Fluke 5320A-LOAD Instruction Sheet Download Page 2

5320A-LOAD 

High Voltage Load Adapter 

 

Turn on the power to the Load’s cooling fans by 

pressing the front-panel power switch so the “1” 

side of the switch is depressed (see Figure 2). A 

light on the power switch illuminates to indicate 

that power is connected to the fans. The power 

switch to the fans may be turned off when the 

Load is no longer being used. 

Using the Load for Leakage 
Current Testing 

The Load resistor should be selected based on 

the appropriate voltage amplitude used for the 

test or the value recommended in the hipot 

tester’s calibration procedure. 

W

 Caution 

To avoid damage, never exceed the 

maximum rated voltage, power, and 

current limit of the Load. 

Usage Limits for Safe Operation 

Safe operation of the load depends both on the 

amount of voltage and the length of time it is 

applied to the Load. For the 10 k

Ω

, 35 k

Ω

50 k

Ω

, 100 k

Ω

, and 250 k

Ω

 resistors, the higher 

voltage levels have limits to the time that they 

can be safely applied. The maximum voltages 

can be applied for up to 3 minutes. Due to self 

heating, exceeding the 3-minute limit for high 

voltages may cause both degradation of 

performance and a permanent shift in the 

resistor values. However, reduced voltage levels 

can be safely applied for increasing longer times. 

At specific levels, sustained voltages can be 

applied indefinitely. This is graphically shown in 

Figure 3 for the 10 k

Ω

, 35 k

Ω

, 50 k

Ω

, 100 k

Ω

and 250 k

Ω

 resistor sets. 

Safe Area

0

1000

2000

3000

4000

5000

6000

1

10

100

Time (min)

V

o

lt

ag

e (

V

)

250 k
100 k
35k/50k
10k

ehq101.eps 

Figure 3. Safe Area Chart 

As an example, the 100 k

Ω

 resistor can 

withstand 5500 V for 3 minutes while it can 

withstand 4000 V for 60 minutes or longer.  

Performance and Verification 
Test 

With normal operation, the resistance values of 

the Load should be verified no less frequently 

than once per year. Also, the Load should be 

verified if there was a possibility of the resistance 

values changing due to excessive heating or 

power dissipation. 
To verify the electrical performance of the Load, 

use one of two following test methods to insure 

the load resistors are within specification. 
The first test method uses voltage and current 

levels that insure the resistors dissipate a 

reasonable power when being verified. The 

alternative second test method uses a multimeter 

to measure the load resistance. Both methods 

check to see if it is within 10 % of the nominal 

value. The multimeter test uses minimal voltage 

and current levels, dissipating negligible power 

when measuring the resistance values of the 

Load. 
Either test method can be used, but the voltage 

method is generally recommended as it verifies 

the resistance value while the resistor is 

dissipating actual power – similar to the normal 

usage of the Load. The voltage method signal 

levels are based on capabilities of the 

recommended voltage calibrators. These levels 

use voltages up to 1 kV. It is possible and 

acceptable to test using other sources to test at 

higher voltages, but staying within the limits of 

the Load’s safe area of operation. 
Table 1 lists the load resistance nominal value 

for each test terminal. 
The voltage test method requires applying a test 

voltage across each resistance, between the 

respective input and COM terminals. The 

resulting current through the resistor is 

measured, and the value of the resistance is 

calculated. A calibrator is used as the precision 

voltage source. A multimeter is recommended to 

measure the current. Figure 4 shows the test 

equipment setup. Refer to Table 1 for the 

respective sourced voltage level settings and the 

nominal currents to be measured. 

Reviews: