6
5.
TECHNICAL DATA SLIM E
SLIM E-100
SLIM E-150
SLIM E-200
STEP
III
II
I
III
II
I
III
II
I
Power supply [V/Hz]
3N
~
400/50
1N
~
230/50
Fan power consumption [W]
130
95
80
195
115
95
250
165
110
Fan current consumption [A]
0,5
0,4
0,3
0,8
0,5
0,4
1,0
0,7
0,5
Air volume [m
3
/h]*
1300
950
800
2200
1500
1250
3000
1850
1400
Range [m]*
3,2
2,8
2,1
3,2
2,8
2,1
3,2
2,8
2,1
Acoustic pressure level [dB(A)]** - 3 m
56,5
49
44
55
46
41
58
42
34,5
Acoustic pressure level [dB(A)]** - 5 m
55,5
48
43
54
45
40
57
41
33,5
Acoustic power level [dB(A)]***
71,5
64
59
70
61
56
73
57
49,5
Weight [kg]
15,1
19,6
24,6
IP
20
3N
~
400/50
Heating elements power [kW]
5
9
12
Heating elements current consumption [A]
8,5
13
17,3
Temperature increase (
Δ
T) [°C]
20
22
24
20
26
32
19
29
36
1N
~
230/50
Heating elements power [kW]
2
3
4
Heating elements current consumption [A]
8,5
13
17,3
Temperature increase (
Δ
T) [°C]
4
5
7
6
8
10
6
10
12
* according to ISO 27327-1;
** Acoustic pressure level has been measured in a 1500m
3
space with a medium sound absorption coefficient, directional factor: Q=2;
*** Acoustic power level according to ISO 27327-2;