QS300820 Rev A2
7
|
#3 - SETTING THE HEIGHT (SENSOR HEIGHT OR 4mA) AND FILL-HEIGHT (FILL-H OR 20mA)
This setting customizes the reading for your installation. Follow these instructions to set the height and fill
height for your tank:
1) In TOP-LEVEL MENU mode, select
TANK
.
2) Select
HEIGHT
.
3) Use the UP and DOWN buttons, set the
HEIGHT of your tank.
4) To enter the value, press and hold OK for 5
seconds and release.
SAVED
will display.
HEIGHT is now set.
5) Select
FILL-H
.
6) Use the UP and DOWN buttons, set the Fill-
H of your tank.
7) To enter the value, press and hold OK for 5
seconds and release.
SAVED
will display.
FILL-H is now set.
8) Select
EXIT
by pressing OK to return to the TOP-LEVEL MENU.
9) Select
RUN
by pressing OK to return to Operational Mode.
Note:
The Height (4mA) and Fill Height (20mA) settings also determine the 4 to 20 mA current span.
#4 - HOW TO SELECT FAIL-SAFE CURRENT OUTPUT (LOST)
In the event the transmitter does not receive an
echo, the Fail-Safe Current Output or
LOST
setting can be set to output a current of
4mA
,
20mA, 21mA, 22mA
or
HOLD
(last known value).
During fail-safe, the display will read
LOST
.
1) In TOP-LEVEL MENU mode, select
SAFE
.
2) Select
4mA
,
20mA, 21mA, 22mA
or
HOLD
.
a. Press and hold OK on the selected
setting for 2 seconds then release.
3) Select
EXIT
to return to the TOP-LEVEL
MENU.
TROUBLESHOOTING
If you face any issues not addressed in this Quick Start, please refer to the EchoTouch
®
Manual located on
Flowline’s website at www.flowline.com.