Changing Alarm Set Points 

 
EchoPod

®

 sensor models with relays have (1-4) channels.  If after accessing the MENU, ALARMS appears in 

the display, then at least (1) relay is configured as an alarm.  The alarm settings may be in any combination of 
LOW and/or HIGH alarms (such as 4-HIGH or 1-LOW & 3-HIGH or 2-LOW & 2-HIGH).  

Note:

 Prior to making 

any changes, write down all existing set point values.  The example below highlights a 2-LOW and 2-HIGH 
alarm operation with (4) set points.  Use the following steps to change your alarm settings. 

 

 

 

 

1.

 

Hold 

SELECT

 for 5 seconds to enter the MENU. 

 

2.

 

Press 

SELECT

 when ALARMS appears. 

 

3.

 

Press 

SELECT

 when the set point (HIGH2, HIGH1, LOW1, LOW2) you want to change appears. 

 

4.

 

Press the 

UP

 and 

DOWN

 buttons to increase or decrease the set point to the desired value.  To scroll 

faster, hold SELECT while pressing UP or DOWN. 

Note

: Never place a relay set point (HIGH2, HIGH1, 

LOW1, LOW2) at the liquid empty or full position. 

 

5.

 

To enter the set point, hold 

SELECT

 for 2 seconds. 

 

6.

 

To change another set point, press 

SELECT

 when the set point appears.  

 

7.

 

To exit the MENU, press 

SELECT

 when RUN appears. 

 

 

Summary of Contents for PodView LI40 Series

Page 1: ...e Inc 10500 Humbolt Street Los Alamitos CA 90720 p 562 598 3015 f 562 431 8507 w flowline com QS204260 Rev B 2016 Flowline Inc All Rights Reserved Made in USA LI40 Series Quick Start PodView Level Ind...

Page 2: ...you for purchasing PodView The indicator provides a LCD display and push button interface with an EchoPod sensor This Quick Start includes everything you ll need to get the indicator up and running CO...

Page 3: ...e in the panel for the cable and threaded nipple 2 Drill 1 small 0 25 6 4mm diameter hole 0 83 21 1mm below the large hole that will prevent the installed indicator from rotating off center 3 From the...

Page 4: ...dView to the corresponding Green and White wires of EchoPod Note Isolate the Green and White wires from active power to prevent a short of the configuration circuit Electrical Connections Usage and Sa...

Page 5: ...Up Down Buttons Used to increase or decrease a set point value Note To increase the scrolling speed hold down the SELECT button while holding down the UP or DOWN button Select Button Used to enter the...

Page 6: ...G 1 ON and 1 OFF set point Use the following steps to change your simplex or duplex pump control settings Automatic Empty Operation Automatic Fill Operation 1 Hold SELECT for 5 seconds to enter the ME...

Page 7: ...ation with 4 set points Use the following steps to change your alarm settings 1 Hold SELECT for 5 seconds to enter the MENU 2 Press SELECT when ALARMS appears 3 Press SELECT when the set point HIGH2 H...

Page 8: ...lined above 2 have been subjected to electrical mechanical or chemical damage due to improper accidental or negligent use 3 have been modified or altered 4 anyone other than service personnel authoriz...

Reviews: