Page 8
FW-F011-P-M_v0404_01_EN.docx
•
Clear total
The value for total can be re-initialized. To do so, press CLEAR twice. After pressing CLEAR
once, the flashing text "PUSH CLEAR" is displayed. To avoid re-initialization at this stage,
press another key than CLEAR or wait for 20 seconds.
Re-initialization of total DOES NOT influence the accumulated total.
The accumulated total cannot be re-initialized. The value will count up to 99,999,999,999. The
unit and number of decimals are displayed according to the configuration settings for total.
•
Low-battery alarm
When the battery voltage drops, it must be replaced. At first "low
battery”" will flash, but as
soon as it is displayed continuously, the battery MUST be replaced shortly after!
The remaining lifetime after the first moment of indication is generally several days up to some
weeks. See paragraph 6.3 for further information on battery replacement.
Fig. 4: Example of low-battery alarm.
•
Range error
As soon as the input value is 5% outside the calibrated measurement range,
“ALARM”
will be displayed, together with the calibrated value.
After pressing the SELECT key, the reason of the alarm will be displayed: “LO RANGE” or
“HI RANGE”.
•
Alarm 01-03
When "alarm" is displayed, please consult Appendix B: problem solving.