DTX-MFM2/GFM2/SFM2 Fiber Modules
Users Manual
16
Table 2. Fiber Test Settings (cont.)
Setting Description
SETUP > Fiber >
Bi-Directional
When enabled in Smart Remote or Loopback mode, the tester prompts you to swap the test
connections halfway through the test. The tester can then make bi-directional measurements for
each fiber at each wavelength (850 nm/1300 nm, 850 nm/1310 nm, or 1310 nm/1550 nm).
SETUP > Fiber >
Number of Adapters
SETUP > Fiber >
Number of Splices
If the selected limit uses a calculated loss limit, enter the number of adapters and splices that will be
added to the fiber path after the reference is set. Figure 6 shows an example of how to determine
the
Number of Adapters
setting.
Only limits that use maximum values for loss per km, loss per connector, and loss per splice use a
calculated limit for overall loss. For example, limits for fiber backbones use a calculated loss limit.
SETUP > Fiber >
Connector Type
Select the type of connector used in the cabling. This setting affects only the diagrams shown for
reference connections. If the cabling's connector type is not listed, use
General
.
-continued-
Summary of Contents for DTX-GFM2
Page 15: ...Installing the Connector Adapter 9 amd99f eps Figure 4 Installing the Connector Adapter...
Page 31: ...Certifying Fiber Cabling 25 amd146f eps Figure 9 Smart Remote Mode Test Connections Method B...
Page 35: ...Certifying Fiber Cabling 29 amd147f eps Figure 11 Loopback Mode Reference Connections Method B...
Page 37: ...Certifying Fiber Cabling 31 amd148f eps Figure 12 Loopback Mode Test Connections Method B...
Page 45: ...Using the Visual Fault Locator 39 amd23f eps Figure 17 Using the Visual Fault Locator...
Page 60: ...DTX MFM2 GFM2 SFM2 Fiber Modules Users Manual B 4...