ProData II
Digital inputs
The ProData 2 features 15 digital inputs, which are
subdivided into three groups of 5 inputs:
• The status of each of the inputs is shown by
the corresponding LED. The corresponding
LED illuminates green if there is a signal on this
interface.
• The GridVis software can be used to assign a
name, unit and description to each digital input.
• The states of the digital inputs are each located on
their own Modbus address.
• The last 16 switches (events) are logged with a
time stamp for each digital input.
• Digital inputs 1-10 can be configured as functional
inputs. Operating these inputs as pulse counters is
not possible in this configuration.
• A tariff selection can be assigned to each digital
input where only the highest activated tariff runs.
Functional attributes
Specific functions can be assigned to digital inputs 1 - 10.
In this function mode, operating these inputs as pulse
counters is not possible.
Digital input 1 to 8:
Configuration as tariff converter
Digital input 9:
Synchronisation of the internal clock; choosing between
minute or hour synchronisation is possible. However,
synchronisation is also possible via a Modbus address.
Digital input 10:
Reset for the synchronisation values (see notes).
You also have the option of resetting the mean values via
a Modbus address.