CHAPTER 3 - OPERATION
FLUID COMPONENTS INTL
Table 3-2. Input Power
Table 3-4. Application
FLOW/LEVEL
TEMP.
ALARM NO. 1
J20
J21
ALARM NO. 2
J18
J19
J UMPER
POWER SELECT
100-130 VAC
200-260VAC
18-26VAC
21-30VDC
J1
IN
OUT
OUT
OUT
J2
OUT
IN
OUT
OUT
J3
IN
OUT
OUT
OUT
J4
OUT
OUT
IN
OUT
J5
IN
IN
OUT
OUT
J6
OUT
IN
IN
IN
J7
OUT
OUT
OUT
IN
J8
OUT
OUT
OUT
IN
J9
OUT
OUT
IN
OUT
Table 3-5. Relay Energization
Table 3-3A. Selectable Heater Wattage Control
JUMPER
J32
J12
J13*
J14*
J33
FLT93-F ELEMENT
WATTAGE
(560 OHM HTR)
0.57
WATTS
0.52
WATTS
0.49
WATTS
0.20
WATTS
OFF
FLT93-S ELEMENT
WATTAGE
(110 OHM HTR)
3
WATTS
1.75
WATTS
0.75
WATTS
0.27
WATTS
OFF
Table 3-6. Relay Contact Configuration
J UMPER
ALARM NO. 1
J27
RELAY DE-ENERGIZED WITH LOW FLOW, LOW
LEVEL (DRY) OR HIGH TEMPERATURE.
J26
RELAY DE-ENERGIZED WITH HIGH FLOW, HIGH
LEVEL (WET) OR LOW TEMPERATURE
ALARM NO. 2
J25
RELAY DE-ENERGIZED WITH LOW FLOW, LOW
LEVEL (DRY) OR HIGH TEMPERATURE.
J24
RELAY DE-ENERGIZED WITH HIGH FLOW, HIGH
LEVEL (WET) OR LOW TEMPERATURE.
*J13 is standard for FLT93-S and
J14 is standard for FLT93-F.
J23
DUAL SPDT (ONE RELAY PER ALARM)
J22
SINGLE DPDT (DISABLES ALARM NO. 2)
Table 3-3B. Fixed Heater Wattage Control
JUMPER
J13
J14
J33
FLT93-F ELEMENT
WATTAGE
(560 OHM HTR)
N.A.
0.20
WATTS
OFF
FLT93-S ELEMENT
WATTAGE
(110 OHM HTR)
0.75
WATTS
N.A.
OFF
Numerical Alarm Set Point Adjustment
The control circuit has two mutually exclusive alarms; they are identified as Alarm No. 1 and Alarm No. 2. Each has
an alarm set point adjustment potentiometer and LED indicator. Both alarms can be setup for one of three
applications; flow, level/interface, or temperature. The following application specific adjustment procedures are
generic and can be used for setting either or both alarms. Use Figure 3-2 to help locate the important setup
components (potentiometers, LEDs, etc.).