Essentials for Reliable Fiber Test Results
13
The gray mandrels included with the DTX-MFM2 are
compliant with TIA/EIA-568-B for 62.5
µ
m fiber with a
3 mm jacket. Mandrels for 50
µ
m fiber are available from
Fluke Networks. Refer to the appropriate standard for
mandrel requirements if you follow other standards.
Table 1 shows a partial list of mandrel requirements for
TIA and ISO standards.
Figure 5 shows how to wrap the fiber around a mandrel.
Place mandrels on the tester’s output fibers, as shown in
Figures 8 through 15.
In the reference and test connection diagrams shown on
the tester, mandrels are indicated by a loop in the fiber.
Table 1. TIA/EIA-568-B.1 and ISO/IEC TR 14763-3 Mandrel Requirements
Fiber
core size
Standard
Wraps Around
Mandrel
Mandrel Diameter for
250 µm Buffered Fiber
Mandrel Diameter for 3 mm
(0.12 in) Jacketed Cable
50 µm
TIA/EIA-568-B.1 7.1
5
25 mm (1.0 in)
22 mm (0.9 in)
ISO/IEC TR 14763-3 6.22
5
15 mm (0.6 in)
15 mm (0.6 in)
62.5 µm
TIA/EIA-568-B.1 7.1
5
20 mm (0.8 in)
17 mm (0.7 in)
ISO/IEC TR 14763-3 6.22
5
20 mm (0.8 in)
20 mm (0.8 in)
Summary of Contents for DTX-GFM2
Page 15: ...Installing the Connector Adapter 9 amd99f eps Figure 4 Installing the Connector Adapter...
Page 31: ...Certifying Fiber Cabling 25 amd146f eps Figure 9 Smart Remote Mode Test Connections Method B...
Page 35: ...Certifying Fiber Cabling 29 amd147f eps Figure 11 Loopback Mode Reference Connections Method B...
Page 37: ...Certifying Fiber Cabling 31 amd148f eps Figure 12 Loopback Mode Test Connections Method B...
Page 45: ...Using the Visual Fault Locator 39 amd23f eps Figure 17 Using the Visual Fault Locator...
Page 60: ...DTX MFM2 GFM2 SFM2 Fiber Modules Users Manual B 4...