background image

Doc no. 1.049.012.0.v

Datalogger

ProData 2

Operating instructions and technical data

Item no. 33.03.168

Janitza electronics GmbH
Vor dem Polstück 1
D-35633 Lahnau
Support tel. 0049 6441 9642-22
Fax 0049 6441 9642-30
E-mail: [email protected]
Internet: http://www.janitza.com

www

.janitza.com

fr

om har

dwar

e r

el. 4

Summary of Contents for ProData 2

Page 1: ...instructions and technical data Item no 33 03 168 Janitza electronics GmbH Vor dem Polst ck 1 D 35633 Lahnau Support tel 0049 6441 9642 22 Fax 0049 6441 9642 30 E mail info janitza com Internet http...

Page 2: ...ent input 25 Device address RS485 26 DIP switch S1 27 Service button S2 27 LED device status 27 Configuration and commissioning 28 Connecting the supply voltage 28 RS485 interface 28 Digital inputs 30...

Page 3: ...electronics GmbH takes no responsibility for errors or defects within this operating manual and takes no responsibility for keeping the contents of this operating manual up to date Comments on the ope...

Page 4: ...for the product and therefore invalidate the warranty for covering any potential damage that result This device is to be operated and maintained exclusively by specialised personnel Specialised perso...

Page 5: ...structions These operating instructions are part of the product Read the operating instructions before using the device Keep the operating instructions throughout the entire service life of the produc...

Page 6: ...e of force and only using suitable tools The devices should be visually checked for flawless mechanical condition It can be assumed that risk free operation is no longer possible if the device for exa...

Page 7: ...g instructions 1 51 00 116 CD with following content GridVis programming software GridVis functional description 1 10 01 855 Screw type terminal pluggable 2 pin supply voltage 3 10 01 873 Screw type t...

Page 8: ...e for recording and saving counter values and process data The data can be used to evaluate the energy consumption and operating hours or to monitor switching states and faults in buildings production...

Page 9: ...gs Assembly on mounting rails 35 mm Connection via pluggable screw terminals Clock and battery function Weekly timer Threshold value monitoring Modbus gateway functionality 1 Working temperature range...

Page 10: ...d CD Additional components that are not included in the scope of deliverables will be required for parametrisation via the RS485 interface C GridVis network analysis software The ProData 2 can be prog...

Page 11: ...11 ProData II...

Page 12: ...tion of a ProData 2 via a UMG 604 as a gateway Direct connection of a ProData 2 to a PC via Ethernet Connection of a ProData 2 to a PC via Ethernet twisted patch cable ProData 2 UMG 96RM twisted patch...

Page 13: ...address 3 1 twisted patch cable UMG 103 Modbus slave UMG 104 Modbus slave ProData 2 Gateway Connecting a ProData 2 as a Modbus slave device The ProData 2 is configured as a Modbus slave Communication...

Page 14: ...ia a 2 pin plug in terminal Before connecting the supply voltage make sure that the voltage and frequency correspond to the details on the ratings plate The supply voltage must be connected through a...

Page 15: ...a II N L Fig Connection example of the supply voltage to a ProData 2 via an external mains supply Circuit breaker Fuse DC AC N L Fig Connection example of the supply voltage to a ProData 2 Circuit bre...

Page 16: ...m 1 4 W at the beginning and at the end of a segment Termination within the device is possible via the S1 DIP switch of the ProData 2 Terminal strip in the cabinet Device with RS485 interface without...

Page 17: ...ng clamp in order to avoid damage due to cable movements Use suitable cable glands to feed the cables into the cabinet e g armoured conduit couplings Cable type The cable used must be suitable for an...

Page 18: ...used to connect the individual segments Devices for which the bus connection is switched on must be under current It is recommended that the master be placed at the end of a segment If the master is r...

Page 19: ...ta 2 to the Ethernet may only be carried out after discussion with the network administrator PC Switch Ethernet Connection LEDs of the Ethernet interface LED Function Yellow Illuminates when a connect...

Page 20: ...o be configured to monitor thetemperature Thiscanbeswitchedviathetemperature measurement input and using a comparator The digital outputs can be controlled via Modbus and the weekly timer The digital...

Page 21: ...connected to the digital outputs C When using the digital outputs as pulse outputs the auxiliary voltage DC must have a maximum residual ripple of 5 C Functions for the digital outputs can be adjuste...

Page 22: ...signal on this interface An input signal is recognised signal 1 if a voltage of at least 18 V is applied typically 4 mA at 24 V If the voltage is lower than 5 V DC no input signal exists signal 0 Wiri...

Page 23: ...3 4k Digital Input 3 2 4k Digital Input 2 1 4k Digital Input 1 3 9V 3 9V 3 9V 3 9V 3 9V ProData 2 Digital inputs 1 5 24 V DC S5 S4 External Auxiliary voltage S3 S2 S1 Fig Example of the connection of...

Page 24: ...ule optional article number 52 24 111 Enables simple and fast connection of S0 pulse transducers Module for a group of 5 inputs with integrated resistors 6 5 4k Digital Input 5 4 4k Digital Input 4 3...

Page 25: ...surement value is determined once per second The sensor type and the desired temperature offset can be set using the GridVis software or a Modbus Fig PT1000 line connection 25 26 27 Example 3 line con...

Page 26: ...2 4 6 7 5 3 8 9 01 2 4 6 7 5 3 8 9 X10 X1 The device address 0 0 is reserved and may not be assigned for operation with Modbus communication 01 2 4 6 7 5 3 8 9 01 2 4 6 7 5 3 8 9 The device address 99...

Page 27: ...ainted with it LED device status The status LEDs below the RS485 interface show different states of the device During the start process the red and the green LEDs illuminate at the same time Once the...

Page 28: ...istor Device address see the device address chapter Baud rate Stop bits The factory settings and the setting area for the baud rate are specified in the parameter list Device termination termination r...

Page 29: ...be selected consistently in the grid and set via address 002 Address 004 can be used to set the number of stop bits where 0 1 bit factory setting and 1 2 bits Data bits 8 and parity none are fixed de...

Page 30: ...e configured as functional inputs Operating these inputs as pulse counters is not possible in this configuration A tariff selection can be assigned to each digital input where only the highest activat...

Page 31: ...h 30 ms 30 ms 60 000 pulse h 50 ms 50 ms 36 000 pulse h 100 ms 100 ms 18 000 pulse h 500 ms 500 ms 3600 pulse h 1 s 1 s 1800 pulse h 10 s 10 s 180 pulse h The pulse counters can be configured with a...

Page 32: ...nd can be set in a region of 1 to 60 minutes After the period ends the value can be called via the Modbus For each digital input an external synchronisation can be triggered in this case a synchronisa...

Page 33: ...16 events for each digital input and specifies the time stamp and the current status Within the ring buffer the event field with the index 0 always describes the current status of the relevant digital...

Page 34: ...send queries to an NTP server active In active mode an NTP server with the IP address must be set A name resolution is not possible Current device time Time after minute pulse 15 05 51 15 06 00 15 05...

Page 35: ...s and the names of the power values can be adjusted and extended via the GridVis software Data memory The size of the ProData 2 s flash memory is 32 MB 24 MB is available for recordings and 5 MB is av...

Page 36: ...by setting or deleting bits 0 to 7 Only the highest value tariff is evaluated Tariff T1 T2 T3 T4 T5 T6 T7 T8 Bit 0 1 2 3 4 5 6 7 Input Address 1 1940 0 1 0 0 0 0 0 0 2 1941 0 0 0 0 0 0 0 0 15 1954 0 0...

Page 37: ...37 ProData II...

Page 38: ...is possible using a comparator The results of the comparator can be combined with the OR operator The combination result of the comparator group can be assigned to digital output 1 Sensor types PT100...

Page 39: ...y automatic integration of a ProData 2 into an existing network with a DHCP server without additional configuration When started the ProData 2 automatically obtains the IP address the network mask and...

Page 40: ...et this is converted to Modbus TCP again and sent via the IP connection The ProData 2 can only forward queries e g from the GridVis software to a Modbus slave device It CANNOT query Modbus slave devic...

Page 41: ...thernet but it cannot send any Ethernet queries to a Modbus slave device The ProData 2 contains a slave function in the RS485 bus and can be read from the master device UMG 604 RS485 mode Slave Addr 3...

Page 42: ...cordance with the legal provisions The permanently installed lithium battery must be disposed of separately Service Should questions arise which are not described in this manual please contact the man...

Page 43: ...be read via the Modbus address 4942 Ethernet using the GridVis software If the battery is exhausted and no time synchronisation NTP is set the software takes the last valid time stamp from the memory...

Page 44: ...e and observe correct polarity when changing it Information about polarity is provided on the battery insert cover Procedure 1 To change the battery the device must be switched off 2 Discharge any ele...

Page 45: ...CP or the RS485 interface Modbus RTU the device firmware can be updated via the GridVis software The new firmware is transferred by selecting a suitable update menu Tools Upgrade Devices menu and the...

Page 46: ...he device RS485 Incorrect device address Correct the device address Different bus speeds baud rate Correct the speed baud rate Incorrect protocol Correct the protocol Termination missing Close bus wit...

Page 47: ...47 ProData II...

Page 48: ...RH Ambient conditions during operation The ProData 2 is intended for weather protected stationary use Protection class II in acc with IEC 60536 VDE 0106 Part 1 Flammability rating of housing UL 94V 0...

Page 49: ...tputs semiconductor relays not short circuit proof Operating voltage 20 V 30 V DC SELV or PELV supply Switching voltage max 60 V DC Switching current max 50 mAeff DC Pulse output energy pulse max 20 H...

Page 50: ...le length Digital inputs and outputs temperature measurement input Up to 30 m Unshielded More than 30 m Shielded Digital inputs 15 digital inputs semiconductor relays not short circuit proof Operating...

Page 51: ...fine stranded 0 20 1 5 mm2 Terminal pins core end sheath 0 20 1 5 mm2 Tightening torque 0 20 0 25 Nm Stripping length 7 mm Clock Precision 5 ppm in temperature range 40 C to 70 C corresponding to app...

Page 52: ...52 ProData II Dimension diagrams All dimensions provided in mm ProData 2 front view ProData 2 side view with Ethernet connector inserted 107 5 90 46 32 2 46 35 5...

Page 53: ...53 ProData II...

Page 54: ...MV ILA V01 03 Burst IEC EN 61000 4 5 2007 EMV ILA V01 03 Surge IEC EN 61000 4 6 2009 EMV ILA V01 03 Conducted disturbances 0 15 80MHz IEC EN 61000 4 11 2005 EMV ILA V01 03 Voltage dips short interrupt...

Page 55: ...55 ProData II...

Page 56: ...Ethernet PC 13 14 B A B A 1 2 3 4 5 6 7 8 9 10 11 12 15 16 17 18 19 20 21 22 23 24 25 26 27 L N Digital inputs Temperature inputs Supply voltage 24 V DC DO1 24 V DC PT1000 Fuse Circuit breaker 24 V D...

Reviews: