30
MN310125 Rev A2
WebCal
®
Appendix
Section Six
This section of WebCal
®
is where you select the sensor configuration settings. Start from the top and work to
the bottom, choosing the selections that are applicable to your configuration. “
Not Applicable
” will
automatically show when a selection doesn’t apply to your configuration settings, and you may move on. All
configuration settings must be selected or have “
Not Applicable
” before you can continue to the next step.
SENSOR CONFIGURATION
Note:
Right click on any
item to open the help menu.
Note:
To reset the
configuration table, press
the Clear Screen button.
NUMBER OF PUMPS
This feature allows you to select the number of pumps or valves used
with EchoPod
®
. This setting activates the control capabilities of one or
two relays. Control relays are often referred to as latching relays.
o
Switch/Alarms Only –
The relays will be standard single point
non-latching relays. Use this setting for high and/or low alarms.
o
1-Pump/Valve
– One relay will be configured as a control or
latching relay (relay will have a start level and a separate stop
level). Use this setting to control one pump or valve for
automatic filling or emptying of a tank.
o
2-Pumps/Valves
– Two relays are configured as control or
latching relays. Each relay will have a unique start level and a
common stop level. Use this setting to control two pumps or
valves for automatic filling or emptying of a tank.
o
4-20mA Transmitter Only
– This setting will disengage all of
the relays. Use this function if you are not using any relays and
using only the 4-20 mA current output.
o
Independent Relays
– This setting will override the
Switch/Alarm Configuration and allow all 4 relays to be set
independent of the other relays. Each relay will have its own
unique ON and OFF setting (see below).