
Page 15
FW-F010-P-M_v0404_01_EN.docx
3.3.5
EXPLANATION OF SETUP-MENU 4 - FLOWMETER
The F010-P is able to handle several types of input signal. The type of flowmeter pickup / signal is
selected with SETUP 4.1. Read also paragraph 4.6.1 Terminals 1-3: Flowmeter input.
SETUP
FUNCTIONS
AND
VARIABLES
4
FLOWMETER
4.1
SIGNAL
TYPE OF SIGNAL
EXPLANATION
RESISTANCE
FREQ. / mV
REMARK
NPN
NPN input
100
kΩ pull
-up
6 kHz.
(open collector)
NPN - LP
NPN input with
low pass filter
100
kΩ pull
-up
1.2 kHz.
(open collector)
less sensitive
REED
Reed-switch input
1
mΩ
pull-up
600 Hz.
REED - LP
Reed-switch input
with low pass
filter
1
mΩ pull
-up
120 Hz.
Less sensitive
PNP
PNP input
47
kΩ pull
-down
6 kHz.
PNP - LP
PNP input with
low pass filter
100
kΩ pull
-down
1.2 kHz.
Less sensitive
NAMUR
Namur input
820
Ω pull
-down
4 kHz.
External power
required
COIL HI
High sensitive coil
input
-
20 mV p.t.p.
Sensitive for
disturbance!
COIL LO
Low sensitive coil
input
-
90 mV p.t.p.
Normal sensitivity
ACTIVE
Active pulse input
detection level
1.2V DC
47
kΩ
10 kHz.
External power
required
3.3.6
EXPLANATION OF SETUP-MENU 5 - OTHERS
SETUP
FUNCTIONS
AND
VARIABLES
5
OTHERS
5.1
TYPE / MODEL
For support and maintenance it is important to have information about
the characteristics of the F010-P.
Your supplier will ask for this information in the case of a serious
breakdown or to assess the suitability of your model for upgrade
considerations.
5.2
SOFTWARE VERSION
5.3
SERIAL NO.
5.4
PASS CODE
All SETUP-values can be pass code protected.
This protection is disabled with value 0000 (zero).
Up to and including 4 digits can be programmed, for example 1234.
5.5
TAGNUMBER
For identification of the F010-P and communication purposes, a
unique tag number of maximum 7 digits can be entered.