background image

26

 

 

 
 
 
 
 

  5. MAINTENANCE AND INSPECTION 

 

 

Repairs to sealed components

 

1)  During repairs  to sealed  components,  all electrical supplies  shall be disconnected  from 
the equipment being worked upon prior to any removal of sealed covers, etc. If it

 

isabsolutely  necessary  to  have  an  electrical  supply  to  equipment  during  servicing,  then  a 
permanently operating form of leak detection shall be located at the most critical point to warn of a 
potentially hazardous situation.

 

2)  Particular  attention  shall be paid to the following  to ensure that  by working  on electrical 
components, the casing is not altered in such a way that the level of protection is  affected.

 

This shall include damage to cables, excessive number of connections, terminals not made to 
original specification, damage to seals, incorrect fitting of glands, etc.

 

Ensure that apparatus is mounted securely.

 

Ensure that seals or sealing materials have not degraded such that they no longer serve

 

the purpose of preventing the ingress of flammable atmospheres. Replacement parts shall be in 
accordance with the manufacturer's specifications.

 

NOTE: The use of silicon sealant may inhibit the effectiveness of some types of leak detection 
equipment. Intrinsically safe components do not have to be isolated prior to

 

 

Repair to intrinsically safe components

 

Do not apply any permanent 

inductive or capacitance loads to the circuit without ensuring 

that 

this will not exceed the permissible voltage and current permitted for the equipment in use.

 

Intrinsically safe components are the only types that can be worked on while live in the 
presence of a flammable atmosphere. The test apparatus shall be at the correct rating.

 

Replace components only with parts specified by the manufacturer. Other parts may result in the 
ignition of refrigerant in the atmosphere from a leak.

 

 

Cabling

 

Check  that  cabling  will  not  be  subject  to  wear,  corrosion,  excessive  pressure,  vibration,  sharp 
edges  or  any  other  adverse  environmental  effects.  The  check  shall  also  take  into  account  the 
effects of aging or continual vibration from sources such as compressors or fans.

 

 

Detection of flammable refrigerants

 

Under no circumstances shall potential sources of ignition be used in the searching for or 
detection of refrigerant leaks. A halide torch (or any other detector using a naked flame)

 

shall not be used.

 

 

Leak detection methods

 

The following leak detection methods are 

deemed acceptable for systems containing 

flammable refrigerants.

 

Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity 
may not be adequate, or may need re-calibration. (Detection equipment shall be calibrated 
in a refrigerant-free area.) Ensure that the detector is not a potential source of ignition and 
is suitable for the refrigerant used. Leak detection equipment shall be set at a percentage 
of the LFL of the refrigerant and shall be calibrated to the refrigerant employed and the

 

appropriate percentage of gas (25 % maximum) is confirmed.

 

Leak detection fluids are suitable for use with most refrigerants but the use of detergents 
containing chlorine shall be avoided as the chlorine may react with the refrigerant and

 

corrode the copper pipe-work.

 

If a leak is suspected, all naked flames shall be removed/ extinguished.

 

If a leakage of refrigerant is found which requires brazing, all of 

the refrigerant shall be

 

recovered from the system, or isolated (by means of shut off valves) in a part of the system remote 
from the leak. Oxygen free 

nitrogen (OFN) shall then be purged through the system 

both before 

and during the brazing process.

 

Summary of Contents for 78568

Page 1: ...intended for use by young children 3 08 2017 ECO RANGE INVERTER HEAT PUMPS Installation Instruction manual INSTALLATION AND OPERATING INSTRUCTIONS I INSTALLATION AND OPERATING INSTRUCTIONS Eco Range...

Page 2: ......

Page 3: ...ool Heat Pumps Electrical Wiring 10 3 6 Initial Start up of the Unit 10 4 Use and Operation Instruction 11 4 1 Interface display 11 4 2 Key and icon function instruction 11 4 3 Startup shutdown 13 4 4...

Page 4: ...t type unit The indoor unit can be Discretely hidden or semi hidden to suit a luxury house Our heat pump has following characteristics 1 Durable The heat exchanger is made of PVC Titanium tube which c...

Page 5: ...liance shall be stored in a room without continuously operating ignition sources for example open flames an operating gas appliance or an operating electric heater Do not pierce or burn Appliance shal...

Page 6: ...ful life must be handled separately from domestic waste must be taken to a recycling centre for electric and electronic devices or handed back to the dealer when purchasing an equivalent appliance 6 D...

Page 7: ...g Power Input kW 0 2 1 25 0 27 1 72 COP 4 5 3 2 4 5 3 2 Power Supply 220 240V 50Hz 220 240V 50Hz Compressor Quantity 1 1 Compressor rotary rotary Fan Number 1 1 Noise dB A 38 50 39 51 Water Connection...

Page 8: ...3 2 18 COP 4 8 3 3 Power Supply 220 240V 50Hz Compressor Quantity 1 Compressor rotary Fan Number 1 Noise dB A 42 53 Water Connection mm 48 3 Water Flow Volume m3 h 3 5 Water Pressure Drop max kPa 4 Un...

Page 9: ...6 545 2 SPECIFICATION 2 2 The dimensions for Swimming Pool Heat Pump Unit UNIT 78566 78567 78568 unit mm 1000 Water outlet 48 3 Water inlet 48 3 418 350 97 605...

Page 10: ...pipe have been filled with water 3 Close the valve and start the unit ATTN It is necessary that the water in pipe is higher than the pool surface The schematic diagram is forreference only Please che...

Page 11: ...inlet These locations deny the unit of a continuous source of fresh air which reduces it efficiency and may prevent adequate heat delivery 3 3 How Close To Your Pool Normally the pool heat pump is ins...

Page 12: ...to provide easier access should servicing be required To pool PVC COUPLER RECOMMENDED Provided From pump CONDENSATION DRAIN BARB FTG Condensation Since the Heat pump cools down the air about 4 5 wate...

Page 13: ...nitial startup of the Unit NOTE In order for the unit to heat the pool or spa the filter pump must be running to circulate water through the heat exchanger Start up Procedure After installation is com...

Page 14: ...effective and used to enter and exit the mute mode with one click Mode key It is used to switch the unit mode temperature setting and parameter setting On off key It is used to carry out startup shutd...

Page 15: ...sh Or else it is off Timing symbol It will display after the user sets the timing and multiple timing intervals can be set Water outlet symbol When the axillary display area displays the water outlet...

Page 16: ...rface When it displays with half screen off or full screen off click any key for returning to ON OFF main interface When the unit is started under the control of wire controller if using the emergency...

Page 17: ...g During the defrosting mode switch is available And when switching the mode the unit won t work under a new mode until defrosting is completed 4 5 Temperature setting Notes Under the temperature sett...

Page 18: ...lay among timer ON1 OFF1 ON2 and OFF2 4 Use andOperation Instruction 4 6 Clock setting 6 1 System time setting Notes Under the clock setting interface if there is no operation for 20 s the system will...

Page 19: ...lay among timer ON1 OFF1 ON2 and OFF2 4 Use andOperation Instruction 4 6 Clock setting 6 1 System time setting Notes Under the clock setting interface if there is no operation for 20 s the system will...

Page 20: ...2 1 cancel the Timer ON OFF as below Take ON1 for example 2 To cancel the first stage timing switch cancel both ON and To cancel the second stage timing switch cancel both ON2 and To cancel the two st...

Page 21: ...silent Keep long press of fo r 2 s Short press or 4 Use andOperation Instruction 4 7 Silent setting 7 1 One click silent function Notes 1 If one click silent and timming silentaare stared at the same...

Page 22: ...em Check the pipe water flow and water pump Anti freezing Prot E07 Water flow is not enough Checkth ep ipew aterfl owa ndw hether waters ystemi sja mmedo rn ot Winter Primary Anti freezing Prot E19 Th...

Page 23: ...nput voltagemeasurement Inv Sampling Volt F11 The input voltage sampling fault Checkand adjustthe current measurement Comm Err DSP PFC F12 DSP and PFC connect fault Checkthe communicationconnection In...

Page 24: ...Default 27 27 27 Remarks Adjustable Adjustable Adjustable 4 Use and Operation Instruction 10 2 Parameter list Meaning 21...

Page 25: ...4 Use and Operation Instruction 4 11 Main board 22...

Page 26: ...23 4 Use and Operation Instruction Main board of the input and output interface instructions below Number Sign Meaning 22 23 Color line controller communication...

Page 27: ...ge Work procedure Work shall be undertaken under a controlled procedure so as to minimise the risk of a flammable gas or vapour being present while the work is being performed Work procedure Work shal...

Page 28: ...times the manufacturer s maintenance and service guidelines shall be followed If in doubt consult the manufacturer s technical department for assistance The following checks shall be applied to instal...

Page 29: ...only with parts specified by the manufacturer Other parts may result in the ignition of refrigerant in the atmosphere from a leak Cabling Check that cabling will not be subject to wear corrosion exces...

Page 30: ...igerants are removed safely When transferring refrigerant into cylinders ensure that only appropriate refrigerant recovery cylinders are employed Ensure that the correct number of cylinders for holdin...

Page 31: ...e in accordance with manufacturer s instructions h Do not overfill cylinders No more than 80 volume liquid charge i Do not exceed the maximum working pressure of the cylinder even temporarily j When t...

Page 32: ...0A 30mA less than 0 1 sec 186 224A 2 95mm2 95mm2 280A 30mA less than 0 1 sec 2 Three phase unit Nameplate maximum current Phase line Earth line MCB Creepage protector Signal line No more than 10A 3 1...

Page 33: ...0 3 0 5 0 8 1 1 3 1 5 1 8 2 2 3 Temperature R410A 51 3 20 9 4 11 19 24 31 35 39 Temperature R32 52 5 20 9 3 5 10 18 23 29 5 33 3 38 7 Pressure MPa 2 5 2 8 3 3 3 3 5 3 8 4 4 5 5 5 5 Temperature R410A 4...

Page 34: ...Note...

Page 35: ...Note...

Page 36: ......

Reviews: