FW_F126PELTP_v1702_02_EN
Page 41
Analog output
Function
transmitting compensated flow rate.
Accuracy
10 bit. Error < 0.05% - update 10 times a second.
Software function to calibrate the 4.00mA and 20.00mA levels precisely within set-up.
Load
max. 1 kOhm
Type AA
Active 4-20mA output (requires type OA + PD, PF or PM).
Type AB
Active 0-20mA output (requires type OA + PD, PF or PM).
Type AF
Passive floating 4-20mA output for Intrinsically safe applications (requires type PC or PD).
Type AI
Passive galvanic isolated output (requires type PB, PD, PF, PL or PM).
Type AP
Passive 4-20mA output - output loop powered.
Type AU
Active 0-10V output (requires type OA + PD, PF or PM).
Switch output(s)
Function
One pulse output - transmitting accumulated total.
Pulse output
Max. frequency 500Hz. Pulse length user definable between 0.001 up to 9.999 seconds.
Type OA
Active 24V DC transistor output; max. 50mA per output (requires type AA + PD, PF or PM).
Type OR
Isolated mechanic relay output; max. switch power 230V AC - 0,5A (requires type PF or PM).
Type OT
Passive transistor output - not isolated. Load max. 50V DC - 300mA.
Communication option
Protocol
bus-rtu; bus-asc
Speed
1200; 2400; 4800; 9600
Addressing
1 - 247
Type CB
RS232
Type CH
RS485 2-wire
Type CI
RS485 4-wire
Type CT
TTL Intrinsically safe communication.
Type CX
no communication.
Operator functions
Shown functions
compensated total and/or compensated flow rate.
compensated total and compensated accumulated total.
line temperature.
compensated total can be reset to zero by pressing the CLEAR-key twice.
Total
Digits
7 digits.
Units
L; m
3
; kg; lb; GAL; USGAL; bbl; no unit
Decimals
0000000; 111111.1; 22222.22; 3333.333
Note
total can be reset to zero.
Accumulated total
Digits
11 digits.
Units / decimals
according to selection for total.
Flow rate
Digits
7 digits.
Units
mL; L; m
3
; mg; g; kg; ton; gal; bbl; lb; cf; rev; - - - - (no unit); scf; nm
3
; nL; p
Decimals
0000000; 111111.1; 22222.22; 3333.333
Time units
/sec; /min; /hour; /day
Line temperature
Digits
7 digits.
Units
°C; °F; K
Decimals
1
Normal temperature
default: 273.15 K - any temperature can be set.
Flow equations
Type EL
Equations Liquid - flow computer for corrected liquid volume
Formula
Qnormal = Q * (1 +
(Tnormal - T)) where
= thermal expansion coefficient.
Outputs
Operational