13
14.
BUILT-IN CONTROL – CONNECTION DIAGRAM SLIM W; SLIM N
❶
Power supply: 1N
~
230V/50Hz (OMY min.3x1,5mm
2
; Protection B4)
❷
SRQ3d
½
”; SRQ2d
½
”
valve with actuator
(OMY min.3x0,75mm
2
)
ADVICE
-
The maximum outer diameter of the cable sleeve is 14.0 mm;
-
The minimum outer diameter of cable sleeve is 4.0 mm;
Maximum wire diameter 4,0 mm
2
.
❸
Motion sensor; to omit/bypass the motion sensor; disconnect and insulate / secure wires from connectors D; D, a cable jumper
(OMY min. 1x1,0 mm
2
) or a door sensor (OMY min. 2x1,0 mm
2
) should be connected in this place;
❹
Heating switch (
I
– heating elements ON ,
O
– heating elements OFF);
❺
Fan step switch (
I
– 1st fan step,
O
– device OFF,
I I
– 3rd fan step).
ADVICE
To connect the 2nd fan step, connect the cable from the 6th connector to the 7th
connector. In this case, the I position on the switch will mean SWITCHING ON the 2nd
fan step.
WARNING
Each time the curtain is turned on by a motion sensor, it operates for a set time (10 s by
default), unless motion is detected in the area covered by the sensor.
PARAMETRY ZAWORÓW SRQ:
- SRQ3d
½
” – Three-way valve
½
” with actuator
- SRQ2d
½
” – Two-way valve
½
” with actuator
Class of protection: IP20
Supply voltage: 230/50 Hz
Max. Medium temperature: + 93oC Max. Operating pressure: 2.1Mpa
SRQ2d 1⁄2 ”Kvs: 3.0 m
3
/h
SRQ3d 1⁄2 ”Kvs: 3.4 m
3
/h
Motor running time: 18 s
A – Return pipe water supply
AB – Valve water supply
B – Exchanger water supply