FW_F115P_v1702_02_EN
Page 41
Data protection
Type
EEPROM backup of all settings. Backup of running totals every minute.
Data retention at least 10 years.
Password
Configuration settings can be password protected.
Hazardous area
Intrinsically safe
Type XI
ATEX approval :
II 1 G Ex ia IIB/IIC T4 Ga
II 1 D Ex ia IIIC T100°C Da
IECEx approval :
Ex ia IIB/IIC T4 Ga
Ex ia IIIC T100°C Da
Explosion proof
Type XD/XF
ATEX approval ref: II 2 EEx d IIB T5. Weight appr. 15kg.
Dimensions of enclosure: 350 x 250 x 200mm (13.7” x 9.9” x 7.9”) LxHxD.
Directives/Standards
EMC
EN 61326-1; FCC 47 CFR part 15
LVD
EN/IEC 61010-1
ATEX / IECEx
EN/IEC 60079-0; EN/IEC 60079-11
RoHS
EN 50581
IP & NEMA
EN 60529; NEMA 250
Flowmeter
Type P
npn; npn-lp; reed; reed-lp; pnp; pnp-lp; namur; coil-hi; coil-lo; 8-1 DC; 12 DC; 24 DC
Frequency Minimum 0 Hz - maximum 7 kHz for total and flow rate.
Maximum frequency depends on signal type and internal low-pass filter.
E.g. Reed switch with low-pass filter: max. frequency 120 Hz.
K-Factor 0.000010 - 9999999 with variable decimal position.
Low-pass filter
npn-lp; reed-lp; pnp-lp
Analog output
Function
transmitting flow rate
Accuracy
10 bit. Error < 0.05% - update 10 times a second.
Software function to calibrate the 4.00mA and 20.00mA levels precisely within set-up.
Load
max. 1 kOhm
Type AA
Active 4-20mA output (requires type OA + PD, PF or PM).
Type AB
Active 0-20mA output (requires type OA + PD, PF or PM).
Type AF
Passive floating 4-20mA output for Intrinsically safe applications (requires type PC or PD).
Type AI
Passive galvanic isolated output (requires type PB, PD, PF, PL or PM).
Type AP
Passive 4-20mA output - output loop powered
Type AU
Active 0-10V output (requires type OA + PD, PF or PM).
Transistor output(s)
Function
two pulse outputs -
transmitting positive (and negative) flow rate.
Pulse output
Max. frequency 500Hz. Pulse length user definable between 0.001 up to 9.999 seconds.
Type OA
Two active 24V DC transistor outputs; max. 50mA per output (requires type AA + PD, PF or
PM).
Type OR
Two mechanic relay outputs; max. switch power 230V AC - 0,5A (requires type PD or PM).
Type OT
Two passive transistor outputs - not isolated. Load max. 50V DC - 300mA.
Communication option
Protocol
bus-rtu; bus-asc
Speed
1200; 2400; 4800; 9600
Addressing
1 - 247
Type CB
RS232
Type CH
RS485 2-wire
Type CI
RS485 4-wire
Type CT
TTL Intrinsically Safe communication.
Type CX
no communication.