For example when two decimals are selected for total and total has a value of 123456,78 the display
will show 23456,78 while communication will read a “total” of 12345678 (note that the decimals
should be adapted according the setting in “total decimals” which is in this case 2).
* Clearing total:
It is possible to clear the total counter by means of writing a value of 0 to all the 3
registers of total/flow rate in a single write action. Writing any other value will result in the reply of an
error message because the registers of total/flow rate are during operation read-only.
Setup variables
PDU
ADDRESS
REGISTER VARIABLE
TOTAL A
NO.
REGISTERS
R/W
TYPE
VALUE / REMARKS
[d] 32
[h] 0x020
40033
unit
1
r/w uint16 0=none
1=L
2= m
3
3=kg
4= lb
5=GAL
6= USGAL
7=bbl
[d] 33
[h] 0x021
40034
decimals
1
r/w uint16 0…3
[d] 34
[h] 0x022
40035
K-factor
2
r/w uint32 1...9999999
Representation: 0.000010…9999999 depending on
variable 37: decimals K-factor.
[d] 37
[h] 0x025
40038
decimals K-factor
1
r/w uint16 0 … 6
PDU
ADDRESS
REGISTER VARIABLE
FLOW RATE A
NO.
REGISTERS
R/W
TYPE
VALUE / REMARKS
[d] 48
[h] 0x030
40049
Unit
1
r/w uint16 0=mL
1=L
2= m
3
3=mg
4=g
5=kg
6=ton
7=GAL
8=bbl
9=lb
10=cf
11=rev
12=none
13=scf
14=NM
3
15=NL
16=P
[d] 49
[h] 0x031
40050
time
1
r/w uint16 0=/sec
1=/min
2=/hour
3=/day
[d] 50
[h] 0x032
40051
decimals
1
r/w uint16 0…3
[d] 51
[h] 0x033
40052
K-factor
2
r/w uint32 1...9999999; Representation: 0.000010…9999999
depending on variable 54: decimals K-factor.
[d] 54
[h] 0x036
40055
decimals K-factor
1
r/w uint16 0…6
[d] 55
[h] 0x037
40056
calculate
1
r/w uint32 1…255
[d] 56
[h] 0x038
40057
cut-off
2
r/w uint16 1...9999
Representation: 0.1 - 999.9 sec
When in the flowmeter menu the parameter K-Factor is set to single, the K-Factor for Total B is the
same as the K-Factor as set for Total A. Note that Writing to the register is prohibited for 'single'.
PDU
ADDRESS
REGISTER VARIABLE
TOTAL B
NO.
REGISTERS
R/W
TYPE
VALUE / REMARKS
[d] 40
[h] 0x028
40041
K-factor
2
r/w uint32 1...9999999
Representation: 0.000010…9999999 depending on
variable 43: decimals K-factor.
[d] 43
[h] 0x02b
40044
decimals K-factor
1
r/w uint16 0 … 6
When in the flowmeter menu the parameter K-Factor is set to single, the K-Factor for Flow rate B is
the same as the K-Factor as set for Total A. Note that Writing to the register is prohibited for 'single'.
PDU
ADDRESS
REGISTER VARIABLE
FLOW RATE B
NO.
REGISTERS
R/W
TYPE
VALUE / REMARKS
[d] 227
[h] 0x0E3
40228
K-factor
2
r/w uint32 1...9999999
Representation: 0.000010…9999999 depending on
variable 43: decimals K-factor.
[d] 230
[h] 0x0E6
40231
decimals K-factor
1
r/w uint16 0 … 6
PDU
ADDRESS
REGISTER VARIABLE
DISPLAY
NO.
REGISTERS
R/W
TYPE
VALUE / REMARKS
[d] 64
[h] 0x040
40065
display function
1
r/w uint16 0=total
1=flow rate
2=all
[d] 65
[h] 0x041
40066
Show A-B
1
r/w uint16
0=disable
1=enable