background image

www.fmiproducts.com

125192-01B

15

FINISHING FIREPLACE

12 

1

/

4

" Ref.

6"

Ref.

12" 

Min.

9" Min.

1

1

/

2

" Max.

3" Nom.

33°

Combustible 

Material

Safe 

Zone for 

Projection of 

Combustible 

Materials

Fireplace 

Opening

Upper 

Section of 

Fireplace

Figure 24 - Mantel Clearances to 

Combustible Material

OPERATION AND MAINTENANCE GUIDELINES

Figure 25 - Bi-Fold Glass Doors

Doors Fully Closed

Fireplace Front

Doors

Fully Opened

Fireplace Front

Combustible  materials,  such  as  wallboard, 

gypsum board, sheet rock, drywall, plywood, 

etc. may make direct contact with sides and 

top around the fireplace face. It is important that 

combustible materials do not overlap the face 

itself. Brick, glass, tile or other noncombustible 

materials may overlap the front face provided 

they do not obstruct essential openings like lou

-

vered slots or any other opening. When overlap

-

ping with a noncombustible facing material, use 

only noncombustible mortar or adhesive.

MANTELS

A  mantel  may  be  installed  if  desired  (see 

Figure 24). Woodwork such as wood trims, 

mantels  or  any  other  combustible  material 

projecting  from  the  front  face  must  not  be 

placed  within  9"  of  the  fireplace  opening. 

Combustible materials above 9" and project

-

ing more than 1 

1

/

2

" from the fireplace must 

not  be  placed  less  than  12"  from  the  top 

opening  of  the  fireplace  (NFPA  STD  211, 

Sec. 7-3.3.3). 

GLASS DOORS

Glass  doors  are  standard  with  fireplace. 

When  fireplace  is  in  operation,  doors  must 

be  FULLY  OPENED  or  FULLY  CLOSED 

position only or a fire hazard may be created 

(see Figure 25).
A  fireplace  equipped  glass  doors  operates 

much differently than a fireplace with an open 

front. A fireplace with glass doors has a limited 

amount of air for combustion. Excessive heat 

within fireplace can result if too large a fire is 

built or if combustion air gate is not completely 

open. The following tips should be followed 

to assure that both fireplace and glass door 

retain  their  beauty  and  function  properly. 

Both flue damper and glass doors must be 

fully opened before starting the fire. This will 

provide sufficient combustion air and maintain 

safe temperatures in firebox.

IMPORTANT

:  Glass  must  be  allowed  to 

warm slowly and evenly. Tempered glass will 

withstand a gradual temperature rise to 550° 

Fahrenheit, which is more than a normal fire 

will generate.
Such materials as pitch/wax laden logs, very 

dry mill end lumber, and large amounts of pa

-

per or cardboard boxes can create an exces

-

sively hot fire and should not be burned in this 

fireplace. Always keep fire back from doors 

and never allow flames to contact glass.

 WARNING: Fireplaces 

equipped with glass doors 

should be operated only with 

doors fully opened or fully 

closed. Doors, if left partly open, 

may draw gas and flame out of 

the  fireplace  opening  creating 

risks of both fire and smoke.

Note:  HUD  requirements  may  supersede 

these minimum dimensions.

Summary of Contents for 36EMW-RBC

Page 1: ...andard A vent free log can only be installed in an aftermarket completion of sale not for purpose of resale from the manufacturer permanently located manufactured mobile home where not prohibited by local codes Ap proved hood must be installed when using a vent free gas log heater see Accessories page 18 This firebox meets the construction and safety stan dards of H U D for application in mobile h...

Page 2: ...PFS Corporation WARNING Improper instal lation adjustment alteration service or maintenance can causeinjury propertydamageor loss of life Refer to this manual for assistance or additional in formation Consult a qualified installer or local distributor IMPORTANT Check HUD re quirementsbeforeinstallingthis fireplace The 36EMW Series is specifically designed for use in manufactured mobile homes These...

Page 3: ...ear View of Fireplace Opening for Outside Air Firestop Thimble 91 2 14 14 FIREPLACE INSTALLATION SELECTING LOCATION To determine the safest and most efficient location for the fireplace you must take into consideration the following guidelines 1 The location must allow for proper clear ances see Figures 1 and 2 page 4 2 Consider a location where the heat output will not be affected by drafts air c...

Page 4: ...0 feet This measurement includes fireplace chim ney sections and height of termination assem bly at level of flue gas outlet see Figure 3 For manufactured home application minimum height is 11 for straight flue or flue with one elbow set Maximum height of any system is 20 Figure 3 Standard and Alternate Venting Installation Effective Height of Termination Cap Effective Height of Termination Cap RT...

Page 5: ... must be fabricated to fit your required platform height Ember protector should extend under fireplace a minimum of 1 1 2 The ember protector should be made of metal material 6 Using screws or nails secure fireplace to framing through flanges located on sides of fireplace see Figure 4 HEARTH EXTENSION A hearth extension projecting a minimum of 16 in front of and a minimum of 8 beyond each side of ...

Page 6: ...pleted during the rough framing of fireplace due to nature of its location The supplied flex duct measures approximately 10 compressed and up to approximately 36 extended Outside combustion air is accessed through mobile home floor using air kit model AK6E or a side wall using air kit model AK6 WE see Accessories on page 18 Installer may choose either left or right side mounting to allow for prope...

Page 7: ...ill not be obstructed by bushes snow etc Locate vent near the fireplace to make flex duct installation easier CHIMNEY PIPE The chimney system approved for this fireplace consists of 12 18 24 36 and 48 snap lock double wall pipe segments planned for maximum adaptability to individual site requirements Actual lengths gained after fitting overlaps must be taken into consider ation lineal gain and are...

Page 8: ... by pulling chimney upward after locking Chimney will not come apart if properly locked It is not neces sary to add screws to keep chimney together exception see Figure 14 page 11 ADJUSTABLE FIRESTOP THIMBLE FST A Adjustable Firestop ThimbleAssembly FST A is used to provide necessary air space and clearance between chimney pipe and insula tion in attic space of a manufactured home To install thimb...

Page 9: ...y 12 A6 12 pitch means that the roof drops 6 for each 12 measured horizontally down from roof rafters 3 Use roof opening chart Figure 11 to determine correct opening length and flashing required 4 Remove shingles around opening mea sured Cut out this section 5 Add next sections of pipe until end pen etrates roof line Check to see that proper clearances are maintained Extend chim ney by adding sect...

Page 10: ...e desired offset you may install combinations of 12 18 24 36 and 48 length of double wall pipe see offset chart and Figure 12 OFFSET CHART 22 50 FT SYSTEM HEIGHT Figure 13 Ceiling Support Pipe 12S 8DM Straps Straps Straps Straps Detail A Return Elbow Detail B Angle Firestop See Detail A See Detail B Figure 12 Elbow Offset B A Screws 2 Chimney weight above offset rests on return elbow Straps must b...

Page 11: ...pacer with Living Space Above Ceiling Existing Ceiling Frame Firestop Spacer Screws or Staples Min of 8 FLASHING INSTALLATION V6F 8DM OR V12F 8DM Determine the flashing to be used with the roof opening chart Slide flashing over pipe until base is flat against roof Replace as many shingles as needed to cover exposed area and flashing base Secure in position by nail ing through shingles see Figure 1...

Page 12: ... a vertical height difference of 18 see Figure 19 24 Min 24 Min 18 Min Typ Figure 19 Multiple Chase Installation Figure 17 Storm Collar Chimney Pipe Waterproof Caulk Storm Collar Flashing Fireplace system must be terminated with listed round top termination In any case refer to installation instructions supplied with termi nation Terminations approved for this fireplace are RT 8DM and RTL 8DM Figu...

Page 13: ...er or a qualified service person Note Before you proceed make sure your gas supply is turned off A gas line may be installed for the purpose of installing a vented or vent free appliance available through your local distributor Use only a 1 2 black iron pipe and appropriate fittings When installing a gas line a shutoff valve designed for installation outside appli ance is recommended 1 Remove knoc...

Page 14: ... BYAQUALI FIED SERVICE PERSON Note Secure incoming gas line to wood fram ing to provide rigidity for threaded end If you wish to install an unvented vent free gas log set ONLY UNVENTED GAS LOG SETS WHICH HAVE BEEN FOUND TO COMPLY WITH THE STANDARD FOR UNVENTED ROOM HEATERS ANSI Z21 11 2 ARE TO BE INSTALLED IN THIS FIREPLACE Avent free log may be installed in an aftermar ket permanently located man...

Page 15: ...3 GLASS DOORS Glass doors are standard with fireplace When fireplace is in operation doors must be FULLY OPENED or FULLY CLOSED position only or a fire hazard may be created see Figure 25 A fireplace equipped glass doors operates much differently than a fireplace with an open front Afireplace with glass doors has a limited amount of air for combustion Excessive heat within fireplace can result if ...

Page 16: ...ly loosen lower pivot clips and upper spring clips Replace doors and fully close them Use 1 8 shims any material to level doors Once proper setting is achieved carefully open doors enough so that you can access spring clips with a phillips screwdriver Tighten screws See Figure 27 Figure 27 Adjusting Bi Fold Doors CLEANING GLASS Clean the glass with any commercial glass cleaner or soap and water Do...

Page 17: ... Note Use only original replacement parts This will protect your warranty coverage for parts replaced under warranty When calling or writing please have your model and serial numbers of your fireplace ready Model and serial number information are in the fireplace s rating plate located on the smoke shelf on the top right side of the fireplace opening OPERATION AND MAINTENANCE GUIDELINES Continued ...

Page 18: ... Support Bracket Self Drilling Screws Cable Ferrule Eye Bolt Screw Strand Wire 50 ft FIRESTOP SPACER 3600FS 8DM 1 BI FOLD GLASS DOORS VDG36E Brushed Finish DP36E Platinum Finish VDBP36E Black Finish EMBER PROTECTOR 20093 GRATE 11116 BRICK LINER Rear PN 20029 Left Side PN 20030 Right Side PN 20030 Front Bottom PN 21242 Rear Bottom PN 21241 OPTIONAL OUTSIDE AIR KIT FOR FLOOR INSTALLATION 90154 Model...

Page 19: ... installing a vent free gas log heater in this firebox ADJUSTABLE FIRESTOP THIMBLE FST A Includes Thimble PN 22383 Adapter Plate PN 22398 For Flat or 12 96 Pitch Ceilings Only Firestop PN 22377 ROUND TOP TERMINATION RTL 8DM 12 96 Pitch 30 144 Pitch 7 13 11 77 144 96 12 30 SQUARE CHASE TOP TERMINATION ETL 8DM ACCESSORIES Continued OPTIONAL OUTSIDE AIR KIT FOR SIDE WALL INSTALLATION AK 6WE HEARTH EX...

Page 20: ... 2 24 8DM 24 Double Wall Pipe 1 0 18 8DM 18 Double Wall Pipe 0 2 FST A Adjustable Firestop Thimble 1 1 V6F 8DM Roof Flashing 1 1 SC1 1 Storm Collar 1 1 RTL 8DM Round Cap Termination 1 1 Use for Most Common Manufactured Mobile Home Installations FACE EXTENSION FE 36R Front face extension would add 6 to the width and 6 to the height of the fireplace face FLEX DUCT 6 X 25 3 PACK MP6 75 AIR INLET HOOD...

Reviews: