www.flowair.com |9
3.5. ELIS T-W-150 2R
PT
Qw
Δpw
Tp2
PT
Qw
Δpw
Tp2
Tp1
V
kW
l/h
kPa
°C
kW
l/h
kPa
°C
°C m
3
/h
Tw1 / Tw2 = 90/70
o
C
Tw1 / Tw2 = 80/60
o
C
0
2
9
0
0
/3
3
0
0
/3
7
0
0
35,8/38,8/41,5
1581/1712/1833
4,5/5,2/5,9
37/35/33
30,5/33/35,4
1342/1452/1555 3,42/3,96/4,48
31/30/28
5
33,5/36,2/38,8
1478/1599/1713
3,97/4,59/5,2
39/37/36
28,2/30,5/32,6
1238/1339/1434 2,96/3,41/3,87
34/32/31
10
31,4/33,7/36,1
1374/1487/1592
3,48/4,02/4,6
42/40/39
25,8/27,9/29,9
1133/1226/1313 2,52/2,91/3,29
36/35/34
15
28,8/31,1/33,4
1270/1375/1472
3,01/3,48/4
44/43/41
23,4/25,3/27,1
1029/1113/1191 2,11/2,44/2,76
39/37/36
20
26,4/28,6/30,6
1167/1262/1351
2,58/2,98/3,4
46/45/44
21/22,7/24,3
924/999/1069
1,74/2/2,27
41/40/39
Tw1 / Tw2 = 70/50
o
C
Tw1 / Tw2 = 60/40
o
C
0
2
9
0
0
/3
3
0
0
/3
7
0
0
25,2/27,2/29,2
1101/1192/1276
2,47/2,85/3,22
26/24/23
19,7/21,3/22,8
858/928/994
1,63/1,88/2,1
20/19/18
5
22,8/24,6/26,4
997/1078/1155
2,06/2,38/2,69
28/27/26
17,2/18,6/20
751/813/871
1,28/1,48/1,67
23/22/21
10
20,4/22/23,6
891/964/1032
1,68/1,94/2,2
31/30/29
14,7/16/17,1
642/696/746
0,97/1,12/1,27
25/24/24
15
17,9/19,4/20,8
785/849/909
1,34/1,54/1,75
33/32/31
12,2/13,2/14,2
531/576/618
0,69/0,8/0,9
27/27/26
20
15,5/16,8/17,9
677/733/785
1,03/1,18/1,34
36/35/34
9,4/10,3/11,1
412/449/483
0,44/0,51/0,58
29/29/29
3.6. ELIS T-W-200 2R
PT
Qw
Δpw
Tp2
PT
Qw
Δpw
Tp2
Tp1
V
kW
l/h
kPa
°C
kW
l/h
kPa
°C
°C m
3
/h
Tw1 / Tw2 = 90/70
o
C
Tw1 / Tw2 = 80/60
o
C
0
2
8
0
0
/3
9
0
0
/4
9
0
0
39,8/49,2/56,5
1758/2170/2494
6,29/9,25/11,95
42/37/34
34,1/42,1/48,4
1500/1852/2127 4,85/7,11/9,17
36/32/29
5
37,3/46/52,9
1645/2031/2334
5,57/8,2/10,58
44/40/37
31,6/39/44,8
1388/1712/1967 4,21/6,17/7,94
38/35/32
10
34,7/42,9/49,3
1533/1892/2174
4,9/7,2/9,28
46/42/40
29/35,8/41,1
1275/1572/1806
3,61/5,28/6,8
40/37/35
15
32,2/39,7/45,6
1421/1753/2014
4,27/6,26/8,07
49/45/42
26,4/32,6/37,4
1161/1432/1645 3,05/4,46/5,73
43/39/37
20
29,7/36,6/42
1309/1614/1854
3,67/5,38/6,93
51/47/45
23,9/29,4/33,7
1048/1292/1483 2,53/3,69/4,75
45/42/40
Tw1 / Tw2 = 70/50
o
C
Tw1 / Tw2 = 60/40
o
C
0
2
8
0
0
/3
9
0
0
/4
9
0
0
28,4/35,1/40,3
1244/1534/1762
3,56/5,21/6,7
30/27/24
22,6/27,9/32
985/1215/1396
2,43/3,54/4,54
24/21/19
5
25,8/31,9/36,6
1130/1394/1601
3/4,38/5,6
32/29/27
20/24,6/28,3
870/1074/1233
1,95/2,83/3,63
26/24/22
10
23,2/28,6/32,9
1016/1253/1439
2,47/3,61/4,64
34/32/30
17,3/21,4/24,5
754/931/1069
1,51/2,19/2,81
28/26/25
15
20,6/25,4/29,1
902/1111/1276
2/2,91/3,7
37/34/32
14,6/18/20,7
636/786/902
1,11/1,62/2,07
30/29/27
20
18/22,1/25,4
786/968/1111
1,56/2,27/2,91
39/36/35
11,8/14,6/16,8
514/637/732
0,76/1,11/1,43
32/31/30
V
– przepływ powietrza / air flow
PT
– moc grzewcza / heating capacity
Tp1
– temperatura powietrza na wlocie do urządzenia / inlet air temperature
Tp2
– temperatura powietrza na wylocie z urządzenia / outlet air temperaturę
Δpw
– spadek ciśnienia wody w wymienniku / water pressure
Tw1
– temperatura wody na zasilaniu wymiennika /
inlet water temperature
Tw2
– temperatura wody na powrocie z wymiennika /
outlet water temperature
Qw
– strumień przepływu wody grzewczej / heating water stream
Summary of Contents for ELIS G W 150 2R