keep chimney together exception see Figure 14 page 11 ADJUSTABLE FIRESTOP THIMBLE FST A Adjustable Firestop ThimbleAssembly FST A is used to provide necessary air space and clearance between chimney pipe and insula tion in attic space of a manufactured home To install thimb...

Page 9: ...y 12 A6 12 pitch means that the roof drops 6 for each 12 measured horizontally down from roof rafters 3 Use roof opening chart Figure 11 to determine correct opening length and flashing required 4 Remove shingles around opening mea sured Cut out this section 5 Add next sections of pipe until end pen etrates roof line Check to see that proper clearances are maintained Extend chim ney by adding sect...

Page 10: ...e desired offset you may install combinations of 12 18 24 36 and 48 length of double wall pipe see offset chart and Figure 12 OFFSET CHART 22 50 FT SYSTEM HEIGHT Figure 13 Ceiling Support Pipe 12S 8DM Straps Straps Straps Straps Detail A Return Elbow Detail B Angle Firestop See Detail A See Detail B Figure 12 Elbow Offset B A Screws 2 Chimney weight above offset rests on return elbow Straps must b...

Page 11: ...pacer with Living Space Above Ceiling Existing Ceiling Frame Firestop Spacer Screws or Staples Min of 8 FLASHING INSTALLATION V6F 8DM OR V12F 8DM Determine the flashing to be used with the roof opening chart Slide flashing over pipe until base is flat against roof Replace as many shingles as needed to cover exposed area and flashing base Secure in position by nail ing through shingles see Figure 1...

Page 12: ... a vertical height difference of 18 see Figure 19 24 Min 24 Min 18 Min Typ Figure 19 Multiple Chase Installation Figure 17 Storm Collar Chimney Pipe Waterproof Caulk Storm Collar Flashing Fireplace system must be terminated with listed round top termination In any case refer to installation instructions supplied with termi nation Terminations approved for this fireplace are RT 8DM and RTL 8DM Figu...

Page 13: ...er or a qualified service person Note Before you proceed make sure your gas supply is turned off A gas line may be installed for the purpose of installing a vented or vent free appliance available through your local distributor Use only a 1 2 black iron pipe and appropriate fittings When installing a gas line a shutoff valve designed for installation outside appli ance is recommended 1 Remove knoc...

Page 14: ... BYAQUALI FIED SERVICE PERSON Note Secure incoming gas line to wood fram ing to provide rigidity for threaded end If you wish to install an unvented vent free gas log set ONLY UNVENTED GAS LOG SETS WHICH HAVE BEEN FOUND TO COMPLY WITH THE STANDARD FOR UNVENTED ROOM HEATERS ANSI Z21 11 2 ARE TO BE INSTALLED IN THIS FIREPLACE Avent free log may be installed in an aftermar ket permanently located man...

Page 15: ...3 GLASS DOORS Glass doors are standard with fireplace When fireplace is in operation doors must be FULLY OPENED or FULLY CLOSED position only or a fire hazard may be created see Figure 25 A fireplace equipped glass doors operates much differently than a fireplace with an open front Afireplace with glass doors has a limited amount of air for combustion Excessive heat within fireplace can result if ...

Page 16: ...ly loosen lower pivot clips and upper spring clips Replace doors and fully close them Use 1 8 shims any material to level doors Once proper setting is achieved carefully open doors enough so that you can access spring clips with a phillips screwdriver Tighten screws See Figure 27 Figure 27 Adjusting Bi Fold Doors CLEANING GLASS Clean the glass with any commercial glass cleaner or soap and water Do...

Page 17: ... Note Use only original replacement parts This will protect your warranty coverage for parts replaced under warranty When calling or writing please have your model and serial numbers of your fireplace ready Model and serial number information are in the fireplace s rating plate located on the smoke shelf on the top right side of the fireplace opening OPERATION AND MAINTENANCE GUIDELINES Continued ...

Page 18: ... Support Bracket Self Drilling Screws Cable Ferrule Eye Bolt Screw Strand Wire 50 ft FIRESTOP SPACER 3600FS 8DM 1 BI FOLD GLASS DOORS VDG36E Brushed Finish DP36E Platinum Finish VDBP36E Black Finish EMBER PROTECTOR 20093 GRATE 11116 BRICK LINER Rear PN 20029 Left Side PN 20030 Right Side PN 20030 Front Bottom PN 21242 Rear Bottom PN 21241 OPTIONAL OUTSIDE AIR KIT FOR FLOOR INSTALLATION 90154 Model...

Page 19: ... installing a vent free gas log heater in this firebox ADJUSTABLE FIRESTOP THIMBLE FST A Includes Thimble PN 22383 Adapter Plate PN 22398 For Flat or 12 96 Pitch Ceilings Only Firestop PN 22377 ROUND TOP TERMINATION RTL 8DM 12 96 Pitch 30 144 Pitch 7 13 11 77 144 96 12 30 SQUARE CHASE TOP TERMINATION ETL 8DM ACCESSORIES Continued OPTIONAL OUTSIDE AIR KIT FOR SIDE WALL INSTALLATION AK 6WE HEARTH EX...

Page 20: ... 2 24 8DM 24 Double Wall Pipe 1 0 18 8DM 18 Double Wall Pipe 0 2 FST A Adjustable Firestop Thimble 1 1 V6F 8DM Roof Flashing 1 1 SC1 1 Storm Collar 1 1 RTL 8DM Round Cap Termination 1 1 Use for Most Common Manufactured Mobile Home Installations FACE EXTENSION FE 36R Front face extension would add 6 to the width and 6 to the height of the fireplace face FLEX DUCT 6 X 25 3 PACK MP6 75 AIR INLET HOOD...

Reviews: