FW_F126PELTP_v1702_02_EN
Page 44
Setup variables
PDU
ADDRESS
REGISTER VARIABLE
TOTAL
NO.
REGISTERS
R/W
TYPE
VALUE / REMARKS
[d] 32
[h] 0x020
40033
unit
1
r/w uint16 0=none
1=L
2= m
3
3=kg
4= lb
5=GAL
6= USGAL
7=bbl
[d] 33
[h] 0x021
40034
decimals
1
r/w uint16 0…3
[d] 34
[h] 0x022
40035
K-Factor
2
r/w uint32 1...9999999
Representation: 0.000010…9999999
depending on variable 54: decimals K-Factor.
[d] 37
[h] 0x025
40038
decimals K-Factor
1
r/w uint16 0…6
PDU
ADDRESS
REGISTER VARIABLE
FLOW RATE A
NO.
REGISTERS
R/W
TYPE
VALUE / REMARKS
[d] 48
[h] 0x030
40049
unit
1
r/w uint16 0=mL
1=L
2= M
3
3=mg
4=g
5=kg
6=ton
7=GAL
8=bbl
9=lb
10=cf
11=rev
12=none
13=scf
14=NM
3
15=NL
16=P
[d] 49
[h] 0x031
40050
time unit
1
r/w uint16
0=/sec
1=/min
2=/hour
3=/day
[d] 50
[h] 0x032
40051
decimals
1
r/w uint16 0…3
[d] 51
[h] 0x033
40052
K-Factor
2
r/w uint32 1...9999999
Representation: 0.000010…9999999
depending on variable 54: decimals K-Factor.
[d] 54
[h] 0x036
40055
decimals K-Factor
1
r/w uint16 0…6
[d] 62
[h] 0x03E
40063
filter
1
r/w uint16 1...99
[d] 71
[h] 0x047
40072
period
1
r/w uint16 1...999
Representation: 0.1 – 99.9 sec
PDU
ADDRESS
REGISTER VARIABLE
DISPLAY
NO.
REGISTERS
R/W
TYPE
VALUE / REMARKS
[d] 64
[h] 0x040
40065
function
1
r/w uint16 0: total
1: flow rate
[d] 67
[h] 0x043
40068
backlight brightness
1
r/w uint16 0: off
1: 20%
2: 40%
3: 60%
4: 80%
5: 100%
PDU
ADDRESS
REGISTER VARIABLE
POWER MANAGEMENT
NO.
REGISTERS
R/W
TYPE
VALUE / REMARKS
[d] 80
[h] 0x050
40081
LCD update time
1
r/w uint16 0=fast
1=1sec
2=3sec
3=15sec
4=30sec
5=off
[d] 81
[h] 0x051
40082
power mode
1
r/w uint16 0=operational
1=shelf
PDU
ADDRESS
REGISTER VARIABLE
FLOWMETER
NO.
REGISTERS
R/W
TYPE
VALUE / REMARKS
[d] 96
[h] 0x060
40097
flowmeter signal
1
r/w uint16 0: npn
1: npn lp
2: reed
3: reed lp
4: pnp
5: pnp lp
6: namur
7: coil-hi
8: coil-lo
9: act. 8.2V
10: act. 12V
11: act. 24V