![Flo Vigaro Instruction Manual Download Page 29](http://html1.mh-extra.com/html/flo/vigaro/vigaro_instruction-manual_2306435029.webp)
29
Alarms
8.1
Medium priority alarms
8.1.1 Pressure too high
Alarm
Actual pressure value too high (C30)
Display
Alarm
Actual value exceeds set target value by 20%
Delay
Cause of alarm present for at least 2 seconds
Acoustic alarm
Medium priority
Visible alarm signal
Yellow LED flashes
Possible cause
Hose system blocked
Deactivate
It is not possible to deactivate the alarm.
Comment
The device switches off automatically.
No further operation possible.
Summary of Contents for Vigaro
Page 1: ...Instruction manual FLO Vigaro Next Generation English Rev 1 0 July 2018 Vigaro from REV 4 15...
Page 3: ...Instruction manual FLO Vigaro Next Generation English July 2018...
Page 4: ......
Page 61: ...61 Notice...
Page 62: ...62 Notice...
Page 64: ...Art Nr 40000245...