FW_F126PELTP_v1702_02_EN
Page 26
Type OA:
An active 24V DC pulse signal output is available with this option.
Max. driving capacity 50mA@24V per output. (Requires power supply type PD/PF/PM).
Fig. 9: Terminal connections - Active output (typical)
Type OR:
A mechanical relay output is available with this option. Max. switch power 240V 0,5A per output.
(Requires power supply type PF/PM). Be sure that the output frequency does not exceed 5Hz, else
the relay life time will be reduced significantly.
Fig. 10: Terminal connections - Mechanical relay output (typical)
Type OT:
A passive transistor output is available with this option. Max. driving capacity 300mA@50V DC.
Fig. 11: Terminal connections - Pulse output (typical)
Terminal 07-08; basic POWER SUPPLY - type AP
– output loop powered
Connect an external power supply of 8-30VDC to these terminals or a 4-20mA loop.
Do connect the
“-“ to terminal 7 and the “+” to terminal 8. When power is applied to these terminals,
the (optional) internal battery will be disabled / enabled automatically to extend the battery life time.
Terminal 07-08 analog output (setup 7) :
An analog output signal proportional to the flow rate is available as standard.