DC Inverter U-match Series Floor Ceiling Type Unit
34
3.3.2 Electrical Parameters
3.3.2.1 Wire Specifications and Fuse Capacity
Model
Power supply
Fuse
capacity
Circuit
breaker
capacity
Min. sectional
area of power
cord
V/Ph/Hz
A
A
mm
2
Indoor
unit
220-240V 1N~50Hz
208-230V 1N~60Hz
3.15
6
1.0
Model
Power supply
Circuit
breaker
capacity
Min. sectional
area of power
cord
V/Ph/Hz
A
mm
2
FGO-121EI/1JA-N3
220-240V 1N~50Hz
208-230V 1N~60Hz
16
1.5
FGO-181EI/1JA-N3
16
1.5
FGO-251EI/1JA-N3
20
2.5
FGO-301EI/1JA-N3
25
2.5
FGO-361EI/1JA-N3
32
4.0
32
4.0
40
6.0
380-415V 3N~50Hz/60Hz
16
1.5
FGO-421EI/3JA-N3
16
1.5
FGO-501EI/3JA-N3
16
1.5
FGO-601EI/3JA-N3
16
1.5
NOTICE:
①
Fuse is located on the main board.
②
Install a circuit breaker at every power terminal near the units (indoor and
outdoor units) with at least 3mm contact gap. The units must be able to
be plugged or unplugged.
③
Circuit breaker and power cord specifications listed in the above table are
determined based on the maximum power input of the units.
④
Specifications of power cords listed in the above table are applicable in a
working condition where ambient temperature is 40
℃
and multi-core
copper cable (e.g. YJV copper cable, with insulated PE and PVC sheath)
is protected by a conduit, and is resistant to 90
℃
in maximum (See IEC
60364-5-52).If working condition changes, please adjust the
specifications according to national standards.