Active signal
Active signal selection may well be desired in the case of option PD being supplied for sensor
supply.
Fig. 18: Terminal connections - Active signal input.
Reed-switch
The F011-P is suitable for use with flowmeters which have a reed-switch. To avoid pulse bounce
from the reed-switch, it is advised to select REED LP - low-pass filter (read chapter 3.3).
Fig. 19: Terminal connections - Reed-switch signal input.
NAMUR-signal
The F011-P is suitable for flowmeters with an NAMUR signal. The standard F011-P is not able to
power the NAMUR sensor, as an external power supply for the sensor is required. However, a 8.2V
sensor supply voltage (terminal 6) can be provided with type PD.
Fig. 20: Terminal connections - NAMUR signal input.
4.6.2
TERMINAL 4-5: POWER SUPPLY - TYPE PX (DEFAULT) AND PD (OPTION)
To power the F011-P an internal battery can be used (type PB) and / or an external DC power
supply of 8-30V DC (type PX) or 16-30V DC (type PD).
Connect the "
-
" to terminal 4 and the "
+
" to terminal 5.
When power is applied to these terminals, the optional internal battery will be disabled / enabled
automatically to extend the battery life time.