Changing Alarm Set Points
EchoPod
®
sensor models with relays have (1-4) channels. If after accessing the MENU, ALARMS appears in
the display, then at least (1) relay is configured as an alarm. The alarm settings may be in any combination of
LOW and/or HIGH alarms (such as 4-HIGH or 1-LOW & 3-HIGH or 2-LOW & 2-HIGH).
Note:
Prior to making
any changes, write down all existing set point values. The example below highlights a 2-LOW and 2-HIGH
alarm operation with (4) set points. Use the following steps to change your alarm settings.
1.
Hold
SELECT
for 5 seconds to enter the MENU.
2.
Press
SELECT
when ALARMS appears.
3.
Press
SELECT
when the set point (HIGH2, HIGH1, LOW1, LOW2) you want to change appears.
4.
Press the
UP
and
DOWN
buttons to increase or decrease the set point to the desired value. To scroll
faster, hold SELECT while pressing UP or DOWN.
Note
: Never place a relay set point (HIGH2, HIGH1,
LOW1, LOW2) at the liquid empty or full position.
5.
To enter the set point, hold
SELECT
for 2 seconds.
6.
To change another set point, press
SELECT
when the set point appears.
7.
To exit the MENU, press
SELECT
when RUN appears.