![FLTR Tekleen GB6-B User Manual Download Page 10](http://html1.mh-extra.com/html/fltr/tekleen-gb6-b/tekleen-gb6-b_user-manual_2308686010.webp)
5.2 VALVES
The GB6-B is only compatible with two-wire latching solenoids. The negative (typically
black) wire on the solenoid(s) should be connected to terminal C. The positive (typically
red
) wire on the solenoid(s) should be connected to the corresponding terminal(s) (1, 1
and M, or 1 and 2).
SECTION VI: GENERAL NOTES
6.1 Installation
The controller may be installed any desirable distance from the filter(s) granted the
DP Gauge is installed near the filter. The tubing running from the DP Gauge and the
Filter header should not exceed 3 ft.
The inside of the controller should be kept free of moisture and loose debris to
prevent shorting out the terminals.
6.2 Battery Power Supply
Under normal operating conditions the GB6-B's batteries will last for approximately
10,000 actuations of a latching solenoid. Ambient temperature, environmental factors,
and battery quality can affect this approximation. All batteries should be replaced at the
same time and should be identical to each other. Do NOT use different battery types
together. 'Energizer L91-FRG' Lithium batteries are recommended but alkaline batteries
may be used for reduced cycle count applications. It is recommend that batteries be
replaced annually to prevent unexpected usage disruptions.
Note:
Changing the batteries or pressing the reset button will clear backwash cycle
counter and user settings.
For more information:
WEB: FLTR.com.au PHONE: (+61) 1300 62 4020 EMAIL: [email protected] SKYPE: Purple.Engineering