29
ProData II
Baud rate
A common baud rate can be adjusted for the RS485
interface. The baud rate must be selected consistently
in the grid and set via address 002.
Address 004 can be used to set the number of stop bits
where 0=1 bit (factory setting) and 1=2 bits. Data bits (8)
and parity (none) are fixed default values.
Setting
Baud rate
0
9.6kbps
1
19.2kbps
2
38.4kbps
3
57.6kbps
4
115.2kbps (factory setting)