Motor Loads
Adjustable Speed Drives
4
51
Adjustable Speed Drives
Checking Current on Phases
When a motor drive is tripping, first check for voltage imbalance (see
“
Checking Voltage Imbalance
”. Then check the current on all three phases
feeding the motor.
1
Open the main menu.
2
3
Make connections as shown below. Run the motor at full load.
If no current is present, you may assume an open fuse or an open circuit
in wiring. The drive will trip.
4
Repeat the measurement for phase 2 and phase 3.
VOLTS
/
AMPS
/
HERTZ