Set the sensor supply
1. Make the F133-P safe. If applicable, mind the battery power.
2. Open the F133-P and carefully remove the cable-connectors and the protective cover.
3. Find and set the switches and select the V
out
as required.
4. Close the protective cover and install the cable connectors.
5. Close the F133-P .
Risk of electrocution - High voltage!
Make sure, all the leads to the terminals are disconnected from the F133-P and NEVER
connect the mains power supply to the unit when the protection cover has been removed!
Type PD
Power supply in:
8-24V AC / 10-30V DC
Switch location (typical)
Sensor
V
out
selection
Sensor supply out
A
1
2
3
4
NOTE: Use an AC
autotransformer (spartrafo)
with galvanic isolation.
int
-
off
off
Coil 1.2V DC; <1mA
Reed 3V DC; <1mA
ext
-
on
on
off
on
off
off
8.2V DC @8V
in
AC / 10V
in
DC
12V DC @10V
in
AC / 14V
in
DC
24V DC @18V
in
AC / 26V
in
DC
Type PF
Power supply in
:
15-24V AC / 20-30V DC
Switch location (typical)
Sensor
V
out
selection
Sensor supply out
A
1
2
3
4
int
-
off
off
Coil 1.2V DC; <1mA
Reed 3V DC; <1mA
ext
-
on
on
off
on
off
off
8.2V DC @8V
in
AC / 10V
in
DC
12V DC @10V
in
AC / 14V
in
DC
24V DC @18V
in
AC / 26V
in
DC
Type PM
Power supply in
: 115V - 230V AC
Switch location (typical)
Sensor
V
out
selection
Sensor supply out
A
1
2
3
4
int
-
off
off
Coil 1.2V DC; <1mA
Reed 3V DC; <1mA
ext
-
on
on
off
on
off
off
8.2V DC
12V DC
24V DC
Fig. 10: Sensor supply voltage - Switch setting
Terminal 03-04; valve control output R2:
This output is available to control the dispensing valve. Relay 2 is switched-on according to the
settings 51-56.
Terminal 05-06; pump control output R1:
This output is available to control the dispensing pump. Relay 1 is switched-on during the whole
batch process.