Logix 3000MD Series Digital Positioner FCD LGENTB0059-01 – 10/09
13
How to order
Selection
Code
Example
3
3
Protocol
HART
2
4
Foundation Fieldbus
4
Diagnostics
Standard (No Sensors)
0
1
Advanced (With Sensors)
1
Pro Diagnostics (with sensors and full ValveSight dianostics)
2
Material
Aluminum, White Paint (Valtek)
0
0
Stainless Steel, No Paint (Valtek)
1
Aluminum, Black Paint (Automax)
2
Aluminum, Food-Grade White Paint (Automax)
3
Aluminum, Black Paint (Accord)
4
Aluminum, Food-Grade White Paint (Accord)
5
Design Version
MD
Certifications
Nonincendive Ex nL nA IIC, ATEX II 3 G, T4amb -40
0
C to +85
0
C, T5 Tamb -40
0
C to
+55
0
C; Intrinsically Safe Ex ia IIC, T4 Tamb -40
0
C to +85
0
C, T5 Tamb -40
0
C to +55
0
C; Ex
ia D 20, T95
0
C -40
0
C to +80
0
C (CENELEC)
04
(3400MD)
14
INMETRO BR-EX ia IIC T4/T5; BR-Ex d IIB+H
2
T5 (South America)
06
Explosionproof Ex d IIB + H
2
, Ex tD A21 T95
0
C, ATEX II 2 G (CENELEC)
(GOST GGTN Ex d IIB+H
2
)
07
(3400MD)
Explosionproof Class I, Div 1, Groups B, C, D Intrinsically Safe Class I,
Div 1, Groups A through G (FM, CSA) FM Nonincendive. CSA Class I,
Div 2, Class I, Zone 1, Group IIB + H
2
and Exia Class 1, Zone 0,
Group IIC (CSA Only)
10
General Purpose
14
Intrinsically Safe Ex ia IIC, T4 Tamb -40
0
C to +85
0
C, T5 Tamb -40
0
C to +55
0
C; Ex ia D 20,
T95
0
C -40
0
C to +80
0
C, ATEX II 1 G D (CENELEC) (GOST GGTN Ex i Intrinsically Safe IIC)
15
(3400MD)
IECEx Explosionproof
16
IECEx Intrinsically Safe
21
ATEX:
Explosion Proof: II2G Ex d IIB+H
2
T5; II2D Ex tD A21 T
amb
-40
0
C to +80
0
C
Intrinsically Save: II1G Ex ia IIC, T4 T
amb
-40
0
C to +85
0
C, T5 T
amb
-40
0
C to +55
0
C
II1D Ex iaD 20 T95
0
C -40
0
C to + 80
0
C
Nonincendive: II3G Ex nL nA IIC, T4 T
amb
-40
0
C to +85
0
C, T5 T
amb
-40
0
C to +55
0
C
II3D Ex tD A22 T95
0
C -40
0
C to + 80
0
C
28
(3200MD)
KOSHA*
Shaft
DD 316 Stainless Steel Shaft (Valtek Standard)
D6
D6
NAMUR 316 Stainless Steel (VDI/VDE 3845)
N6
Conduit
Connections
1/2" NPT
E
M
M20
M
Action
Four-way (Double-Acting)
04
4V
Three-way (Single-Acting)
03
Four-way Vented (Double-Acting)
4V
Three-way Vented (Single-Acting)
3V
Temperature
Low Temperature (-40°F to 176°F; -40°C to 80°C)
40
40
Gauges
SS with brass internals, psi (bar/kPa) (Valtek Standard)
OG
KS
SS with SS internals, psi (bar/kPa)
OS
SS with brass internals, psi (kg/cm2 )
KG
SS with SS internals, psi (kg/cm2 ) KS
KS
No Gauges
U
Special Options
No special options
OO
OF
4-20 mA Position Feedback
OF
Remote Mount Feedback (Only Available with Certi cation Option 14)
RM
Fail Option Feedback*
SF
For each category, select the code for one of the options.
* Contact factory before specifying this option