Power Quality Logger
Safety
Instructions
11
Power Network Configurations
You can set up the Logger to work with several power network configurations
(listed below). You make these settings using PQ Log software while
connected to the Logger using the interface cable. See the PQ Log Users
Manual for details.
•
Delta system
•
Delta 2 element system (2 voltage/current transformer)
•
Wye (Star) system
•
Single phase
•
Split single phase
Working with Logged Data
See the PQ Log manual for full details. Logged data can be evaluated using the
PQ Log software to provide the following:
•
Amount, date/time, and duration of quick and slow voltage variations
•
Half-cycle: 10 ms-extreme values for 50 Hz (8.3 ms at 60 Hz) MIN
and MAX for each measuring interval
•
Depth and duration of voltage dips
•
Correlation between peak current and voltage dips
•
95 %-flicker values according to EN50160
•
Number and duration of interruptions
•
Compliance of harmonic levels with defined limits
•
Mean and peak values of phase currents
•
Value of neutral conductor current
•
Current total harmonic distortion (THD) of phase and neutral
conductor currents
•
Profile of active, reactive, and apparent power versus time
•
Monitoring of power factor (PF) and information about effectiveness
of compensation systems
•
Graphical representations of logging data and statistics